May 22, 2018
Tina and David Wilson
2609 Davos Trail
Vail, Colorado 81657
tinawilsonvail@gmail.com
Project No. 18-7-289
Subject: Observation of Excavation, Proposed Additions to Residence, Lot 11, Filing 23,
Vail Valley, 1945 Sunburst, Vail, Colorado
Dear Mrs. and Mr. Wilson:
As requested, a representative of H-P/Kumar observed the excavation at the subject site on May
16, 2018 to evaluate the soils exposed for foundation support. The findings of our observations
and recommendations are presented in this report. The services were performed in accordance
with our agreement for professional engineering services to you, dated April 23, 2016.
Building additions are planned on the northwest and northeast sides of the residence. The
northwest addition will be new'living area with a slab-on-grade floor. The northeast addition
will be new deck area. The additions have been designed to be supported on spread footings
using an allowable soil bearing pressure of 2,000 psf based on a previous subsoil study at the site
by Chen-Northern, Inc. dated September 29,1993, Job No. 4 257 93. We have been provided a
copy of that report. The existing residence is apparently founded on shallow spread footings
with no signs of excessive settlement and distress reported.
At the time of our site visit, the foundation excavations were essentially complete and had been
cut in three levels from about 4 to 8 feet below the adjacent ground surface. The steps in grade
between the excavation levels were about 21/2 to 4 feet. The excavation subgrade was at the same
elevation as the existing residence spread footing bearing elevation. The soils exposed in the
bottom of the excavations consisted of medium dense, silty clayey sand and gravel with cobbles.
The results of a gradation analysis performed on a sample of the granular soils (minus 3 inch
Tina and David Wilson
May 22, 2018
Page 2
fraction) obtained from the site are presented on Figure 1. No free water was encountered in the
excavation and the soils were generally moist.
Considering the conditions exposed in the excavations and the nature of the proposed
construction, spread footings placed on the undisturbed natural granular soil designed for an
allowable bearing pressure of 2,000 psf can be used for support of the proposed additions. There
could be some differential settlement with respect to the existing structure which should be
considered in the design. Footings should be a minimum width of 16 inches for continuous walls
and 2 feet for columns. Any existing fill and all loose disturbed soils in footing areas should be
removed and the bearing level extended down to the undisturbed natural granular soils, and the
subgrade compacted. Exterior footings should be provided with adequate soil cover above their
bearing elevations for frost protection. Continuous foundation walls should be reinforced top
and bottom to span local anomalies such as by assuming an unsupported length of at least 10
feet. Foundation walls acting as retaining structures should also be designed to resist a lateral
earth pressure based on an equivalent fluid unit weight of at least 45 pcf for on-site soil
(excluding debris, topsoil and plus 6-inch size rocks) as backfill. A perimeter foundation drain
should be provided to prevent temporary buildup of hydrostatic pressure behind the foundation
walls and prevent wetting of the lower level. Structural fill placed within floor slab areas can
consist of the on-site sand and gravel soils compacted to at least 95% of standard Proctor density
(SPD) at a moisture content near optimum. Backfill placed around the structure should be
compacted to at least 90% SPD (95% in pavement areas) and the surface graded to prevent
ponding within at least 10 feet of the building. Landscape that requires regular heavy irrigation,
such as sod, and lawn sprinkler heads should not be located within 5 feet of the foundation.
The recommendations submitted in this letter are based on our observation of the soils exposed
within the foundation excavations and do not include subsurface exploration to evaluate the
subsurface conditions within the loaded depth of foundation influence. This study is based on
the assumption that soils beneath the footings have equal or better support than those exposed.
The risk of foundation movement may be greater than indicated in this report because of possible
variations in the subsurface conditions. In order to reveal the nature and extent of variations in
the subsurface conditions below the excavations, drilling would be required. It is possible the
H-Pk'KUMAR
Project No. 18-7-289
Tina and David Wilson
May 22, 2018
Page 3
data obtained by subsurface exploration could change the recommendations contained in this
letter. Our services do not include determining the presence,prevention or possibility of mold or
other biological contaminants (MOBC) developing in the future. If the client is concerned about
MOBC, then a professional in this special field of practice should be consulted.
If you have any questions or need further assistance, please call our office.
Sincerely,
t `ik
ii
.o 1.-; f
a ./ iii- .74
David A. Young, l 32`216
1. r, .Z3 j
DAY/kac �°+to ONAL � +
attachment Figure 1, Gradation Test Resiilts
cc: Evans Chaffee Construction—Mark Jones (mjones@evanschaffee.com)
H-PWUMAR
Project No. 18-7-289
HYDROMETER ANALYSIS SIEVE ANALYSIS
TIME READINGS U.S. STANDARD SERIES CLEAR SQUARE OPENINGS
24 HRS 7 MRS
10a 45 MIN 15 MIN 60MIN 19MIN 4MIN 1MIN a 00 #100 E 0#40#30 16 #10 8 4 3 8" 3 4" 1 1/2" " "6" 8"0
Ammo
_- i
90 -a ==��
10
60 _� _- I
___1____ 20
. •
70 MIIIII.
-� 30
60
us
E'.
��� I 40
50 z
IOWI 50
ti -1111140 I 60
ti
a -_®__ ES
a
30 1 I
I 70
I I
20 I I
T 1 80
10
I - I 90
0 -_�
.001 .002 .005 .009 .019 .037 .075 .150 .300 I .600 1.18 12.36 4.75 9.5 19 38.1 76.2 127 200 00
I DIAMETER OF PARTICLES IN MILLIMETERS 152
CLAY TO SILT SAND GRAVEL
-
FINE ' MEDIUM COARSE FINE COARSE COBBLES
•
•
GRAVEL 50 % - SAND 31 •% SILT AND CLAY 19
LIQUID LIMIT PLASTICITY INDEX
SAMPLE OF: Silty Cloyey Sand and Gravel FROM: Bottom of North East addition area
•
s'
EglE
i
j
SThese test results apply only to the
samples which were tested. The
d testing report shall not be reproduced,
except in full, without the written
ori approval of Kumar & Associates, Inc.
„q Sieve analysis testing Is performed in
accordance with ASTM D422, ASTM C136
e 6 and/or ASTM D1140.
"g 18-7-289 H-P- KUii#1AR GRADATION TEST RESULTS Fig. 1