HomeMy WebLinkAboutVAIL MARRIOT BALLROOM TAB.PDF TEST, ADJUST AND BALANCE REPORT
PROJECT
VAIL MARRIOTT BALLROOM
#1336
PREPARED FOR
R&H MECHANICAL
REPORT ISSUE DATE
2/6/2018
PREPARED BY
HVAC TAB llc
P.O. BOX 1926
VAIL, CO 81658
PHONE: 970-376-5198
E-MAIL: mrichardson@hvactab.co
HVAC TAB llc
DATE: 1/18/2018
INSTRUMENT
CALIBRATION REPORT
PROJECT : VAIL MARRIOTT BALLROOM PROJECT ALTITUDE: “HG
INSTRUMENT/ SERIAL # APPLICATION DATE OF USE CALIBRATION DATE CALIBRATION DUE DATE
SHORTRIDGE ADM-870C / #W08162 AIR FLOW READINGS 1/18/2018 06/07/2017 06/07/2018
ANEMOMETER #RVA501416001 AIR FLOW READINGS 1/18/2018 06/12/2017 06/12/2018
SHORTRIDGE FLOW HOOD AIF FLOW READINGS 1/18/2018 * *
TH-720 HYGROMETER/ #TH7200950003 AIR TEMP / HUMIDITY NOT USED 06/07/2017 06/07/2018
PITOT TUBE 18” PRES. READINGS 1/18/2018 N/A N/A
PITOT TUBE 24” PRES. READINGS NOT USED N/A N/A
PITOT TUBE 36” PRES. READINGS NOT USED N/A N/A
PITOT TUBE 48” PRES. READINGS NOT USED NA NA
SHIMPO TACHOMETER / #C105B0010 RPM READINGS 1/18/2018 06/07/2017 06/07/2018
FLUKE 375 / #21290229 VOLT / AMP 1/18/2018 06/08/2017 06/08/2018
SHORTRIDGE HDM-250/ #W11037 WATER PRES. READINGS 1/18/2018 01/18/2017 01/18/2018
ASCROFT / 0-100 PSI / #DO68332-06 WATER PRES. READINGS NOT USED * *
FLUKE 52 II THERMOMETER / 99780167 TEMP. READINGS 1 /18/2018 06/28/2017 06/28/2018
REFRACTOMETER RHA-100 / #RHA-
100
GLYCOL % READINGS NOT USED N/A N/A
* CHECKED TO CALIBRATED METER
REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE:
NOTES:
FILTERS 2 EACH 16 X 20 X 2"
HVAC TAB llc
DATE: 1/18/2018
AIR APPARATUS
TEST REPORT
AIR HANDLER UNIT DATA
MANUFACTURER ENVIRO TEC
MODEL AHU171005-09
SERIAL 6MEM000364
FAN TYPE CENTRIFUGAL
RATING/OUTLET TOTAL 2000CFM@0.5"ESP
MIN OSA CFM 450 CFM
MOTOR NAMEPLATE DATA
MANUFACTURER -
HP R.P.M. 3/4 -
PHASE FRAME 1 -
S.F. TYPE - -
VOLTS AMPS 208 5.2
THERMALLY PROTECTED -
DRIVE DATA
MOTOR DRIVE 1 VP 4 1/8"
MOTOR BORE 5/8"
FAN DRIVE 1 FP 5 3/8" H
FAN BORE 3/4" H
NO. BELTS & SIZE 1 / A 39
ROTATION CORRECT
CENTERLINE 13 1/16" MOTOR ADJ +3 -0
PULLEY
SPEED + 1 TURN
STARTER DATA
MANUFACTURER NONE
MODEL NONE
SIZE/THERMAL NO. NONE
RANGE (AMPS) NONE
SET AT (AMPS) NONE
REQ. THERMAL NONE
RATING (AMPS) NONE
TEST DATA INITIAL FINAL
FAN R.P.M. 1133 1137
VOLTAGE 208 208
AMPERAGE 5.0 5.3
PAGE:
AIRFLOW DATA
SUPPLY CFM 1766
OSA CFM 475
RETURN CFM 1291
PROJECT: VAIL MARRIOTT BALLROOM SYSTEM: FC-1
COIL CW
HW
F I
L T
E R
-0.15" 0.24" -0.69" -0.33"
NOTES:
FILTERS 2 EACH 16 X 20 X 2"
HVAC TAB llc
DATE: 1/18/2018
AIR APPARATUS
TEST REPORT
AIR HANDLER UNIT DATA
MANUFACTURER ENVIRO TEC
MODEL AHU171005-09
SERIAL 6MEM000363
FAN TYPE CENTRIFUGAL
RATING/OUTLET TOTAL 2000CFM@0.5"ESP
MIN OSA CFM 450 CFM
MOTOR NAMEPLATE DATA
MANUFACTURER -
HP R.P.M. 3/4 -
PHASE FRAME 1 -
S.F. TYPE - -
VOLTS AMPS 208 5.2
THERMALLY PROTECTED -
DRIVE DATA
MOTOR DRIVE 1 VP 4 1/8"
MOTOR BORE 5/8"
FAN DRIVE 1 FP 5 3/8" H
FAN BORE 3/4" H
NO. BELTS & SIZE 1 / A 39
ROTATION CORRECT
CENTERLINE 13 1/16" MOTOR ADJ +3 -0
PULLEY
SPEED + 1 TURN
STARTER DATA
MANUFACTURER NONE
MODEL NONE
SIZE/THERMAL NO. NONE
RANGE (AMPS) NONE
SET AT (AMPS) NONE
REQ. THERMAL NONE
RATING (AMPS) NONE
TEST DATA INITIAL FINAL
FAN R.P.M. - 1178
VOLTAGE 209 209
AMPERAGE 3.8 5.0
PAGE:
AIRFLOW DATA
SUPPLY CFM 1553
OSA CFM 436
RETURN CFM 1117
PROJECT: VAIL MARRIOTT BALLROOM SYSTEM: FC-2
COIL CW
HW
F I
L T
E R
-0.02" 0.22" -0.56" -0.22"
NOTES:
FILTERS 2 EACH 16 X 20 X 2" NA DENOTES NO ACCESS
HVAC TAB llc
DATE: 1/18/2018
AIR APPARATUS
TEST REPORT
AIR HANDLER UNIT DATA
MANUFACTURER ENVIRO TEC
MODEL AHU171005-09
SERIAL 6MEM000365
FAN TYPE CENTRIFUGAL
RATING/OUTLET TOTAL 2000CFM@0.5"ESP
MIN OSA CFM 450 CFM
MOTOR NAMEPLATE DATA
MANUFACTURER -
HP R.P.M. 3/4 -
PHASE FRAME 1 -
S.F. TYPE - -
VOLTS AMPS 208 5.2
THERMALLY PROTECTED -
DRIVE DATA
MOTOR DRIVE 1 VP NA
MOTOR BORE NA
FAN DRIVE 1 FP NA H
FAN BORE 3/4" H
NO. BELTS & SIZE 1 / NA
ROTATION CORRECT
CENTERLINE - MOTOR ADJ - PULLEY SPEED-
STARTER DATA
MANUFACTURER NONE
MODEL NONE
SIZE/THERMAL NO. NONE
RANGE (AMPS) NONE
SET AT (AMPS) NONE
REQ. THERMAL NONE
RATING (AMPS) NONE
TEST DATA INITIAL FINAL
FAN R.P.M. NA NA
VOLTAGE 208 208
AMPERAGE 4.6 4.6
PAGE:
AIRFLOW DATA
SUPPLY CFM 1720
OSA CFM 371
RETURN CFM 1349
PROJECT: VAIL MARRIOTT BALLROOM SYSTEM: FC-3
COIL CW
HW
F I
L T
E R
-0.11" 0.11" -0.56" -0.23"
SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES
NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM
FC-1 1 CD 24/24 500 280 336 NO DAMPER
2 CD 24/24 500 364 464 NO DAMPER
3 CD 24/24 500 382 492 NO DAMPER
4 CD 24/24 500 374 474 NO DAMPER
2000 1400 1766 TOTAL
FC-2 1 CD 24/24 500 234 197 NO DAMPER
2 CD 24/24 500 402 314 NO DAMPER
3 CD 24/24 500 246 570 NO DAMPER
4 CD 24/24 500 204 472 NO DAMPER
2000 1086 1553 TOTAL
FC-3 1 CD 24/24 500 388 406 NO DAMPER
2 CD 24/24 500 300 430 NO DAMPER
3 CD 24/24 500 396 432 NO DAMPER
4 CD 24/24 500 412 452 NO DAMPER
2000 1496 1720 TOTAL
NOTES:
HVAC TAB llc
DATE: 1/18/2018
AIR TERMINAL
TEST REPORT
PAGE:
PROJECT: VAIL MARRIOTT BALLROOM SYSTEM: FC-1 / FC-2 / FC-3
HVAC TAB llc
DATE: 1/18/2018
FLOW METER DESIGN MEASURED
LOCATION TYPE SIZE DESIGN P
DESIGN
GPM FINAL P
VALVE POSITION
% OPEN
FINAL GPM
FC-1 HW TACO 1" 8.1 41.4 65% 8.2
FC-1 CW TACO 1 1/2" 16.0 4.1 100% 9.0
FC-2 HW TACO 1' 8.1 41.0 70% 8.2
FC-2 CW TACO 1 1/2" 16.0 3.7 100% 8.5
FC-3 HW TACO 1" 8.1 41.2 70% 8.2
FC-3 CW TACO 1 1/2" 16.0 3.2 100% 8.0
CW EWT 41.5 DEGREES
BALANCE VALVE
TEST REPORT
PROJECT: VAIL MARRIOTT BALLROOM
PAGE:
NOTES:
SYSTEM:: FC-1 / FC-2 / FC-3
PAGE: