Loading...
HomeMy WebLinkAbout2663 THE MARKET FINAL REPORT CBC.pdfCertified Balancing and Commissioning, LLC. I Testing, Adjusting and Balancing Report Project The Market Address 430 E. Lionshead Cir, Vail CO Architect Unknown Mechanical Engineer Bighorn Consulting Engineers Contractor Skyline Mechanical Balancing Supervisors Greg Barnes | Pat Handley Date May 21, 2018 Job Number 2663 Certified Balancing and Commissioning, LLC. II ABBREVIATION INDEX AHU: Air Handling Unit Motor FLA: Full Load Amperage RTU: Roof Top Unit S.F.: Service Factor MAU: Make Up Air Unit P.F.: Power Factor FCU: Fan Coil Unit Nom. Eff.: Nominal Efficiency CRAC: Computer Room Air Conditioning Unit RPM: Revolutions per Minute VAV: Variable Air Volume FPB: Fan Powered Box K Factor: Correction Factor T1: Terminal 1 T2: Terminal 2 T3: Terminal 3 AK: Area Correction OD: Outside Diameter CUH: Cabinet Unit Heater UH: Unit Heater ERV: Energy Recovery Ventilator TDH: Total Dynamic Head ERU: Energy Recovery Unit PSI: Pounds per Square Inch EF: Exhaust Fan BV: Balance Valve KEF: Kitchen Exhaust Fan CS: Circuit Setter SF: Supply Fan Valve D.P.: Discharge Pressure RF: Return Fan Valve S.P.: Suction Pressure TF: Transfer Fan Diff.: Differential SEF: Smoke Exhaust Fan Design D.P.: Design Differential Pressure SPF: Stairwell Pressurization Fan Actual D.P.: Recorded Differential Pressure SP: Static Pressure Ind.Imp.Dia.: Indicated Impeller Diameter TSP: Total Static Pressure in.wc.: Inches of Water ESP: External Static Pressure HW: Heating Water VP: Velocity Pressure CHW: Cooling Water SA: Supply Air CW: Condenser Water RA: Return Air HX: Heat Exchanger OSA: Outside Air DX: Direct Expansion OA: Outside Air EAT: Entering Air Temperature MA: Mixed Air LAT: Leaving Air Temperature SD: Supply Diffuser EWT: Entering Water Temperature CD: Ceiling Diffuser LWT: Leaving Water Temperature SWD: Sidewall Diffuser ER: Exhaust Register MVD: Manual Volume Damper RG: Return Grille OBD: Opposed Blade Damper CFM: Cubic Feet Per Minute NAC: No Access FPM: Feet Per Minute NG: Not Given NIC: Not in Contract E: Existing Certified Balancing and Commissioning, LLC. III Method of Balancing: Supply, Return and Exhaust diffusers, grilles and registers were measured with an Alnor Balometer EBT-721, which includes the flow hood, velgrid, pitot tube and airfoil. Heating and Chilled water flow rates were measured with an Alnor Hydronic Manometer HM-680 by obtaining pressure measurements. RPM was measured with a Shimpo tachometer. Amperage and Voltage readings were taken with a Fluke 930 meter. Instrumentation: Digital Manometer Alnor Balometer EBT-721 Flow hood Alnor Balometer EBT-721 Digital Pressure Gage Alnor Hydronic Manometer HM-680 Tachometer Shimpo Digital Volt-Amp Meter Fluke 930 Thermometer Alnor Balometer EBT-721 Warranty Information: This project was completed per TABB Procedural Standards. The data presented in this report is a record of system measurements and final adjustments that have been obtained in accordance with the current edition of the TABB Procedural Standards for testing, adjusting, and balancing environmental systems. Any variances from design quantities, which exceed TABB tolerances, are noted in the Test-Adjust- Balance Report Project Summary. If a Test-Adjust-Balance Report Project Summary is not issued directly following this cover page, all measurements met the design requirements as specified by the design mechanical engineer. This project has a one-year guarantee on all Testing, Adjusting & Balancing from the date listed on this cover page. Greg Barnes Owner/ TABB Supervisor greg@certtab.com 720-201-6274 Certified Balancing and Commissioning, LLC. IV Project Summary 1. Individual Notes, Explanations, and Deficiencies, if exist, are shown underneath the associated equipment. Air Handling UnitPROJECT:LOCATION:THE MARKET AT VAILVAIL, CO 2663PROJECT #: DATE:CONTACT: AUTHOR: 5/21/2018Kara Handley Tested By:Daniel Takacs Date:5/20/2018 SYSTEM/UNIT: MA-01 Log:MA-01 5/18/2018 Daniel Takacs OUTLET (17) INSTALLED IN VESTIBULE NOT SHOWN ON PRINTS. SET TO TYPICAL 185CFM. Unit Data Unit Manufacturer THERMOTEK Unit Model Number CD-LPD-VB-I-03-2M-TA Unit Serial Number 3216098 Starter Data MA-01/Supply Fan Starter Manufacturer LENZE VFD Test Data Design Airflow 3145 CFM Actual Airflow 3265 CFM MA-01/Supply Fan Actual RPM DIRECT DRIVE RPM Motor Volts T1-T2 211 Volts Motor Volts T2-T3 212 Volts Motor Volts T1-T3 212 Volts Motor Amps T1 8.20 Amps Motor Amps T2 8.10 Amps Motor Amps T3 8.20 Amps Drive Frequency 58.0 Hertz Motor Data MA-01/Supply Fan Motor Manufacturer WESTINGHOUSE Motor HP 3 HP Motor RPM 1755 RPM Motor Type ASGHUW 10- Motor Rated Volts 230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 8.6/4.3 Amps Motor Service Factor 1.15 Motor Frame 182T Nominal Efficiency 89.5 % Sheave Data MA-01/Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP In -0.17 in. wc Filter SP Out -0.19 in. wc Cooling Coil SP In -0.19 in. wc Cooling Coil SP Out -0.52 in. wc Heating Coil SP In 0.99 in. wc Heating Coil SP Out 0.16 in. wc Fan SP In -0.61 in. wc Fan SP Out 0.99 in. wc Final Filter SP In -0.52 in. wc Final Filter SP Out -0.61 in. wc Certified Balancing and Commissioning Page 1 of 4 Air Handling UnitPROJECT:LOCATION:THE MARKET AT VAILVAIL, CO 2663PROJECT #: DATE:CONTACT: AUTHOR: 5/21/2018Kara Handley System/Unit Outlet Type Size LxW / D AK Factor Design Airflow Prelim Airflow % Prelim Diff. Final Airflow % Final Diff. Outlet-01 SD 185 180 97 190 103 Outlet-02 SD 185 180 97 195 105 Outlet-03 SD 185 190 103 200 108 Outlet-04 SD 185 205 111 200 108 Outlet-05 SD 185 175 95 195 105 Outlet-06 SD 185 195 105 190 103 Outlet-07 SD 185 200 108 190 103 Outlet-08 SD 185 190 103 185 100 Outlet-09 SD 185 180 97 185 100 Outlet-10 SD 185 160 86 195 105 Outlet-11 SD 185 175 95 200 108 Outlet-12 SD 185 185 100 195 105 Outlet-13 SD 185 165 89 185 100 Outlet-14 SD 185 160 86 190 103 Outlet-15 SD 185 170 92 185 100 Outlet-16 SD 185 170 92 190 103 Outlet-17 SD 185 425 230 195 105 Totals:---3145 3305 105 3265 104 MA-01 Supply Outlet Summary Certified Balancing and Commissioning Page 2 of 4 Air Handling UnitPROJECT:LOCATION:THE MARKET AT VAILVAIL, CO 2663PROJECT #: DATE:CONTACT: AUTHOR: 5/21/2018Kara Handley Tested By:Daniel Takacs Date:5/20/2018 SYSTEM/UNIT: MA-02 Unit Data Unit Manufacturer THERMOTEK Unit Model Number CD-LPD-VB-I-03-2M-TA Unit Serial Number 3216098 Starter Data MA-02/Supply Fan Starter Manufacturer LENZE VFD Test Data Design Airflow 3110 CFM Actual Airflow 3195 CFM MA-02/Supply Fan Actual RPM DIRECT DRIVE RPM Motor Volts T1-T2 212 Volts Motor Volts T2-T3 211 Volts Motor Volts T1-T3 212 Volts Motor Amps T1 8.10 Amps Motor Amps T2 8.20 Amps Motor Amps T3 8.20 Amps Drive Frequency 58.0 Hertz Motor Data MA-02/Supply Fan Motor Manufacturer WESTINGHOUSE Motor HP 3 HP Motor RPM 1755 RPM Motor Type ASGHUW 10- Motor Rated Volts 230/460 Volts Motor Phase 3 Motor Hertz 60 Hz Motor FL Amps 8.6/4.3 Amps Motor Service Factor 1.15 Motor Frame 182T Nominal Efficiency 89.5 % Sheave Data MA-02/Supply Fan Motor Sheave Model DIRECT DRIVE Test Pressures Filter SP In -0.26 in. wc Filter SP Out -0.27 in. wc Cooling Coil SP In -0.27 in. wc Cooling Coil SP Out -0.46 in. wc Heating Coil SP In NO ACCESS in. wc Heating Coil SP Out 0.18 in. wc Fan SP In NO ACCESS in. wc Fan SP Out NO ACCESS in. wc Final Filter SP In -0.46 in. wc Final Filter SP Out NO ACCESS in. wc Certified Balancing and Commissioning Page 3 of 4 Air Handling UnitPROJECT:LOCATION:THE MARKET AT VAILVAIL, CO 2663PROJECT #: DATE:CONTACT: AUTHOR: 5/21/2018Kara Handley System/Unit Outlet Type Size LxW / D AK Factor Design Airflow Prelim Airflow % Prelim Diff. Final Airflow % Final Diff. Outlet-01 SD 185 195 105 195 105 Outlet-02 SD 185 180 97 185 100 Outlet-03 SD 185 200 108 195 105 Outlet-04 SD 185 205 111 195 105 Outlet-05 SD 185 195 105 190 103 Outlet-06 SD 185 190 103 180 97 Outlet-07 SD 185 180 97 185 100 Outlet-08 SD 185 175 95 185 100 Outlet-09 SD 150 165 110 145 97 Outlet-10 SD 185 180 97 185 100 Outlet-11 SD 185 195 105 195 105 Outlet-12 SD 185 200 108 185 100 Outlet-13 SD 185 195 105 200 108 Outlet-14 SD 185 180 97 190 103 Outlet-15 SD 185 185 100 195 105 Outlet-16 SD 185 195 105 200 108 Outlet-17 SD 185 200 108 190 103 Totals:---3110 3215 103 3195 103 MA-02 Supply Outlet Summary Certified Balancing and Commissioning Page 4 of 4 Fan UnitPROJECT:LOCATION:THE MARKET AT VAILVAIL, CO 2663PROJECT #: DATE:CONTACT: AUTHOR: 5/21/2018Kara Handley Tested By:Daniel Takacs Date:5/18/2018 SYSTEM/UNIT: EF-01 Unit Data Fan Manufacturer JENCOFAN Fan Model Number FF150 Test Data Design Airflow 100 CFM Actual Airflow 145 CFM Fan Actual RPM DIRECT DRIVE RPM Motor Volts T1-T2 121 Volts Motor Amps T1 1.10 Amps Suction SP ATMOSPHERE in. wc Discharge SP NO ACCESS in. wc Motor Data Motor Rated Volts 120 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.30 Amps Sheave Data Motor Sheave Model DIRECT DRIVE Tested By:Daniel Takacs Date:5/18/2018 SYSTEM/UNIT: EF-02 Unit Data Fan Manufacturer JENCOFAN Fan Model Number FF150 Test Data Design Airflow 100 CFM Actual Airflow 150 CFM Fan Actual RPM DIRECT DRIVE RPM Motor Volts T1-T2 121 Volts Motor Amps T1 1.10 Amps Suction SP ATMOSPHERE in. wc Discharge SP NO ACCESS in. wc Motor Data Motor Rated Volts 120 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 1.30 Amps Sheave Data Motor Sheave Model DIRECT DRIVE Tested By:Daniel Takacs Date:5/18/2018 SYSTEM/UNIT: EF-03 Unit Data Fan Manufacturer JENCOFAN Fan Model Number FF700 Test Data Design Airflow 400 CFM Actual Airflow 415 CFM Fan Actual RPM DIRECT DRIVE RPM Motor Volts T1-T2 121 Volts Motor Amps T1 1.70 Amps Suction SP ATMOSPHERE in. wc Discharge SP 0.19 in. wc Motor Data Motor Manufacturer BROAN Motor RPM 910 RPM Motor Rated Volts 120 Volts Motor Phase 1 Motor Hertz 60 Hz Motor FL Amps 2.50 Amps Sheave Data Motor Sheave Model DIRECT DRIVE Certified Balancing and Commissioning Page 1 of 1 123467891011DABC5EML 111SERVICE AREAML 109ELECTICAL CL.ML 110PREP ROOMML 103GROCERIESML113OFFICEML 100VESTIBULEML 104DAIRY COOLERML 101LIQUOR STOREML112HALLML 102BEER/WINE COOLERML 105MECHANICALML106MEN'S RESTROOMML 108HALLML107WOMEN'S RESTROOMMECHANICAL -FLOOR PLANM1-1DATE:CHECKED BY:JOB NO:DRAWN BY:DATE:ISSUED FOR:SHEET NUMBER:Bighorn Consulting Engineers, Inc. Mechanical & Electrical Engineers 569 S. Westgate Dr., Suite 1 Grand Junction, CO 81505 phone: 970-241-8709, fax: 970-241-9514 THE MARKET AT VAIL 430 EAST LIONSHEAD CIRCLESCALE:AS SHOWN09/22/17FINAL REVIEWBCEBCE09/22/201717-121VAIL, COLORADO 81657 --11/7/1711/17/1712/06/17EF-1EF-2MA-2123456789123456MA-178910111213141516171011121314151617EF-3 M1-3DATE:CHECKED BY:JOB NO:DRAWN BY:DATE:ISSUED FOR:SHEET NUMBER:Bighorn Consulting Engineers, Inc. Mechanical & Electrical Engineers 569 S. Westgate Dr., Suite 1 Grand Junction, CO 81505 phone: 970-241-8709, fax: 970-241-9514 THE MARKET AT VAIL 430 EAST LIONSHEAD CIRCLESCALE:AS SHOWN09/22/17FINAL REVIEWBCEBCE09/22/201717-121VAIL, COLORADO 81657 --11/7/1711/17/1712/06/17ELECTRIC BASEBOARD SCHEDULEEQUIPMENT NO.SERVICELOCATIONLENGTH(FT)HEAT OUTPUT(BTU)ELEMENTMANUFACTURER & MODELFINISHOPTIONS/ACCESSORIESWATTSAMPSV./PH./CY.EB-1RESTROOMWALL32,0486002.9208/1/60RAYWALL, F3906-36CWHITESEE NOTE 1 NOTES:1. WITH INTEGRAL THERMOSTAT, THERMAL LIMIT, 12 GAUGE COVER. EXHAUST FAN SCHEDULEEQUIPMENT NO.SERVICELOCATIONCFMEXTERNAL STATICPRESS (IN. W.G.)MOTORMANUFACTURER & MODELOPTIONS/ACCESSORIESWATTSHPRPMVOLT/PH/HZEF-1, 2RESTOOMSCEILING1000.5100NA1075120/1/60COOK, GC-148SEE NOTE 1EF-3REF ROOMCEILING4000.5300.00NA1500120/1/60COOK, GC-642SEE NOTE 1 NOTES:1. PROVIDE SOLID STATE SPEED CONTROLLER, EC MOTOR, VIBRATION ISOLATORS, BACKDRAFT DAMPER, DISCONNECT SWITCH.GAS FIRED MAKE-UP AIR UNIT SCHEDULEEQUIPMENT NO.SERVICESUPPLY AIR (CFM)EXTERNALSTATIC PRESS. (IN.W.G.)INPUT (MBH)OUTPUT (MBH)EFFICIENCYA.F.U.E.GAS RATE(CFH)ELECTRICMANUFACTURER & MODELWEIGHT (LBS)OPTIONS/ACCESSORIESHPV/PH/HZMA-1, 2MARKET30000.7540032480%4943208/3/60GREASEMASTER,GM2-IBT-400-200-200-20D1876SEE NOTE 1NOTES:1. PROVIDE WITH MOTORIZED BACKDRAFT DAMPER, HIGH ALTITUDE KIT, HEATED CONDENSATE DRAIN, IBT EVAP INTERLOCK, EVAP FREEZE PROTECTION, INDOOR HANGING OPTION, MIXING BOX WITH OUTSIDE AIR CONTROL, MERV 8 FILTERS,VFD, OCCUPIED SCHEDULING.LOUVER SCHEDULEEQUIPMENT NO.SERVICEWIDTH (IN)HEIGHT (IN)THICKNESS OF WALL (IN)MATERIALINSECT/BIRD SCREENMANUFACTURER & MODELOPTIONS/ACCESSORIESLV-1INTAKE44446STEELINSECT NOTES: 1.INTAKE AND RELIEF HOOD SCHEDULEEQUIPMENT NO.THROATSIZE(Lin X Win)HOOD SIZE(Lin X Win)TYPEMANUFACTURER & MODELOPTIONS/ACCESSORIESRH-134X3446X46RELIEFCOOK, TRESEE NOTE 1NOTES:1. PROVIDE ROOF CURB, INSECT SCREEN, MOTORIZED DAMPER.ELECTRIC UNIT HEATER SCHEDULEEQUIPMENTNO.SERVICECFMHPRPMBTU/HRKWAIR TEMP.RISE (F)FULL LOADAMPS (FLA)V/PH/HZMANUFACTURER & MODELOPTIONS/ACCESSORIESEUH-1ENTRY175NA6005,1202NA12.5120/1/60RAYWALL, AFA115DSEE NOTE 1NOTES:1. PROVIDE WITH DISCONNECT SWITCH, THERMAL RESET, BUILT IN THERMOSTAT.GRILLE-REGISTER-DIFFUSER SCHEDULEEQUIPMENT NO.SIZEMODELMANUFACTURERFINISHOPTIONS/ACCESSORIESA14"X6"520PRICEWHITEOBDB120"X14"530PRICEWHITEC24"X24"80PRICEWHITE 123467891011DABC5EML 111SERVICE AREAML 109ELECTICAL CL.ML 110PREP ROOMML 103GROCERIESML113OFFICEML 100VESTIBULEML 104DAIRY COOLERML 101LIQUOR STOREML112HALLML 102BEER/WINE COOLERML 105MECHANICALML106MEN'S RESTROOMML 108HALLML107WOMEN'S RESTROOMPLUMBING -FLOOR PLANP1-1DATE:CHECKED BY:JOB NO:DRAWN BY:DATE:ISSUED FOR:SHEET NUMBER:Bighorn Consulting Engineers, Inc. Mechanical & Electrical Engineers 569 S. Westgate Dr., Suite 1 Grand Junction, CO 81505 phone: 970-241-8709, fax: 970-241-9514 THE MARKET AT VAIL 430 EAST LIONSHEAD CIRCLESCALE:AS SHOWN09/22/17FINAL REVIEWBCEBCE09/22/201717-121VAIL, COLORADO 81657 --11/7/1711/17/1712/06/17 P1-3DATE:CHECKED BY:JOB NO:DRAWN BY:DATE:ISSUED FOR:SHEET NUMBER:Bighorn Consulting Engineers, Inc. Mechanical & Electrical Engineers 569 S. Westgate Dr., Suite 1 Grand Junction, CO 81505 phone: 970-241-8709, fax: 970-241-9514 THE MARKET AT VAIL 430 EAST LIONSHEAD CIRCLESCALE:AS SHOWN09/22/17FINAL REVIEWBCEBCE09/22/201717-121VAIL, COLORADO 81657 --11/7/1711/17/1712/06/17ELECTRIC WATER HEATER SCHEDULEEQUIPMENT NO.CAPACITY(GAL)RECOVERY @ 90DEG. F. RISEBTU/HWATER CONN.HEATING ELEMENT(KW)V/PH/HZMANUFACTURER & MODELOPTIONS/ACCESSORIESWH-115NA68003/4"2.0120/1/60RHEEM, PROE15SEE NOTE 1NOTES:1. PROVIDE WITH ASME RELIEF VALVE, ANODE ROD.PLUMBING FIXTURE SCHEDULEFIXTURE NO.DESCRIPTIONMANUFACTURERMODELTRIMPIPING CONNECTIONSOPTIONS-ACCESSORIESS/WVENTC.W.HWEP-1EFFLUENT PUMPLIBERTY405NA2"2"1/2 HP MOTOR, 115 VOLT, CHECK VALVE, POWER CORD, POLYOLEFIN BASINFD-1FLOOR DRAINJR SMITH3"2"--PROVIDE NICKLE BRONZE STRAINERLV-1WALL MOUNTED BATHROOM SINKAMERICAN STANDARD1 1/2"1 1/2"1/2"1/2"GRID DRAINWC-1ADA MACERATING WATER CLOSETLIBERTY ASCENT IIASCENTII-ESWFLUSH VALVE KIT1-1/2"1-1/2"3/4"-1/2 HP MOTOR, CUTTER, ALARM, SEAT, LID, POWER CORD, 115 V.RESPONSIBLE DIVISIONITEMFURNISHEDSETPOWER-WIREDCONTROLWIREDEQUIPMENT232326-MAG MOTOR STARTERS23262623DISCONNECT SWITCHES26(1)26(1)26-SWITCHES, MANUAL AND MULTI-SPEED232626-CONTROLS, RELAYS, TRANSFORMERS23232623THERMOSTATS AND TIME SWITCHES23232623LINE VOLTAGE THERMOSTATS23232626T.C. CONTROL PANELS23232623MOTOR AND SOLENOID VALVES DAMPER MOTORS2323(2)-23(2)PUSH BUTTONS AND PILOT LIGHTS2323(2)-23(2)HVAC CONTROLS23232623EXHAUST FAN SWITCHES23262623(2)FIRE PROTECTION CONTROLS26262626FIRE AND SMOKE DETECTORS26(3)26(3)2626(3)(1) UNDER DIVISION 23 IF FURNISHED FACTORY-WIRED AS PART OR IF FURNISHED WITH COMBINATIONSTARTERS.(2) IF ITEM IS FOR LINE VOLTAGE, SET IN PLACE AND CONNECT UNDER DIVISION 26. WHERE FACTORYMOUNTED ON EQUIPMENT OR ATTACHED TO PIPING OR DUCTS AND USING LINE VOLTAGE FURNISH AND SETUNDER DIVISION 23, CONNECT UNDER DIVISION 26.(3) FOR UNITS FACTORY MOUNTED IN OR ON MECHANICAL EQUIPMENT OR DUCTS, FAN STOP CONNECTIONSSHALL BE UNDER DIVISION 23, ALL OTHER CONNECTIONS UNDER DIVISION 26. 123467891011DABC5EML 111SERVICE AREAML 109ELECTICAL CL.ML 110PREP ROOMML 103GROCERIESML113OFFICEML 100VESTIBULEML 104DAIRY COOLERML 101LIQUOR STOREML112HALLML 102BEER/WINE COOLERML 105MECHANICALML106MEN'S RESTROOMML 108HALLML107WOMEN'S RESTROOMELECTRICAL -FLOOR PLANE2-1DATE:CHECKED BY:JOB NO:DRAWN BY:DATE:ISSUED FOR:SHEET NUMBER:Bighorn Consulting Engineers, Inc. Mechanical & Electrical Engineers 569 S. Westgate Dr., Suite 1 Grand Junction, CO 81505 phone: 970-241-8709, fax: 970-241-9514 THE MARKET AT VAIL 430 EAST LIONSHEAD CIRCLESCALE:AS SHOWN09/22/17FINAL REVIEWBCEBCE09/22/201717-121VAIL, COLORADO 81657 --11/7/1711/17/1712/06/17 MECHANICAL EQUIPMENT SCHEDULEREFRIGERATION EQUIPMENT SCHEDULEONE LINE DIAGRAMSCHEMATIC FOR A GROUNDING ELECTRODE SYSTEME2-3DATE:CHECKED BY:JOB NO:DRAWN BY:DATE:ISSUED FOR:SHEET NUMBER:Bighorn Consulting Engineers, Inc. Mechanical & Electrical Engineers 569 S. Westgate Dr., Suite 1 Grand Junction, CO 81505 phone: 970-241-8709, fax: 970-241-9514 THE MARKET AT VAIL 430 EAST LIONSHEAD CIRCLESCALE:AS SHOWN09/22/17FINAL REVIEWBCEBCE09/22/201717-121VAIL, COLORADO 81657 --11/7/1711/17/1712/06/17