HomeMy WebLinkAboutE18-0085_Approved Plans_1526507634.pdfOwner Name: Alonzo Residence
Location: The Lion, 701 W Lionshead Cir, Unit E209, Vail
Electrical Contractor: Native Electric, Inc.
Phone No. for Electrical Contractor: (970) 328-1293
Factor Descriptions Load Value Multiplier/Demand
Total VA
(Volt Amperes)
General Lighting Load = Floor Area @ 3va/ft² (NEC 220.12) 5700
Main or Floor Area
Second or 3rd Floor Area
Basement Floor Area
Small Appliance Load - @1500va for EA 20Amp Branch (NEC 220.52
(A)) 3000
Dishwasher (NEC 220.14) 1500
Microwave (NEC220.14) 1500
Range Hood (NEC 220.14)
Refrigerator (NEC 220.14) 1500
Electrical Water Heater (NEC 220.14)
Central A/C Unit (NEC 220.51)
Baseboard Heater (NEC 220.52)
Laundry Machine (NEC 220.52 (B) ) 1500
Garbage Disposal (NEC 220.53) 1500
Dryer (NEC 220.54) 5000
Oven Range (NEC 220.55) 7000
Heat Tape (NEC 427.22)
Electrical Vehicle Charger (NEC 625 Level II)
Hot Tub/Spa (NEC 680.42)
Boiler 1500
Cook Top 1500
Calculation: 31,200 - 10,000 = 21,200 X 40% = 8,480
8,480 / 208V = 89 AMP for 150AMP Service
Total Calculated Demend Load in VA 31,200
Total Calculated Demand Load iin AMPS @120/208V 89 AMP
Existing Service Size = 150AMPS
Minimum Service Size = 150AMPS
Service Size Required = 150AMPS
Phone: 970-390-3674 - Tom Warzecha - G Contractor
Name: Larry Arguello
Total Sq. FT. : 1900
NEC Standard Electrical Demand Load Calculation for Dwelling Unit
Load Calculation Submitted by: Native Electrical, Inc.
05/16/18
05/16/18