HomeMy WebLinkAboutGround Engineering 17-6553 - 303 Gore Ck #8 - Matl Test Reports 180417.pdf May 3, 2018 Subject: Interim Materials Testing Summary, 303 Gore Creek Row House # 8 - Materials Testing / Special Inspections, Vail, Colorado Job Number: 17-6553 TOV Permit #: B16-0321 Mr. Guy Cuccia Cuccia Construction Inc. PO Box 3613 Vail, CO 81658 Dear Mr. Cuccia, For the period ending April 17, 2018, representatives of GROUND Engineering Consultants, Inc. were on site to provide materials testing services at times scheduled by the Contractor, Subcontractor and/or Owner. Our reports have been completed in the field as our testing and observations were performed. The Contractor and applicable Sub Contractors were notified of the testing results and/or observations prior to our departure from the project site. This summary report includes the observation reports as well as the materials test results. Please do not hesitate to contact this office if you have any questions concerning these reports. Sincerely, GROUND ENGINEERING CONSULTANTS, INC. Chris Hutto, CET Construction Services Manager 303 Gore Creek – Row House # 8 - Materials Testing/Special Inspections Vail, Colorado Job #17-6553 GROUND Engineering Consultants, Inc. Period Ending 4-17-2018 General Comments Field Observation Reports Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Job No: Date: Field Representative: General Comments As scheduled, a representative arrived on-site to perform the below discussed services and we have the following comments. Shane Sorensen 17-6553 June 6, 2017 ***OPEN HOLE*** The exposed materials at the base of the excavation for the north expansion foundation footings and SW interior spread footings were observed. At approximate building elevations of 96' for north expansion and 96.8' for SW interior spread footings, the exposed materials appeared to be comprised of primarily coarse grained sands and gavels with scattered cobbles that were generally consistent with our experience of the anticipated conditions in this area. A mini-excavator was used to expose the undisturbed native material in the foundation excavations, and a jumping jack used to recompact the surface. Inter-Mountain Engineering, Inc. prepared a project geotechnical report for this site dated 8/25/1981, referenced in plans, but it is not available at this time. Plans call for a maximum allowable soil bearing pressure of 2,000 psf. Quantitatively verifying bearing capacity generally requires access to subsurface and Standard Penetration Test data. Based on the limited amount of available subsurface date, the observed soils are deemed to be likely capable of providing an allowable bearing capacity of 2,000 psf, however, the possibility of the presence of weak subsurface materials resulting in allowable bearing capacities less than 2,000 psf cannot be ruled out from surface observations only. In the event that quantitative verification of allowable bearing capacity is necessary, drilling and sampling should be performed. We did observe one area near the NW corner to be above optimum moisture content due to previous saturation from roof drains, which are now rerouted. We recommended removing the soft, wet material and replacing it with properly compacted native material. Guy with Cuccia Construction was immediately notified of today's observations. Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Job No: Date: Field Representative: General Comments As scheduled, a representative arrived on-site to perform the below discussed services and we have the following comments. Shane Sorensen 17-6553 June 6, 2017 ***OPEN HOLE*** We observed one area near the NW corner of the foundation excavation, which was somewhat soft previously, to have been reworked with properly compacted native material. A stable platform was observed. Guy with Cuccia Construction was immediately notified of today's observations. 303 Gore Creek – Row House # 8 - Materials Testing/Special Inspections Vail, Colorado Job #17-6553 GROUND Engineering Consultants, Inc. Period Ending 4-17-2018 Concrete Field Observation Reports/ Compressive Strength Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Comments or Photos: Results within Specifications? Reinforcing Steel Checked? Subgrade Tested? Number of Cylinders Cast this Date: Number of Pages Attached: Field Representative: Yes No Not Applicable As scheduled, a representative visited the project site to perform periodic concrete testing. The locations of each sample are approximate. General Contractor:General Contractor Rep. Notified:Rep Notified Job Number Concrete Cover Report Date:Date Job Number:Job NameJune 19, 2017 17-6553 Cuccia Construction Guy 4 1 Matty Baldwin Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Cylinders Cast on Ticket Number: Total Number of Cylinders Cast: Cylinder Diameter (in.) Cross Sectional Area (sq. in.) Maximum Load (lbs.) Compressive Strength (psi) Test Date Test Age (days) Fracture Type Average 28-Day Compressive Strength (psi): Placement Contractor:Earthwork Contractor Rep. Notified:Rep Notified Report Date:Date Job Number:Job Name General Contractor:General Contractor Rep. Notified:Rep Notified Placement Date: Job Number Placement Method: Finish Method: Item Number /Structure Type: Concrete Supplier: Mix Identification: Total Cubic Yards Placed: Weather/Temp.: (°F)(pcf) Placement Location: Specifications Specified Strength (psi): Air Content (%): Slump (in.): Temperature (°F): Concrete Field Properties Test No.Sample Location Truck Number Ticket Number Batch Time (gal.) Test Time Slump/ Spread C143 Air Content C231 Conc. Temp. C1064 Unit Weight C138 Water Added (inches) (%) Compressive Strength Results (ASTM C39) Laboratory ID: Field Technician: Comments: July 17, 2017 17-6553 June 19, 2017 Cuccia Construction Guy Vasquez Concrete Gilbert United Companies 37610449 9 Sunny and 80 Line pump Hand and vibrate Footers Basement footers 4,500 N/A N/A 50-90 1 NW basement footer 56393 33212633 2:40pm 3:40pm 4 1/2 4.5 83 141.0 8 33212633 4 5275 4.00 12.57 52,730 4,190 6/26/17 7 3 4.00 12.57 77,050 6,130 7/17/17 28 5 4.00 12.57 71,940 5,720 7/17/17 28 5 4.00 12.57 73,610 5,860 7/17/17 28 5 5,900 Matty Baldwin Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Comments or Photos: Results within Specifications? Reinforcing Steel Checked? Subgrade Tested? Number of Cylinders Cast this Date: Number of Pages Attached: Field Representative: Yes No Not Applicable As scheduled, a representative visited the project site to perform periodic concrete testing. The locations of each sample are approximate. General Contractor:General Contractor Rep. Notified:Rep Notified Job Number Concrete Cover Report Date:Date Job Number:Job NameJune 23, 2017 17-6553 Cuccia Construction Guy 4 1 Emanuel Aragon Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Cylinders Cast on Ticket Number: Total Number of Cylinders Cast: Cylinder Diameter (in.) Cross Sectional Area (sq. in.) Maximum Load (lbs.) Compressive Strength (psi) Test Date Test Age (days) Fracture Type Average 28-Day Compressive Strength (psi): Placement Contractor:Earthwork Contractor Rep. Notified:Rep Notified Report Date:Date Job Number:Job Name General Contractor:General Contractor Rep. Notified:Rep Notified Placement Date: Job Number Placement Method: Finish Method: Item Number /Structure Type: Concrete Supplier: Mix Identification: Total Cubic Yards Placed: Weather/Temp.: (°F)(pcf) Placement Location: Specifications Specified Strength (psi): Air Content (%): Slump (in.): Temperature (°F): Concrete Field Properties Test No.Sample Location Truck Number Ticket Number Batch Time (gal.) Test Time Slump/ Spread C143 Air Content C231 Conc. Temp. C1064 Unit Weight C138 Water Added (inches) (%) Compressive Strength Results (ASTM C39) Laboratory ID: Field Technician: Comments: July 21, 2017 17-6553 June 23, 2017 Cuccia Construction Guy Vasquez Concrete Gilbert United Companies 37610449 7 Sunny and 80 Line pump Hand and vibrate Walls Basement walls 4,500 N/A N/A 50-90 2 NE corner 7143 310919 1:49 3:10 3 6.0 78 139.1 0 310919 4 5310 4.00 12.57 56,900 4,530 6/30/17 7 5 4.00 12.57 78,510 6,250 7/21/17 28 3 4.00 12.57 78,550 6,250 7/21/17 28 3 4.00 12.57 77,730 6,180 7/21/17 28 3 6,230 Emanuel Aragon Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Comments or Photos: Results within Specifications? Reinforcing Steel Checked? Subgrade Tested? Number of Cylinders Cast this Date: Number of Pages Attached: Field Representative: Yes No Not Applicable As scheduled, a representative visited the project site to perform periodic concrete testing. The locations of each sample are approximate. General Contractor:General Contractor Rep. Notified:Rep Notified Job Number Concrete Cover Report Date:Date Job Number:Job NameJuly 31, 2017 17-6553 Cuccia Construction Guy 4 1 Matty Baldwin Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Cylinders Cast on Ticket Number: Total Number of Cylinders Cast: Cylinder Diameter (in.) Cross Sectional Area (sq. in.) Maximum Load (lbs.) Compressive Strength (psi) Test Date Test Age (days) Fracture Type Average 28-Day Compressive Strength (psi): Placement Contractor:Earthwork Contractor Rep. Notified:Rep Notified Report Date:Date Job Number:Job Name General Contractor:General Contractor Rep. Notified:Rep Notified Placement Date: Job Number Placement Method: Finish Method: Item Number /Structure Type: Concrete Supplier: Mix Identification: Total Cubic Yards Placed: Weather/Temp.: (°F)(pcf) Placement Location: Specifications Specified Strength (psi): Air Content (%): Slump (in.): Temperature (°F): Concrete Field Properties Test No.Sample Location Truck Number Ticket Number Batch Time (gal.) Test Time Slump/ Spread C143 Air Content C231 Conc. Temp. C1064 Unit Weight C138 Water Added (inches) (%) Compressive Strength Results (ASTM C39) Laboratory ID: Field Technician: Comments: August 28, 2017 17-6553 July 31, 2017 Cuccia Construction Guy Vasquez Concrete Gilbert Casey Concrete 7.0 3/8 F 70/30 2" 7 Sunny and 75 Line pump Hand and vibrate Footers Basement footers 4,500 N/A N/A 50-90 3 SE basement footer 135 311520 12:35pm 2:00pm 5 3.5 83 142.7 6 311520 4 5427 4.00 12.57 52,620 4,190 8/7/17 7 5 4.00 12.57 75,290 5,990 8/28/17 28 5 4.00 12.57 75,780 6,030 8/28/17 28 5 4.00 12.57 77,320 6,150 8/28/17 28 5 6,060 Matty Baldwin Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Comments or Photos: Results within Specifications? Reinforcing Steel Checked? Subgrade Tested? Number of Cylinders Cast this Date: Number of Pages Attached: Field Representative: Yes No Not Applicable As scheduled, a representative visited the project site to perform periodic concrete testing. The locations of each sample are approximate. General Contractor:General Contractor Rep. Notified:Rep Notified Job Number Concrete Cover Report Date:Date Job Number:Job NameAugust 10, 2017 17-6553 Cuccia Construction Guy 4 1 Matty Baldwin Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Cylinders Cast on Ticket Number: Total Number of Cylinders Cast: Cylinder Diameter (in.) Cross Sectional Area (sq. in.) Maximum Load (lbs.) Compressive Strength (psi) Test Date Test Age (days) Fracture Type Average 28-Day Compressive Strength (psi): Placement Contractor:Earthwork Contractor Rep. Notified:Rep Notified Report Date:Date Job Number:Job Name General Contractor:General Contractor Rep. Notified:Rep Notified Placement Date: Job Number Placement Method: Finish Method: Item Number /Structure Type: Concrete Supplier: Mix Identification: Total Cubic Yards Placed: Weather/Temp.: (°F)(pcf) Placement Location: Specifications Specified Strength (psi): Air Content (%): Slump (in.): Temperature (°F): Concrete Field Properties Test No.Sample Location Truck Number Ticket Number Batch Time (gal.) Test Time Slump/ Spread C143 Air Content C231 Conc. Temp. C1064 Unit Weight C138 Water Added (inches) (%) Compressive Strength Results (ASTM C39) Laboratory ID: Field Technician: Comments: September 7, 2017 17-6553 August 10, 2017 Cuccia Construction Guy Vasquez Concrete Gilbert Casey Concrete 7.0 3/8 F 70/30 2" 4 Sunny and 75 Line pump Hand and vibrate Footers and foundation walls Center footers and foundation Walls 4,500 N/A N/A 50-90 4 Center footer 149 311732 1:20pm 2:10pm 3 1/2 3.5 82 143.7 0 311732 4 5480 4.00 12.57 68,520 5,450 8/17/17 7 3 4.00 12.57 89,660 7,130 9/7/17 28 2 4.00 12.57 88,500 7,040 9/7/17 28 4 4.00 12.57 91,880 7,310 9/7/17 28 5 7,160 Matty Baldwin Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Comments or Photos: Results within Specifications? Reinforcing Steel Checked? Subgrade Tested? Number of Cylinders Cast this Date: Number of Pages Attached: Field Representative: Yes No Not Applicable As scheduled, a representative visited the project site to perform periodic concrete testing. The locations of each sample are approximate. General Contractor:General Contractor Rep. Notified:Rep Notified Job Number Concrete Cover Report Date:Date Job Number:Job NameSeptember 20, 2017 17-6553 Cuccia Construction Guy 4 1 Alex Schultz Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Cylinders Cast on Ticket Number: Total Number of Cylinders Cast: Cylinder Diameter (in.) Cross Sectional Area (sq. in.) Maximum Load (lbs.) Compressive Strength (psi) Test Date Test Age (days) Fracture Type Average 28-Day Compressive Strength (psi): Placement Contractor:Earthwork Contractor Rep. Notified:Rep Notified Report Date:Date Job Number:Job Name General Contractor:General Contractor Rep. Notified:Rep Notified Placement Date: Job Number Placement Method: Finish Method: Item Number /Structure Type: Concrete Supplier: Mix Identification: Total Cubic Yards Placed: Weather/Temp.: (°F)(pcf) Placement Location: Specifications Specified Strength (psi): Air Content (%): Slump (in.): Temperature (°F): Concrete Field Properties Test No.Sample Location Truck Number Ticket Number Batch Time (gal.) Test Time Slump/ Spread C143 Air Content C231 Conc. Temp. C1064 Unit Weight C138 Water Added (inches) (%) Compressive Strength Results (ASTM C39) Laboratory ID: Field Technician: Comments: October 18, 2017 17-6553 September 20, 2017 Cuccia Construction Guy Vasquez Concrete Gilbert Casey Concrete 7.0 3/8 F 70/30 2" 7 Sunny and 66 Line pump Hand and vibrate Spread Footing E edge of foundation, S side of foundation on eastern half, west edge of foundation 10' from the S side 3,000 N/A N/A 50-90 5 S side of foundation 143 312447 9:54am 11:45am 3 3/4 2.9 68 143.0 0 312447 4 5603 4.00 12.57 47,160 3,750 9/27/17 7 5 4.00 12.57 68,210 5,430 10/18/17 28 3 4.00 12.57 69,320 5,510 10/18/17 28 3 4.00 12.57 72,560 5,770 10/18/17 28 5 5,570 Alex Schultz 303 Gore Creek – Row House # 8 - Materials Testing/Special Inspections Vail, Colorado Job #17-6553 GROUND Engineering Consultants, Inc. Period Ending 4-17-2018 Drilled & Epoxied Reinforcing Steel Field Observation Reports Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Comments or Photos: Yes No Discrepancies Reported this Date? No. of Pages Attached: Field Representative: Drill and Epoxy Cover Report Date:Date Job NameJob Number:Job Number As scheduled, a representative visited the project site to perform special inspections for drill and epoxy at locations requested. General Contractor:General Contractor Rep. Notified:Rep Notified June 16, 2017 17-6553 Cuccia Construction Guy 1 Shane Sorensen/Matty Baldwin Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Location: 1.) 2.) 3.) 4.) Orientation (vertical/horizontal): 1.) 3.) 2.) 4.) Hole Diameter (inches): 1.) Length (inches): 1.) 2.) 2.) 3.) 3.) 4.) 4.) Hole Spacing (inches): 1.) 3.) 2.) 4.) Drilling Equipment: Method to Clean Hole: Epoxy Type: Epoxy Expiration: Placement Method: Type (rebar/bolt/anchor): 1.) Size: 1.) Length (inches) 1.) 2.) 2.) 2.) 3.) 3.) 3.) 4.) 4.) 4.) Placement Method: Additional Reinforcing Steel: Field Representative: Comments: Reinforcement Epoxy Documents Used: Drill and Epoxy Drilling Subcontractor: Rep. Notified: pGeneral Contractor: Rep. Notified: p Job Number:Report Date:June 16, 2017 17-6553 Cuccia Construction Guy Vasquez Concrete Richard Plans Into existing foundation for new foundation along west side of unit, first two sections Underpinning existing footing for new footing along east side of unit, first two sections Horizontal Vertical 3/4 4 1/2 3/4 4 1/2 16 16 Hammer drill Wire brush, compressed air Hilti HIY-HY 200-R 02/2018 Hilti Epoxy gun 90° hooked rebar #5 6x36 Rebar #5 36 Hand set For location 2, contractor chose to splice rebar hooks to epoxy dowels due to space constraints beneath footing. Shane Sorensen/Matty Baldwin Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Comments or Photos: Yes No Discrepancies Reported this Date? No. of Pages Attached: Field Representative: Drill and Epoxy Cover Report Date:Date Job NameJob Number:Job Number As scheduled, a representative visited the project site to perform special inspections for drill and epoxy at locations requested. General Contractor:General Contractor Rep. Notified:Rep Notified July 31, 2017 17-6553 Cuccia Construction Guy 1 Matty Baldwin/ Shane Sorensen Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Location: 1.) 2.) 3.) 4.) Orientation (vertical/horizontal): 1.) 3.) 2.) 4.) Hole Diameter (inches): 1.) Length (inches): 1.) 2.) 2.) 3.) 3.) 4.) 4.) Hole Spacing (inches): 1.) 3.) 2.) 4.) Drilling Equipment: Method to Clean Hole: Epoxy Type: Epoxy Expiration: Placement Method: Type (rebar/bolt/anchor): 1.) Size: 1.) Length (inches) 1.) 2.) 2.) 2.) 3.) 3.) 3.) 4.) 4.) 4.) Placement Method: Additional Reinforcing Steel: Field Representative: Comments: Reinforcement Epoxy Documents Used: Drill and Epoxy Drilling Subcontractor: Rep. Notified: pGeneral Contractor: Rep. Notified: p Job Number:Report Date:July 31, 2017 17-6553 Cuccia Construction Guy Vasquez Concrete Richard Plans Into existing foundation for new foundation along west side of unit, last two sections Underpinning existing footing for new footing along east side of unit, last section Horizontal Vertical 3/4 4 1/2 3/4 4 1/2 16 16 Hammer drill Wire brush, compressed air Hilti HIY-HY 200-R 01/2018 Hilti Epoxy gun Rebar #5 36 90° hooked rebar, 90 into slab #5 6x36x16 Hand set For location 1, contractor chose to splice rebar hooks to epoxy dowels due to space constraints beneath footing. Matty Baldwin/ Shane Sorensen Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Comments or Photos: Yes No Discrepancies Reported this Date? No. of Pages Attached: Field Representative: Drill and Epoxy Cover Report Date:Date Job NameJob Number:Job Number As scheduled, a representative visited the project site to perform special inspections for drill and epoxy at locations requested. General Contractor:General Contractor Rep. Notified:Rep Notified September 18, 2017 17-6553 Cuccia Construction Guy 1 Matty Baldwin/ Shane Sorensen Client: www.groundeng.com Englewood, Commerce City, Loveland, Granby, Gypsum 303 Gore Creek, Row House # 8 Guy Cuccia Cuccia Construction, Inc. PO Box 3613 Vail, CO 81658 Location: 1.) 2.) 3.) 4.) Orientation (vertical/horizontal): 1.) 3.) 2.) 4.) Hole Diameter (inches): 1.) Length (inches): 1.) 2.) 2.) 3.) 3.) 4.) 4.) Hole Spacing (inches): 1.) 3.) 2.) 4.) Drilling Equipment: Method to Clean Hole: Epoxy Type: Epoxy Expiration: Placement Method: Type (rebar/bolt/anchor): 1.) Size: 1.) Length (inches) 1.) 2.) 2.) 2.) 3.) 3.) 3.) 4.) 4.) 4.) Placement Method: Additional Reinforcing Steel: Field Representative: Comments: Reinforcement Epoxy Documents Used: Drill and Epoxy Drilling Subcontractor: Rep. Notified: pGeneral Contractor: Rep. Notified: p Job Number:Report Date:September 18, 2017 17-6553 Cuccia Construction Guy Vasquez Concrete Gilbert Plans SE Wall from existing foundation wall to proposed wall SE footer to proposed footer SW stem wall into upper proposed stem wall SW stem wall into upper proposed stem wall Horizontal Vertical Vertical Horizontal 3/4 6 3/4 5 3/4 6 3/4 5 12 12 12 12 Hammer drill Wire brush, compressed air Hilti HIY-HY 200-R 02/2018 Hilti Epoxy gun Rebar #5 54 Rebar #5 36 Rebar #5 54 Rebar #5 24 Hand set For location 2, contractor chose to splice rebar hooks to epoxy dowels due to space constraints beneath footing. Matty Baldwin/ Shane Sorensen 303 Gore Creek – Row House # 8 - Materials Testing/Special Inspections Vail, Colorado Job #17-6553 GROUND Engineering Consultants, Inc. Period Ending 4-17-2018 Structural Steel Field Observation Report & Discrepancy List Building - Steel 1st floor to 5th floor (roof)Placement Location: Structure Type: General Contractor: Steel Erector/Fabricator: Cuccia Construction Trinity Welding Performed by:Lee Royse As directed by Guy Cuccia with Cuccia Construction:Summary Comments: Visual Special Inspections Visual Non-Compliance Building - Steel, Non-Compliant Connection Types: Description of Non-Compliance: Beam to Beam|Beam to Column|Angle to Beam|Anchored Connection of Plate GROUND has not received Welder Qualification Test Records (WQTRs), Weld Procedure Specifications (WPS) for welds performed and continuity logs if the WQTRs are over six months old for AWS D1.1 from Trinity Welding. From level two to roof level there are column base plate to column base plate bolted connections. Per structural general note C these are to be A325 high strength bolts. Currently installed these are not A325 bolts. At each column base plate and column to beam these connections are to be bolted per details 8/S5 and 9/S5 and 2/S3. These connections are currently welded on two sides in lieu of bolting. This is from level 1-5 at all connections. At numerous connections from level 1-5 slag has not been removed from the weld. This is to be done before inspection per AWS D1.1:15 C6 5.29.2. On level 3 on the outside wall in the center the beam to Beam connection has a shim stack installed and the beam to beam connection has no shear plate installed. On level 3-4 at the center of the outside wall a column has been covered and cannot be inspected. On level four to roof a column to beam connection has plates added and has no detail provided for this connection. This is at south side. On level one the anchored connections of column base plates to foundation the nuts are loose and one base plate has anchor bolts missing. On level one at the center of the building the shear plates to beam do not have a weld detail for one side of shear plate to beam per details 16/S5 and 17/S5. Currently the shear plates are welded on one side to the beam with approximately a 1/8" to 3/16" fillet weld. On level two on the north side the C Channel to C Channel connections for the cantilever deck does not have a weld detail per detail 7/S5. Cuccia Construction Inc. PO Box 3613 Vail, CO 81658 Guy Cuccia 303 Gore Creek, Row House # 8 Client: Oct 6, 2017 Work Order Date: Work Order No.: Structural Steel 17-6553.StructuralSteel(Field).0001; ver: Report Date: Oct 5, 2017 Reviewed by:Paul Gustafson Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. This report should not be reproduced, except in full, without the written permission of GROUND Engineering Consultants, Inc. www.groundeng.com Englewood | Commerce City | Loveland | Granby | Gypsum Page 1 of 4 The following individuals were notifed of all results while on-site. Name Company Notifications Guy Cuccia Cuccia Construction Discrepancies The following discrepancies were added as a result of services performed. It is the contractor's responsibility to resolve reported discrepancies and schedule retesting. A list of open discrepancies can be provided upon request. Number Description Structural Steel (Field) 1 GROUND has not received Welder Qualification Test Records (WQTRs), Weld Procedure Specifications (WPS) for welds performed and continuity logs if the WQTRs are over six months old for AWS D1.1 from Trinity Welding. Structural Steel (Field) 10 On level two on the north side the C Channel to C Channel connections for the cantilever deck does not have a weld detail per detail 7/S5. Structural Steel (Field) 2 From level two to roof level there are column base plate to column base plate bolted connections. Per structural general note C these are to be A325 high strength bolts. Currently installed these are not A325 bolts. Structural Steel (Field) 3 At each column base plate and column to beam these connections are to be bolted per details 8/S5 and 9/S5 and 2/S3. These connections are currently welded on two sides in lieu of bolting. This is from level 1-5 at all connections. Structural Steel (Field) 4 At numerous connections from level 1-5 slag has not been removed from the weld. This is to be done before inspection per AWS D1.1:15 C6 5.29.2. Structural Steel (Field) 5 On level 3 on the outside wall in the center the beam to Beam connection has a shim stack installed and the beam to beam connection has no shear plate installed. Structural Steel (Field) 6 On level 3-4 at the center of the outside wall a column has been covered and cannot be inspected. Structural Steel (Field) 7 On level four to roof a column to beam connection has plates added and has no detail provided for this connection. This is at south side. Structural Steel (Field) 8 On level one the anchored connections of column base plates to foundation the nuts are loose and one base plate has anchor bolts missing. Structural Steel (Field) 9 On level one at the center of the building the shear plates to beam do not have a weld detail for one side of shear plate to beam per details 16/S5 and 17/S5. Currently the shear plates are welded on one side to the beam with approximately a 1/8" to 3/16" fillet weld. 1) WPS - Welding Procedure Specification : The detailed methods and practices including all joint welding procedures involved in the production of weldments. All prequalified WPS's shall be written. WPS's should be assigned an identification #. 2) WQTR - Welder Qualification Test Record : Performance qualification test to determine a welder's ability to produce sound welds. This shall be performed in conformance with a WPS. Identification # of the WPS shall be displayed on the WQTR. 3) Continuity Record : Clause 4.2.3 Period of Effectiveness. A welder's qualification is considered remaining in effect provided; the period of time that the welder does not engage in the given process does not exceed 6 months, the contract documents state differently, or there is a specific reason to question a welder's ability to produce sound welds. The welder's employer should maintain records of each welder's use of qualified welding processes. 4) Common Processes : SMAW - Shielded Metal Arc Welding, commonly referred to as stick welding. FCAW - Flux Cored Arc Welding, commonly referred to as wire feed. GMAW - Gas Metal Arc Welding, commonly referred to as wire feed. SW - Stud Welding, commonly referred to as headed anchor studs (HAS), threaded anchor studs (TAS), and deformed anchor studs (DAS). 5) Most commonly used welding codes: AWS D1.1 - Structural Welding Code, covers carbon or low alloy steels 1/8-inch or thicker. AWS D1.3 - Structural Welding Code Sheet Steel, covers structural sheet/strip steels including cold formed members (Metal Studs) equal to or less than 3/16-inch. Decking usually requires single and double sheet certification. AWS D1.4 - Structural Welding Code Reinforcing Steel, covers reinforcing steel to reinforcing steel and reinforcing steel to carbon or low alloy Weld Certification Submittal Information Cuccia Construction Inc. PO Box 3613 Vail, CO 81658 Guy Cuccia 303 Gore Creek, Row House # 8 Client: Oct 6, 2017 Work Order Date: Work Order No.: Structural Steel 17-6553.StructuralSteel(Field).0001; ver: Report Date: Oct 5, 2017 Reviewed by:Paul Gustafson Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. This report should not be reproduced, except in full, without the written permission of GROUND Engineering Consultants, Inc. www.groundeng.com Englewood | Commerce City | Loveland | Granby | Gypsum Page 2 of 4 steels, this includes A706 weldable bar. Photos These are not A325 structural bolts. Relates to discrepancy number 2.Column cap plates and base plates to be bolted. All locations welded in lieu of bolting and slag has not been removed. This relates to discrepancy number 3 and 4. Shim stack installed and no shear plate installed. This relates to discrepancy number 5. Column covered on level 3 and cannot be inspected on this date. This relates to discrepancy number 6. Cuccia Construction Inc. PO Box 3613 Vail, CO 81658 Guy Cuccia 303 Gore Creek, Row House # 8 Client: Oct 6, 2017 Work Order Date: Work Order No.: Structural Steel 17-6553.StructuralSteel(Field).0001; ver: Report Date: Oct 5, 2017 Reviewed by:Paul Gustafson Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. This report should not be reproduced, except in full, without the written permission of GROUND Engineering Consultants, Inc. www.groundeng.com Englewood | Commerce City | Loveland | Granby | Gypsum Page 3 of 4 Plates added to column base on level 4. No detail provided for this connection. This relates to discrepancy number 7. Missing anchor connections on level 1. Relates to discrepancy number 8. Loose anchor connections on level 1. Relates to discrepancy number 8.Shear plates to beam have no weld detail provided for one side per detail 16 and 17 on S5. This is on level 1. Relates to discrepancy number 9. Cuccia Construction Inc. PO Box 3613 Vail, CO 81658 Guy Cuccia 303 Gore Creek, Row House # 8 Client: Oct 6, 2017 Work Order Date: Work Order No.: Structural Steel 17-6553.StructuralSteel(Field).0001; ver: Report Date: Oct 5, 2017 Reviewed by:Paul Gustafson Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. This report should not be reproduced, except in full, without the written permission of GROUND Engineering Consultants, Inc. www.groundeng.com Englewood | Commerce City | Loveland | Granby | Gypsum Page 4 of 4 Miscellaneous | Wood frame house with steel structures. Reinspected open discrepancy items.Placement Location: Structure Type: General Contractor: Steel Erector/Fabricator: Cuccia Construction Trinity Welding Performed by:Lee Royse As directed by Guy Cuccia with Cuccia Construction: Reinspected discrepancy numbers 1-10 and added tracking to these items. Summary Comments: The following individuals were notifed of all results while on-site. Name Company Notifications Guy Cuccia Cuccia Construction Discrepancies The following discrepancies were added as a result of services performed. It is the contractor's responsibility to resolve reported discrepancies and schedule retesting. A list of open discrepancies can be provided upon request. Number Description Structural Steel (Field) 11 At the fireplace on level 3 the W10x15 over the stone has no connection detail for this connection. Structural Steel (Field) 12 On level four in the north guest master bedroom the HSS tube column to roof beam connection has a shim between the column and roof beam. This shim is not per project plans. Visual Special Inspections Visual Non-Compliance Building - Steel, Non-Compliant Connection Types: Description of Non-Compliance: Beam to HSS|Beam to Beam At the fireplace on level 3 the W10x15 over the stone has no connection detail for this connection. On level four in the north guest master bedroom the HSS tube column to roof beam connection has a shim between the column and roof beam. This shim is not per project plans. Photos W10x15 above fireplace on level 3 with no connection detail.1/8 inch shim added between HSS column and roof beam on level 4 in the north guest master bedroom. Cuccia Construction Inc. PO Box 3613 Vail, CO 81658 Guy Cuccia 303 Gore Creek, Row House # 8 Client: Nov 17, 2017 Work Order Date: Work Order No.: Structural Steel 17-6553.StructuralSteel(Field).0002; ver: Report Date: Nov 16, 2017 Reviewed by:Paul Gustafson Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. This report should not be reproduced, except in full, without the written permission of GROUND Engineering Consultants, Inc. www.groundeng.com Englewood | Commerce City | Loveland | Granby | Gypsum Page 1 of 1 Miscellaneous | Wood frame house remodel with steel structures added. EmailPlacement Location: Structure Type: General Contractor: Steel Erector/Fabricator: Cuccia Construction Trinity Welding Performed by:Lee Royse GROUND has received EOR observation report dated 27 November 2017 in reference to discrepancy numbers 1, 3, 4, 5, 7, 10, 11 and 12 and added tracking to these items. Summary Comments: Visual Special Inspections Visual Non-Compliance Cuccia Construction Inc. PO Box 3613 Vail, CO 81658 Guy Cuccia 303 Gore Creek, Row House # 8 Client: Jan 22, 2018 Work Order Date: Work Order No.: Structural Steel 17-6553.StructuralSteel(Field).0003; ver: Report Date: Jan 19, 2018 Reviewed by:Paul Gustafson Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. This report should not be reproduced, except in full, without the written permission of GROUND Engineering Consultants, Inc. www.groundeng.com Englewood | Commerce City | Loveland | Granby | Gypsum Page 1 of 1 Miscellaneous Level’s 1-5Placement Location: Structure Type: General Contractor: Steel Erector/Fabricator: Cuccia Construction Trinity Welding Performed by:Barry Bowland As directed by Guy Cuccia with Cuccia Construction. Ground was onsite to review remaining open discrepancies. Summary Comments: The following individuals were notifed of all results while on-site. Name Company Notifications Guy Cuccia Cuccia Construction Visual Special Inspections Other Connection Types:Column cap plate to beam. Connection Comments:Ground reinspected the following: Discrepancy #1-Ground reviewed with the General Contractor the remaining documents required to close out this discrepancy. Tracking added. Discrepancy #4-Ground did a walkthrough of level’s 1-5 with Guy Cuccia of Cuccia Construction. All exposed connections were reviewed, any welds that had slag remaining were de-slagged while Ground remained onsite. Ground found the de-slagged welds to be visually acceptable and in general conformance with project plans and AWS D1.1 2015 Clause 6, Table 6.1. This item is now closed. Visual Non-Compliance Cuccia Construction Inc. PO Box 3613 Vail, CO 81658 Guy Cuccia 303 Gore Creek, Row House # 8 Client: Mar 16, 2018 Work Order Date: Work Order No.: Structural Steel 17-6553.StructuralSteel(Field).0006; ver: Report Date: Mar 15, 2018 Reviewed by:Austin Nicodemus Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. This report should not be reproduced, except in full, without the written permission of GROUND Engineering Consultants, Inc. www.groundeng.com Englewood | Commerce City | Loveland | Granby | Gypsum Page 1 of 1 Miscellaneous Onsite with Guy Cuccia.Placement Location: Structure Type: General Contractor: Steel Erector/Fabricator: Cuccia Construction Trinity Welding Performed by:Barry Bowland As directed by Guy Cuccia with Cuccia Construction.Summary Comments: The following individuals were notifed of all results while on-site. Name Company Notifications Guy Cuccia Cuccia Construction Visual Special Inspections Connection Comments:Discrepancy #1-Ground received the welding continuity log for Trinity Welding. This item is now closed. Visual Non-Compliance Cuccia Construction Inc. PO Box 3613 Vail, CO 81658 Guy Cuccia 303 Gore Creek, Row House # 8 Client: Apr 18, 2018 Work Order Date: Work Order No.: Structural Steel 17-6553.StructuralSteel(Field).0007; ver: 1Report Date: Apr 17, 2018 Reviewed by:Austin Nicodemus Results apply only to the specific items and locations referenced and at the time of testing, observations or special inspections. This report should not be reproduced, except in full, without the written permission of GROUND Engineering Consultants, Inc. www.groundeng.com Englewood | Commerce City | Loveland | Granby | Gypsum Page 1 of 1 Structural Steel (Field) 1 GROUND has not received Welder Qualification Test Records (WQTRs), Weld Procedure Specifications (WPS) for welds performed and continuity logs if the WQTRs are over six months old for AWS D1.1 from Trinity Welding. Lee Royse 10/5/2017 Discrepancy #1-Ground reviewed with the General Contractor the remaining documents required to close out this discrepancy. 3/15/2018Barry Bowland GROUND has not received the WPS and the continuity logs at this time. This item will remain open at this time. 1/19/2018Lee Royse GROUND has received the WQTRs for trinity Welding but have not received the WPS for welds performed and continuity logs due to the WQTRs are over six months old. This item will remain open. 11/16/2017Lee Royse Ground received the Continuity Log for Trinity Welding. 4/17/2018Barry Bowland Per Plan Structural Steel (Field) 2 From level two to roof level there are column base plate to column base plate bolted connections. Per structural general note C these are to be A325 high strength bolts. Currently installed these are not A325 bolts. Lee Royse 10/5/2017 A325 bolts were found installed where non compliant bolts were located. These connections were found to be in the snug tight condition with plies in firm contact. This item is now closed. 11/16/2017Lee Royse Per Plan Structural Steel (Field) 3 At each column base plate and column to beam these connections are to be bolted per details 8/S5 and 9/S5 and 2/S3. These connections are currently welded on two sides in lieu of bolting. This is from level 1-5 at all connections. Lee Royse 10/5/2017 Per details 9/S5 and 8/S5 the weld is to be a single bevel weld. The depth of preparation is not called out and GROUND is not able to verify that a bevel has been installed before welding. This item will remain open. 11/16/2017Lee Royse This item is acceptable as is per EOR observation report dated 27 November 2017. This item is now closed. 1/19/2018Lee Royse Per Structural EOR Letter Cuccia Construction Inc. PO Box 3613 Vail, CO 81658 Guy Cuccia 303 Gore Creek, Row House # 8 Client: Date: Project No. Project Discrepancy Log 17-6553May 03, 2018 Number Description Reported By Date Resolution Type www.groundeng.com Englewood | Commerce City | Loveland | Granby | Gypsum Page 1 of 3 It is the responsibility of the contractor to schedule our office to perform retesting once the necessary corrective action has been made or provide our office with documentation that resolves the discrepancy. Resolved Discrepancy follow up commentaryNOT resolved Structural Steel (Field) 4 At numerous connections from level 1-5 slag has not been removed from the weld. This is to be done before inspection per AWS D1.1:15 C6 5.29.2. Lee Royse 10/5/2017 Did a walkthrough with the GC of level’s 1-5, any welds with slag remaining were de- slagged and found visually acceptable. 3/15/2018Barry Bowland Per Plan GROUND has not had the opportunity to inspect welds with slag remaining on them. This item will remain open at this time. 1/19/2018Lee Royse Most slag was found removed. However there is slag remaining on numerous locations and this item will remain open. 11/16/2017Lee Royse Structural Steel (Field) 5 On level 3 on the outside wall in the center the beam to Beam connection has a shim stack installed and the beam to beam connection has no shear plate installed. Lee Royse 10/5/2017 This condition has not been changed. Guy Cuccia stated that he will work with the EOR for a correction or acceptance to this item. 11/16/2017Lee Royse This item is acceptable as is per EOR observation report dated 27 November 2017. This item is now closed. 1/19/2018Lee Royse Per Structural EOR Letter Structural Steel (Field) 6 On level 3-4 at the center of the outside wall a column has been covered and cannot be inspected. Lee Royse 10/5/2017 The concealed connection has been exposed. The connections are open and per Guy will remain open due to the column plates at the top and bottom are the same condition as discrepancy number 3. This item is now closed but the column conditions have been added to discrepancy number 3. 11/16/2017Lee Royse Per Plan Structural Steel (Field) 7 On level four to roof a column to beam connection has plates added and has no detail provided for this connection. This is at south side. Lee Royse 10/5/2017 The shims that have been added are not per detail 4/S6. Guy Cuccia stated that he will work with the EOR for a correction to this condition. This item will remain open. 11/16/2017Lee Royse This item is acceptable as is per EOR observation report dated 27 November 2017. This item is now closed. 1/19/2018Lee Royse Per Structural EOR Letter Cuccia Construction Inc. PO Box 3613 Vail, CO 81658 Guy Cuccia 303 Gore Creek, Row House # 8 Client: Date: Project No. Project Discrepancy Log 17-6553May 03, 2018 Number Description Reported By Date Resolution Type www.groundeng.com Englewood | Commerce City | Loveland | Granby | Gypsum Page 2 of 3 It is the responsibility of the contractor to schedule our office to perform retesting once the necessary corrective action has been made or provide our office with documentation that resolves the discrepancy. Resolved Discrepancy follow up commentaryNOT resolved Structural Steel (Field) 8 On level one the anchored connections of column base plates to foundation the nuts are loose and one base plate has anchor bolts missing. Lee Royse 10/5/2017 Loose and missing anchor nuts were found installed and in the snug tight condition and in general compliance with the project plans. This item is now closed. 11/16/2017Lee Royse Per Plan Structural Steel (Field) 9 On level one at the center of the building the shear plates to beam do not have a weld detail for one side of shear plate to beam per details 16/S5 and 17/S5. Currently the shear plates are welded on one side to the beam with approximately a 1/8" to 3/16" fillet weld. Lee Royse 10/5/2017 These connections were found to be in general compliance with AWS D1.1:15 C6 table 6.1 and per details 16/S5 and 17/S5. This item is now closed. 11/16/2017Lee Royse Per Plan Structural Steel (Field) 10 On level two on the north side the C Channel to C Channel connections for the cantilever deck does not have a weld detail per detail 7/S5. Lee Royse 10/5/2017 Detail 7/S5 shows a single bevel groove weld for this connection. GROUND cannot verify that a bevel has been installed per this detail. This item will remain open. 11/16/2017Lee Royse This item is acceptable as is per EOR observation report dated 27 November 2017. This item is now closed. 1/19/2018Lee Royse Per Structural EOR Letter Structural Steel (Field) 11 At the fireplace on level 3 the W10x15 over the stone has no connection detail for this connection. Lee Royse 11/16/2017 This item is acceptable as is per EOR observation report dated 27 November 2017. This item is now closed. 1/19/2018Lee Royse Per Structural EOR Letter Structural Steel (Field) 12 On level four in the north guest master bedroom the HSS tube column to roof beam connection has a shim between the column and roof beam. This shim is not per project plans. Lee Royse 11/16/2017 This item is acceptable as is per EOR observation report dated 27 November 2017. This item is now closed. 1/19/2018Lee Royse Per Structural EOR Letter Cuccia Construction Inc. PO Box 3613 Vail, CO 81658 Guy Cuccia 303 Gore Creek, Row House # 8 Client: Date: Project No. Project Discrepancy Log 17-6553May 03, 2018 Number Description Reported By Date Resolution Type www.groundeng.com Englewood | Commerce City | Loveland | Granby | Gypsum Page 3 of 3 It is the responsibility of the contractor to schedule our office to perform retesting once the necessary corrective action has been made or provide our office with documentation that resolves the discrepancy. Resolved Discrepancy follow up commentaryNOT resolved