HomeMy WebLinkAbout2654 marriott - vail cbc report.pdfCERTIFIED BALANCING AND COMMISSIONING, LLC. I Testing, Adjusting and Balancing Report Project Vail Marriott Address 715 Lionshead Circle | Vail, CO 81657 Architect NEO Studio Mechanical Engineer BA Consultants Contractor GAR Mechanical Balancing Supervisors Greg Barnes Date May 11, 2018 Job Number 2654 CERTIFIED BALANCING AND COMMISSIONING, LLC. II ABBREVIATION INDEX AHU: Air Handling Unit Motor FLA: Full Load Amperage RTU: Roof Top Unit S.F.: Service Factor MAU: Make Up Air Unit P.F.: Power Factor FCU: Fan Coil Unit Nom. Eff.: Nominal Efficiency CRAC: Computer Room Air Conditioning Unit RPM: Revolutions per Minute VAV: Variable Air Volume FPB: Fan Powered Box K Factor: Correction Factor T1: Terminal 1 T2: Terminal 2 T3: Terminal 3 AK: Area Correction OD: Outside Diameter CUH: Cabinet Unit Heater UH: Unit Heater ERV: Energy Recovery Ventilator TDH: Total Dynamic Head ERU: Energy Recovery Unit PSI: Pounds per Square Inch EF: Exhaust Fan BV: Balance Valve KEF: Kitchen Exhaust Fan CS: Circuit Setter SF: Supply Fan Valve D.P.: Discharge Pressure RF: Return Fan Valve S.P.: Suction Pressure TF: Transfer Fan Diff.: Differential SEF: Smoke Exhaust Fan Design D.P.: Design Differential Pressure SPF: Stairwell Pressurization Fan Actual D.P.: Recorded Differential Pressure SP: Static Pressure Ind.Imp.Dia.: Indicated Impeller Diameter TSP: Total Static Pressure in.wc.: Inches of Water ESP: External Static Pressure HW: Heating Water VP: Velocity Pressure CHW: Cooling Water SA: Supply Air CW: Condenser Water RA: Return Air HX: Heat Exchanger OSA: Outside Air DX: Direct Expansion OA: Outside Air EAT: Entering Air Temperature MA: Mixed Air LAT: Leaving Air Temperature SD: Supply Diffuser EWT: Entering Water Temperature CD: Ceiling Diffuser LWT: Leaving Water Temperature SWD: Sidewall Diffuser ER: Exhaust Register MVD: Manual Volume Damper RG: Return Grille OBD: Opposed Blade Damper CFM: Cubic Feet Per Minute NAC: No Access FPM: Feet Per Minute NG: Not Given NIC: Not in Contract E: Existing CERTIFIED BALANCING AND COMMISSIONING, LLC. III Method of Balancing: Supply, Return and Exhaust diffusers, grilles and registers were measured with an Alnor Balometer EBT-721, which includes the flow hood, velgrid, pitot tube and airfoil. Heating and Chilled water flow rates were measured with an Alnor Hydronic Manometer HM-680 by obtaining pressure measurements. RPM was measured with a Shimpo tachometer. Amperage and Voltage readings were taken with a Fluke 930 meter. Instrumentation: Digital Manometer Alnor Balometer EBT-721 Flow hood Alnor Balometer EBT-721 Digital Pressure Gage Alnor Hydronic Manometer HM-680 Tachometer Shimpo Digital Volt-Amp Meter Fluke 930 Thermometer Alnor Balometer EBT-721 Warranty Information: This project was completed per TABB Procedural Standards. The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the TABB Procedural Standards for testing, adjusting, and balancing environmental systems. Any variances from design quantities, which exceed TABB tolerances, are noted in the Test-Adjust- Balance Report Project Summary. If a Test-Adjust-Balance Report Project Summary is not issued directly following this cover page, all measurements met the design requirements as specified by the design mechanical engineer. This project has a one-year guarantee on all Testing, Adjusting & Balancing from the date listed on this cover page. Greg Barnes Owner/ TABB Supervisor greg@certtab.com 720-201-6274 CERTIFIED BALANCING AND COMMISSIONING, LLC. IV Project Summary 1. Individual Notes, Explanations, and Deficiencies, if exist, are shown underneath the associated equipment. Energy Recovery UnitPROJECT:LOCATION:MARRIOTT - VAILVAIL, CO 2654PROJECT #: DATE:CONTACT: AUTHOR: 5/11/2018Daniel Takacs CBC REPORT DEPT. Tested By:Daniel Takacs Date:5/11/2018 SYSTEM/UNIT: ERV-01 Log:ERV-01 5/11/2018 Daniel Takacs AIRFLOWS VERIFIED AT INTAKE/DISCHARGE ON EXTERIOR WALL. ERV-01 5/11/2018 Daniel Takacs UNABLE TO OBTAIN PRESSURE DATA DUE TO LIMITED ACCESS, FINISHED CABINET, AND FLEX DUCTWORK. VERIFIED OPERATION. ERV-01 5/11/2018 Daniel Takacs NO SAFE ACCESS TO GATHER VOLT AND AMP READINGS. Unit Data Unit Manufacturer DAIKIN Unit Model Number VAM600GVJU Unit Serial Number F000958 Starter Data ERV-01/Exhaust Fan Starter Manufacturer THERMALLY PROTECTED ERV-01/Supply Fan Starter Manufacturer THERMALLY PROTECTED Test Data S/Fan Design Airflow 520 CFM S/Fan Actual Airflow 565 CFM E/Fan Design Airflow 520 CFM E/Fan Actual Airflow 540 CFM Motor Data ERV-01/Exhaust Fan Motor HP 3/8 HP Motor Rated Volts 208/230 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.7 Amps ERV-01/Supply Fan Motor HP 3/8 HP Motor Rated Volts 208/230 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.7 Amps Certified Balancing and Commissioning Page 1 of 2 “All I have in this world is my faith and my word, I don’t break them for anyone” Energy Recovery UnitPROJECT:LOCATION:MARRIOTT - VAILVAIL, CO 2654PROJECT #: DATE:CONTACT: AUTHOR: 5/11/2018Daniel Takacs CBC REPORT DEPT. Tested By:Daniel Takacs Date:5/11/2018 SYSTEM/UNIT: ERV-02 Log:ERV-02 5/11/2018 Daniel Takacs UNABLE TO OBTAIN PRESSURE DATA DUE TO LIMITED ACCESS, FINISHED CABINET, AND FLEX DUCTWORK. VERIFIED OPERATION. ERV-02 5/11/2018 Daniel Takacs NO SAFE ACCESS TO GATHER VOLT AND AMP READINGS. ERV-02 5/11/2018 Daniel Takacs AIRFLOWS VERIFIED AT INTAKE/DISCHARGE ON EXTERIOR WALL. Unit Data Unit Manufacturer DAIKIN Unit Model Number VAM600GVJU Unit Serial Number F000957 Starter Data ERV-02/Exhaust Fan Starter Manufacturer THERMALLY PROTECTED ERV-02/Supply Fan Starter Manufacturer THERMALLY PROTECTED Test Data S/Fan Design Airflow 520 CFM S/Fan Actual Airflow 555 CFM E/Fan Design Airflow 520 CFM E/Fan Actual Airflow 545 CFM Motor Data ERV-02/Exhaust Fan Motor HP 3/8 HP Motor Rated Volts 208/230 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.7 Amps ERV-02/Supply Fan Motor HP 3/8 HP Motor Rated Volts 208/230 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 3.7 Amps Certified Balancing and Commissioning Page 2 of 2 “All I have in this world is my faith and my word, I don’t break them for anyone”