HomeMy WebLinkAboutVAIL MARRIOT BALLROOM TAB.PDF TEST, ADJUST AND BALANCE REPORT PROJECT VAIL MARRIOTT BALLROOM #1336 PREPARED FOR R&H MECHANICAL REPORT ISSUE DATE 2/6/2018 PREPARED BY HVAC TAB llc P.O. BOX 1926 VAIL, CO 81658 PHONE: 970-376-5198 E-MAIL: mrichardson@hvactab.co HVAC TAB llc DATE: 1/18/2018 INSTRUMENT CALIBRATION REPORT PROJECT : VAIL MARRIOTT BALLROOM PROJECT ALTITUDE: “HG INSTRUMENT/ SERIAL # APPLICATION DATE OF USE CALIBRATION DATE CALIBRATION DUE DATE SHORTRIDGE ADM-870C / #W08162 AIR FLOW READINGS 1/18/2018 06/07/2017 06/07/2018 ANEMOMETER #RVA501416001 AIR FLOW READINGS 1/18/2018 06/12/2017 06/12/2018 SHORTRIDGE FLOW HOOD AIF FLOW READINGS 1/18/2018 * * TH-720 HYGROMETER/ #TH7200950003 AIR TEMP / HUMIDITY NOT USED 06/07/2017 06/07/2018 PITOT TUBE 18” PRES. READINGS 1/18/2018 N/A N/A PITOT TUBE 24” PRES. READINGS NOT USED N/A N/A PITOT TUBE 36” PRES. READINGS NOT USED N/A N/A PITOT TUBE 48” PRES. READINGS NOT USED NA NA SHIMPO TACHOMETER / #C105B0010 RPM READINGS 1/18/2018 06/07/2017 06/07/2018 FLUKE 375 / #21290229 VOLT / AMP 1/18/2018 06/08/2017 06/08/2018 SHORTRIDGE HDM-250/ #W11037 WATER PRES. READINGS 1/18/2018 01/18/2017 01/18/2018 ASCROFT / 0-100 PSI / #DO68332-06 WATER PRES. READINGS NOT USED * * FLUKE 52 II THERMOMETER / 99780167 TEMP. READINGS 1 /18/2018 06/28/2017 06/28/2018 REFRACTOMETER RHA-100 / #RHA- 100 GLYCOL % READINGS NOT USED N/A N/A * CHECKED TO CALIBRATED METER REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE: NOTES: FILTERS 2 EACH 16 X 20 X 2" HVAC TAB llc DATE: 1/18/2018 AIR APPARATUS TEST REPORT AIR HANDLER UNIT DATA MANUFACTURER ENVIRO TEC MODEL AHU171005-09 SERIAL 6MEM000364 FAN TYPE CENTRIFUGAL RATING/OUTLET TOTAL 2000CFM@0.5"ESP MIN OSA CFM 450 CFM MOTOR NAMEPLATE DATA MANUFACTURER - HP R.P.M. 3/4 - PHASE FRAME 1 - S.F. TYPE - - VOLTS AMPS 208 5.2 THERMALLY PROTECTED - DRIVE DATA MOTOR DRIVE 1 VP 4 1/8" MOTOR BORE 5/8" FAN DRIVE 1 FP 5 3/8" H FAN BORE 3/4" H NO. BELTS & SIZE 1 / A 39 ROTATION CORRECT CENTERLINE 13 1/16" MOTOR ADJ +3 -0 PULLEY SPEED + 1 TURN STARTER DATA MANUFACTURER NONE MODEL NONE SIZE/THERMAL NO. NONE RANGE (AMPS) NONE SET AT (AMPS) NONE REQ. THERMAL NONE RATING (AMPS) NONE TEST DATA INITIAL FINAL FAN R.P.M. 1133 1137 VOLTAGE 208 208 AMPERAGE 5.0 5.3 PAGE: AIRFLOW DATA SUPPLY CFM 1766 OSA CFM 475 RETURN CFM 1291 PROJECT: VAIL MARRIOTT BALLROOM SYSTEM: FC-1 COIL CW HW F I L T E R -0.15" 0.24" -0.69" -0.33" NOTES: FILTERS 2 EACH 16 X 20 X 2" HVAC TAB llc DATE: 1/18/2018 AIR APPARATUS TEST REPORT AIR HANDLER UNIT DATA MANUFACTURER ENVIRO TEC MODEL AHU171005-09 SERIAL 6MEM000363 FAN TYPE CENTRIFUGAL RATING/OUTLET TOTAL 2000CFM@0.5"ESP MIN OSA CFM 450 CFM MOTOR NAMEPLATE DATA MANUFACTURER - HP R.P.M. 3/4 - PHASE FRAME 1 - S.F. TYPE - - VOLTS AMPS 208 5.2 THERMALLY PROTECTED - DRIVE DATA MOTOR DRIVE 1 VP 4 1/8" MOTOR BORE 5/8" FAN DRIVE 1 FP 5 3/8" H FAN BORE 3/4" H NO. BELTS & SIZE 1 / A 39 ROTATION CORRECT CENTERLINE 13 1/16" MOTOR ADJ +3 -0 PULLEY SPEED + 1 TURN STARTER DATA MANUFACTURER NONE MODEL NONE SIZE/THERMAL NO. NONE RANGE (AMPS) NONE SET AT (AMPS) NONE REQ. THERMAL NONE RATING (AMPS) NONE TEST DATA INITIAL FINAL FAN R.P.M. - 1178 VOLTAGE 209 209 AMPERAGE 3.8 5.0 PAGE: AIRFLOW DATA SUPPLY CFM 1553 OSA CFM 436 RETURN CFM 1117 PROJECT: VAIL MARRIOTT BALLROOM SYSTEM: FC-2 COIL CW HW F I L T E R -0.02" 0.22" -0.56" -0.22" NOTES: FILTERS 2 EACH 16 X 20 X 2" NA DENOTES NO ACCESS HVAC TAB llc DATE: 1/18/2018 AIR APPARATUS TEST REPORT AIR HANDLER UNIT DATA MANUFACTURER ENVIRO TEC MODEL AHU171005-09 SERIAL 6MEM000365 FAN TYPE CENTRIFUGAL RATING/OUTLET TOTAL 2000CFM@0.5"ESP MIN OSA CFM 450 CFM MOTOR NAMEPLATE DATA MANUFACTURER - HP R.P.M. 3/4 - PHASE FRAME 1 - S.F. TYPE - - VOLTS AMPS 208 5.2 THERMALLY PROTECTED - DRIVE DATA MOTOR DRIVE 1 VP NA MOTOR BORE NA FAN DRIVE 1 FP NA H FAN BORE 3/4" H NO. BELTS & SIZE 1 / NA ROTATION CORRECT CENTERLINE - MOTOR ADJ - PULLEY SPEED- STARTER DATA MANUFACTURER NONE MODEL NONE SIZE/THERMAL NO. NONE RANGE (AMPS) NONE SET AT (AMPS) NONE REQ. THERMAL NONE RATING (AMPS) NONE TEST DATA INITIAL FINAL FAN R.P.M. NA NA VOLTAGE 208 208 AMPERAGE 4.6 4.6 PAGE: AIRFLOW DATA SUPPLY CFM 1720 OSA CFM 371 RETURN CFM 1349 PROJECT: VAIL MARRIOTT BALLROOM SYSTEM: FC-3 COIL CW HW F I L T E R -0.11" 0.11" -0.56" -0.23" SYSTEM TERMINAL DESIGN INITIAL FINAL NOTES NO TYPE SIZE AK VEL CFM VEL CFM VEL CFM FC-1 1 CD 24/24 500 280 336 NO DAMPER 2 CD 24/24 500 364 464 NO DAMPER 3 CD 24/24 500 382 492 NO DAMPER 4 CD 24/24 500 374 474 NO DAMPER 2000 1400 1766 TOTAL FC-2 1 CD 24/24 500 234 197 NO DAMPER 2 CD 24/24 500 402 314 NO DAMPER 3 CD 24/24 500 246 570 NO DAMPER 4 CD 24/24 500 204 472 NO DAMPER 2000 1086 1553 TOTAL FC-3 1 CD 24/24 500 388 406 NO DAMPER 2 CD 24/24 500 300 430 NO DAMPER 3 CD 24/24 500 396 432 NO DAMPER 4 CD 24/24 500 412 452 NO DAMPER 2000 1496 1720 TOTAL NOTES: HVAC TAB llc DATE: 1/18/2018 AIR TERMINAL TEST REPORT PAGE: PROJECT: VAIL MARRIOTT BALLROOM SYSTEM: FC-1 / FC-2 / FC-3 HVAC TAB llc DATE: 1/18/2018 FLOW METER DESIGN MEASURED LOCATION TYPE SIZE DESIGN P DESIGN GPM FINAL P VALVE POSITION % OPEN FINAL GPM FC-1 HW TACO 1" 8.1 41.4 65% 8.2 FC-1 CW TACO 1 1/2" 16.0 4.1 100% 9.0 FC-2 HW TACO 1' 8.1 41.0 70% 8.2 FC-2 CW TACO 1 1/2" 16.0 3.7 100% 8.5 FC-3 HW TACO 1" 8.1 41.2 70% 8.2 FC-3 CW TACO 1 1/2" 16.0 3.2 100% 8.0 CW EWT 41.5 DEGREES BALANCE VALVE TEST REPORT PROJECT: VAIL MARRIOTT BALLROOM PAGE: NOTES: SYSTEM:: FC-1 / FC-2 / FC-3 PAGE: