HomeMy WebLinkAboutRES check 1255 Westhaven.pdf rREScheck Software Version 4.6.2
%ilh Compliance Certificate
Project Lipnick ResidenceriwNPoa,z.ct ,
I.
Energy Code: 2015 IECC i Al �' '•O fl
Location: Vail, Colorado :cam 3/13/17 ic,•
ift
Construction Type: Single-family39•
Project Type: New Construction 1 • • 5
Conditioned Floor Area: 6,140 ft2 CO 5* , �•,.• �
Glazing Area 23%
Climate Zone: 6 (9248 HDD) '�► tS �
Permit Date:
Permit Number:
Construction Site: Owner/Agent: Designer/Contractor:
1255 Westhaven Circle Robert Lipnick Heather Barrie
Vail, CO 81657 1255 Westhaven Circle K.H. Webb Architects
Vail, CO 81657 710 West Lionshead Circle
301-938-0585 Unit A
RNLipnick@gmail.com Vail, CO 81657
970-477-2990
heather@khwebb.com
Compliance: Passes using UA trade-off
Compliance: 3.7%Better Than Code Maximum UA: 1166 Your UA: 1123
The%Better or Worse Than Code Index reflects how close to compliance the house is based on code trade-off rules.
It DOES NOT provide an estimate of energy use or cost relative to a minimum-code home.
Envelope Assemblies
Gross Area Cavity Cont.
Assembly or R-Value R-Value U-Factor UA
Perimeter
Roof: Flat Ceiling or Scissor Truss 3,399 22.0 27.5 0.020 68
Above Grade Walls: Wood Frame, 16" o.c. 6,912 14.0 10.0 0.043 228
Windows (U=0.29): Wood Frame:Double Pane with Low-E 517 0.290 150
Windows (U=0.39): Wood Frame:Double Pane with Low-E 280 0.390 109
Glass Doors (U=0.29): Glass 323 0.290 94
Glass Doors (U=0.34): Glass 260 0.340 88
Glass Doors (U=0.39): Glass 210 0.390 82
Solid Doors: Solid 29 0.300 9
Below Grade Walls: Solid Concrete or Masonry 1,979 14.0 10.0 0.031 61
Wall height: 11.0'
Depth below grade: 11.0'
Insulation depth: 11.0'
Floor Over Outside: All-Wood Joist/Truss:Over Outside Air 105 38.0 0.0 0.026 3
Slab on Grade: Slab-On-Grade:Heated 337 10.0 0.684 231
Insulation depth: 6.0'
Project Title: Lipnick Residence Report date: 03/13/17
Data filename:J:\Jobs\2016 -Jobs\16090.00 - Lipnick Page 1 of10
Residence\Mechanical\Calculations\Rescheck\16090-Rescheck.rck
Compliance Statement: The proposed building design described here is consistent with the building plans, specifications, and other
calculations submitted with the permit application.The proposed building has been designed to meet the 2015 IECC requirements in
REScheck Version 4.6.2 and to comply with the mandatory requirements listed in the REScheck Inspection Checklist.
Joey Brenner- Mechanical Engineer 3/13/17
Name-Title Signature / // Date
Project Notes:
Calcs By:Joey Brenner- Rader Engineering (970)-845-7910
Project Title: Lipnick Residence Report date: 03/13/17
Data filename:J:\Jobs\2016 -Jobs\16090.00 - Lipnick Page 2 of10
Residence\Mechanical\Calculations\Rescheck\16090-Rescheck.rck
RInspectionEScheck Software VersionChecklist 4.6.2
Energy Code: 2015 IECC
Requirements: 0.0% were addressed directly in the REScheck software
Text in the "Comments/Assumptions" column is provided by the user in the REScheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section Plans Verified Field Verified
# Pre-Inspection/Plan Review Value Value Complies? Comments/Assumptions
& Req.ID
103.1, 'Construction drawings and '❑Complies
103.2 documentation demonstrate ❑Does Not
[PR1]1 energy code compliance for the
La building envelope.Thermal ❑Not Observable
envelope represented on ❑Not Applicable
construction documents.
103.1, Construction drawings and ❑Complies i
103.2, documentation demonstrate EDoes Not
403.7 energy code compliance for
[PR3]1 lighting and mechanical systems. ['Not Observable
Systems serving multiple ENot Applicable
dwelling units must demonstrate
compliance with the IECC
Commercial Provisions.
302.1, Heating and cooling equipment is Heating: Heating: ❑Complies
403.7 sized per ACCA Manual S based Btu/hr Btu/hr EDoes Not
[PR2]z on loads calculated per ACCA Cooling: Cooling:
y, Manual J or other methods ['Not Observable
Btu/hr Btu/hr
approved by the code official. ❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Lipnick Residence Report date: 03/13/17
Data filename:J:\Jobs\2016 -Jobs\16090.00 - Lipnick Page 3 of10
Residence\Mechanical\Calculations\Rescheck\16090-Rescheck.rck
Section Plans Verified Field Verified
# Foundation Inspection Value Value Complies? Comments/Assumptions
& Req.ID
402.1.2 Slab edge insulation R-value. R- R- ❑Complies See the Envelope Assemblies
[Foil' ❑ Unheated ❑ Unheated ❑Does Not table for values.
O ❑ Heated ❑ Heated [Not Observable
ENot Applicable
402.1.2 Slab edge insulation ft ft EComplies See the Envelope Assemblies
[FO3]' depth/length. ❑Does Not table for values.
O ['Not Observable
j ENot Applicable
402.1.1 Conditioned basement wall R- R- ❑Complies See the Envelope Assemblies
[FO4]' insulation R-value.Where interior R- R- ❑Does Not table for values.
410 insulation is used, verification ['Not Observable
may need to occur during
Insulation Inspection. Not ENot Applicable
required in warm-humid locations
in Climate Zone 3.
303.2 Conditioned basement wall ❑Complies
[FO5]' insulation installed per ❑Does Not
al manufacturer's instructions.
[Not Observable
,❑Not Applicable
402.2.9 Conditioned basement wall ft ft ❑Complies See the Envelope Assemblies
1[FO6]' insulation depth of burial or El Does Not table for values.
distance from top of wall.
❑Not Observable
ENot Applicable
303.2.1 A protective covering is installed ❑Complies
[FO11]2 to protect exposed exterior ❑Does Not
insulation and extends a
9,1
minimum of 6 in. below grade. ['Not Observable
ENot Applicable
403.9 Snow-and ice-melting system ❑Complies
[FO controls installed. ❑Does Not
['Not Observable
ENot Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Lipnick Residence Report date: 03/13/17
Data filename:J:\Jobs\2016 -Jobs\16090.00 - Lipnick Page 4 of10
Residence\Mechanical\Calculations\Rescheck\16090-Rescheck.rck
Section Plans Verified Field Verified
# Framing/Rough-In Inspection Value Value Complies? Comments/Assumptions
& Req.ID
402.1.1, :Door U-factor. U- U- ❑Complies See the Envelope Assemblies
402.3.4 ❑Does Not table for values.
[Fii) , ❑Not Observable
❑Not Applicable
402.1.1, 1 Glazing U-factor(area-weightedU- U- ❑Complies See the Envelope Assemblies
402.3.1, average). I El Does Not table for values.
402.3.3,
402.3.6,
[Not Observable
402.5 : ❑Not Applicable
[FR2]1
303.1.3 1U-factors of fenestration products ❑Complies
[FR4]1 are determined in accordance ❑Does Not
9i, with the NFRC test procedure or
taken from the default table. ❑Not Observable
❑Not Applicable
402.4.1.1 ;Air barrier and thermal barrier ❑Complies
[FR23]1 installed per manufacturer's ❑Does Not
9i, ,instructions.
❑Not Observable
; ❑Not Applicable
402.4.3 ;Fenestration that is not site built ❑Complies
[FR20]1 is listed and labeled as meeting ❑Does Not
AAMA/WDMA/CSA 101/1.5.2/A440
or has infiltration rates per NFRC ❑Not Observable
400 that do not exceed code ❑Not Applicable
limits.
402.4.5 :IC-rated recessed lighting fixtures ❑Complies
[FR16]2 sealed at housing/interior finish ❑Does Not
;and labeled to indicate <_2.0 cfm
;leakage at 75 Pa. ❑Not Observable
❑Not Applicable
403.2.1 Supply and return ducts in attics ❑Complies
[FR12]1 insulated >= R-8 where duct is El Does Not
Ca >= 3 inches in diameter and >_
R-6 where < 3 inches. Supply and [Not Observable
return ducts in other portions of ❑Not Applicable
the building insulated >= R-6 for
diameter>= 3 inches and R-4.2
for< 3 inches in diameter.
403.3.3.5 Building cavities are not used as ■❑Complies
[FR15]3 ducts or plenums. ❑Does Not
❑Not Observable
❑Not Applicable
403.4 HVAC piping conveying fluids R- R- ❑Complies
[FR17] above 105 °F or chilled fluids ❑Does Not
below 55 °F are insulated to >_R-
3 ❑Not Observable
❑Not Applicable
403.4.1 :Protection insulation on HVAC I❑Complies
[FR24]1 piping. ❑Does Not
fi ❑Not Observable
❑Not Applicable
403.5.3 Hot water pipes are insulated to R- R- ElComplies
[FR18]2 >_R-3. ❑Does Not
0 ❑Not Observable
❑Not Applicable
403.6Automatic or gravity dampers are ❑Complies
[FR19] installed on all outdoor air El Does Not
intakes and exhausts.
[Not Observable
❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Lipnick Residence Report date: 03/13/17
Data filename:J:\Jobs\2016 -Jobs\16090.00 - Lipnick Page 5 of10
Residence\Mechanical\Calculations\Rescheck\16090-Rescheck.rck
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Lipnick Residence Report date: 03/13/17
Data filename:J:\Jobs\2016 -Jobs\16090.00 - Lipnick Page 6 of10
Residence\Mechanical\Calculations\Rescheck\16090-Rescheck.rck
Section Plans Verified Field Verified
# Insulation Inspection Value Value Complies? Comments/Assumptions
& Req.ID
303.1 ;All installed insulation is labeled '❑Complies
[IN13]2 or the installed R-valuesIP ❑Does Not
✓ :provided.
[Not Observable
❑Not Applicable
402.1.1, Floor insulation R-value. R- R- ❑Complies See the Envelope Assemblies
402.2.6 ❑ Wood ❑ Wood El Does Not table for values.
[IN1]1 ❑ Steel ❑ Steel [Not Observable
ogp
ENot Applicable
303.2, Floor insulation installed per ❑Complies
402.2.7 manufacturer's instructions and ❑Does Not
[IN2]1 in substantial contact with the
underside of the subfloor, or floor ['Not Observable
framing cavity insulation is in ❑Not Applicable
contact with the top side of
sheathing, or continuous
insulation is installed on the
underside of floor framing and
extends from the bottom to the
top of all perimeter floor framing
members.
402.1.1, Wall insulation R-value. If this is a R- R- EComplies See the Envelope Assemblies
402.2.5, mass wall with at least 1/2 of the ❑ Wood ❑ Wood ❑Does Not table for values.
402.2.6 wall insulation on the wall ❑ Mass ❑ Mass ['Not Observable
[IN3]1 exterior,the exterior insulation
requirement applies(FR10).
111 Steel III Steel ❑Not Applicable
303.2 Wall insulation is installed per 1 ❑Complies
[IN4]1 manufacturer's instructions. ❑Does Not
[Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Lipnick Residence Report date: 03/13/17
Data filename:J:\Jobs\2016 -Jobs\16090.00 - Lipnick Page 7 of10
Residence\Mechanical\Calculations\Rescheck\16090-Rescheck.rck
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.ID
402.1.1, ;Ceiling insulation R-value. R- R- ❑Complies See the Envelope Assemblies
402.2.1, ❑ Wood ❑ Wood EDoes Not table for values.
402.2.2, ❑ Steel ❑ Steel [Not Observable
402.2.6
[FI1]1 ENot Applicable
303.1.1.1, Ceiling insulation installed per 'EComplies
303.2 manufacturer's instructions. ❑Does Not
[F12]1 Blown insulation marked every
300 ft2. [Not Observable
❑Not Applicable
402.2.3 :Vented attics with air permeable EComplies
[F122]2 insulation include baffle adjacent ❑Does Not
to soffit and eave vents that
:extends over insulation. [Not Observable
j ❑Not Applicable
402.2.4 Attic access hatch and door R- R- EComplies
[F13]1 insulation >_R-value of the ❑Does Not
adjacent assembly.
[Not Observable
❑Not Applicable
402.4.1.2 Blower door test @ 50 Pa. <=5 ACH 50 = ACH 50 = EComplies
[F117]1 ach in Climate Zones 1-2, and ❑Does Not
<=3 ach in Climate Zones 3-8.
[Not Observable
❑Not Applicable
403.2.3 Duct tightness test result of<=4 cfm/100 cfm/100 EComplies
[F14]1 cfm/100 ft2 across the system or ft2 ft2 ❑Does Not
<=3 cfm/100 ft2 without air
handler @ 25 Pa. For rough-in ['Not Observable
tests,verification may need to ENot Applicable
occur during Framing Inspection.
403.3.2 Ducts are pressure tested to cfm/100 cfm/100 EComplies
[F127]1 determine air leakage with ft2 ft2 ❑Does Not
either: Rough-in test:Total
leakage measured with a ['Not Observable
pressure differential of 0.1 inch ENot Applicable
w.g. across the system including
the manufacturer's air handler
enclosure if installed at time of
test. Postconstruction test:Total
leakage measured with a
pressure differential of 0.1 inch
w.g. across the entire system
including the manufacturer's air
handler enclosure.
403.3.2.1 Air handler leakage designated EComplies
[F124]1 by manufacturer at<=2%of ❑Does Not
design air flow.
[Not Observable
❑Not Applicable
403.1.1 :Programmable thermostats EComplies
[F19]2 installed for control of primary ❑Does Not
;heating and cooling systems and
:initially set by manufacturer to ENot Observable
:code specifications. ❑Not Applicable
i
403.1.2 'Heat pump thermostat installed ❑Complies
[F110]2 ion heat pumps. ElDoes Not
ENot Observable
ElNot Applicable
403.5.1 Circulating service hot water qElComPlies
[FI11]2 have o ❑Does
accessible
systems manualautcontrols.maticor.
❑Not ObservableNot
ENot Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Lipnick Residence Report date: 03/13/17
Data filename:J:\Jobs\2016 -Jobs\16090.00 - Lipnick Page 8 of10
Residence\Mechanical\Calculations\Rescheck\16090-Rescheck.rck
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.ID
403.6.1 ;All mechanical ventilation system ' 'ElComplies
[F125]z fans not part of tested and listed ❑Does Not
ail
HVAC equipment meet efficacy
and air flow limits. ❑Not Observable
❑Not Applicable
403.2 Hot water boilers supplying heat ❑Complies
[F126]z through one-or two-pipe heating ❑Does Not
441 systems have outdoor setback
control to lower boiler water ❑Not Observable
temperature based on outdoor ENot Applicable
temperature.
403.5.1.1 :Heated water circulation systems ❑Complies
[F128]2 have a circulation pump.The ❑Does Not
system return pipe is a dedicated
return pipe or a cold water supply ❑Not Observable
pipe. Gravity and thermos- ENot Applicable
syphon circulation systems are
not present. Controls for
circulating hot water system
pumps start the pump with signal
for hot water demand within the
iii'occupancy. Controls
automatically turn off the pump
when water is in circulation loop
is at set-point temperature and
no demand for hot water exists.
403.5.1.2 'Electric heat trace systems ❑Complies
[F129]2 comply with IEEE 515.1 or UL EDoes Not
515. Controls automatically
adjust the energy input to the ['Not Observable
heat tracing to maintain the ENot Applicable
desired water temperature in the ,
piping.
403.5.2 Water distribution systems that ;❑Complies
[F130]2 have recirculation pumps that ElDoes Not
pump water from a heated water
supply pipe back to the heated ❑Not Observable
water source through a cold ❑Not Applicable
water supply pipe have a
demand recirculation water
system. Pumps have controls
that manage operation of the
pump and limit the temperature
of the water entering the cold
:water piping to 104°F.
403.5.4 Drain water heat recovery units
❑Complies
[F13tested tested in accordance with CSA ❑Does Not
B55.1. Potable water-side
pressure loss of drain water heat ❑Not Observable
recovery units < 3 psi for ;❑Not Applicable
individual units connected to one
or two showers. Potable water-
side pressure loss of drain water
heat recovery units < 2 psi for
:individual units connected to
:three or more showers.
i
404.1 '75%of lamps in permanent ❑Complies
[F16]' fixtures or 75%of permanent ❑Does Not
fixtures have high efficacy lamps.
Does not apply to low-voltage ❑Not Observable
lighting. ENot Applicable
1
404.1.1 Fuel gas lighting systems have ❑Complies
[F123]3 no continuous pilot light. ❑Does Not
[Not Observable
❑Not Applicable
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Lipnick Residence Report date: 03/13/17
Data filename:J:\Jobs\2016 -Jobs\16090.00 - Lipnick Page 9 of10
Residence\Mechanical\Calculations\Rescheck\16090-Rescheck.rck
Section Plans Verified Field Verified
# Final Inspection Provisions Value Value Complies? Comments/Assumptions
& Req.ID
401.3 Compliance certificate posted. '❑Complies
[F17F ❑Does Not
[Not Observable
❑Not Applicable
303.3 Manufacturer manuals for ❑Complies
[F118P mechanical and water heating ❑Does Not
systems have been provided. •
[Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: Lipnick Residence Report date: 03/13/17
Data filename:J:\Jobs\2016 -Jobs\16090.00 - Lipnick Page 10 of10
Residence\Mechanical\Calculations\Rescheck\16090-Rescheck.rck
ci. 2015 IECC Energy
Efficiency Certificate
Insulation Ratin. - e
Above-Grade Wall 24.00
Below-Grade Wall 24.00
Floor 10.00
Ceiling / Roof 49.50
Ductwork (unconditioned spaces):
Glass& Door Rating U-Factor SHGC
Window 0.29
Door 0.29
Heating&Cooling Equipment Efficiency
Heating System:
Cooling System:
Water Heater:
Name: Date:
Comments