HomeMy WebLinkAboutA18-0025_Scope of Work - Unit 702_1526655459.pdf!April 11th, 2018 Vail Fire 42 West Meadow Drive Vail, CO 81657 Attn: Mike Vaughan, Fire Marshal Pjct: Antlers Unit 702 Re: Scope of Work for Fire Alarm System Addition Dear Mike, The scope of work will be to bring the remodeled area up to NFPA standards adopted by Vail Fire. Work performed will be to one new FAPT- multi-criteria smoke detector to the each bedroom of the unit along with a B200S-LF low frequency sounder base to match the existing system. There are a total of three bedrooms In addition two multi-criteria combination smoke/CO FCO-851’s will be installed at the top of the stairs and in the living room by the fire place along with the B200SLF sounder bases. These devices will be added to the current main fire alarm control system, a Notifier NFS2-3030 in and will provide continuity between Unit 702 and the existing building. Once work has been completed and tested, CSI will contact Vail Fire Department and schedule a final fire alarm test of the new area. If there are any questions or concerns about the above information, please feel free to contact me at any time. Sincerely, Commercial Specialists of Western Colorado, LLC Tim Ward Tim Ward Vice President NICET Level IV 115941 601 Mulberry Street * Grand Junction Colorado 81501 210 Marmot Lane Unit 5B * Eagle, Colorado 81631 Voice (970) 328.1951 Fax (970) 328.1956 www.cswcfire.com Commercial Specialists, Inc. * Fire Alarm * BI - Directonal Amplifers * Test & Inspectons * * Security * Intercom * Area of Rescue * Access Control * approved for install Vail Fire & Emergency Services 05/18/18