HomeMy WebLinkAboutB18-0067_compliance-report-20180312_154113_680_1521237340.pdf irlA COMcheck Software Version 4.0.8.0
8(1 Interior Lighting Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: WESTWIND POOL REMODEL
Project Type: New Construction
Construction Site: Owner/Agent: Designer/Contractor:
VAIL, CO BILL PIERCE STANTON HUMPHRIES
PIERCE ARCHITECTS AEC
VAIL, CO AVON, CO
9704788520
Additional Efficiency Package(s) STAN@AEC-VAIL.COM
Dedicated Outdoor Air System
Allowed Interior Lighting Power
A B C D
Area Category Floor Area Allowed Allowed Watts
(ft2) Watts/ft2 (B X C)
1-POOL, ELEC,MECH ROOM(Common Space Types:Electrical/Mechanical) 700 0.95 665
2-POOL HOUSE(Common Space Types:Conference/Meeting/Multipurpose) 400 1.23 492
Total Allowed Watts= 1157
Proposed Interior Lighting Power
A B C D E
Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
1-POOL, ELEC, MECH ROOM (Common Space Types:Electrical/Mechanical)
LED 1: F: LED:Other: 1 9 34 306
2-POOL HOUSE (Common Space Types:Conference/Meeting/Multipurpose)
LED 2:C:VANITY:Other: 1 2 25 50
LED 3: D: DOWNLIGHT:Other: 1 3 16 49
LED 4:A: LED PENDENT W/LF:Other: 1 12 10 120
Total Proposed Watts= 525
Interior Lighting PASSES: Design 55% better than code
Interior Lighting Compliance Statement
Compliance Statement: The proposed interior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed interior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.8.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name-Title Signature Date
Project Title: WESTWIND POOL REMODEL Report date: 03/12/18
Data filename: Untitled.cck Page 1 of 7
irdt COMcheck Software Version 4.0.8.0
ii Exterior Lighting Compliance Certificate
Project Information
Energy Code: 2015 IECC
Project Title: WESTWIND POOL REMODEL
Project Type: New Construction
Exterior Lighting Zone 2 (Residential mixed use area)
Construction Site: Owner/Agent: Designer/Contractor:
VAIL, CO BILL PIERCE STANTON HUMPHRIES
PIERCE ARCHITECTS AEC
VAIL, CO AVON, CO
9704788520
STAN@AEC-VAIL.COM
Allowed Exterior Lighting Power
A B C D E
Area/Surface Category Quantity Allowed Tradable Allowed Watts
Watts/Unit Wattage (B X C)
DRIVEWAY AND POOL(Special feature area) 4700 ft2 0.14 Yes 658
Total Tradable Watts(a)= 658
Total Allowed Watts= 658
Total Allowed Supplemental Watts(b)= 600
(a)Wattage tradeoffs are only allowed between tradable areas/surfaces.
(b)A supplemental allowance equal to 600 watts may be applied toward compliance of both non-tradable and tradable areas/surfaces.
Proposed Exterior Lighting Power
A B C D E
Fixture ID : Description/Lamp/Wattage Per Lamp/Ballast Lamps/ #of Fixture (C X D)
Fixture Fixtures Watt.
DRIVEWAY AND POOL(Special feature area 4700 ft2): Tradable Wattage
LED 1:AA: EXTERIOR SCONCE:Other: 1 32 15 480
Total Tradable Proposed Watts= 480
Exterior Lighting PASSES: Design 62% better than code
Exterior Lighting Compliance Statement
Compliance Statement: The proposed exterior lighting design represented in this document is consistent with the building plans,
specifications, and other calculations submitted with this permit application.The proposed exterior lighting systems have been
designed to meet the 2015 IECC requirements in COMcheck Version 4.0.8.0 and to comply with any applicable mandatory
requirements listed in the Inspection Checklist.
Name-Title Signature Date
Project Title: WESTWIND POOL REMODEL Report date: 03/12/18
Data filename: Untitled.cck Page 2 of 7
COMcheck Software Version 4.0.8.0
Inspection Checklist
Energy Code: 2015 IECC
Requirements: 0.0% were addressed directly in the COMcheck software
Text in the "Comments/Assumptions" column is provided by the user in the COMcheck Requirements screen. For each
requirement, the user certifies that a code requirement will be met and how that is documented, or that an exception
is being claimed. Where compliance is itemized in a separate table, a reference to that table is provided.
Section
# Plan Review Complies? Comments/Assumptions
& Req.ID
C103.2 Plans, specifications, and/or ❑Complies
[PR4]1 calculations provide all information ❑Does Not
with which compliance can be
determined for the interior lighting ❑Not Observable
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
the standard are claimed. Information
provided should include interior
lighting power calculations, wattage of
bulbs and ballasts,transformers and
control devices.
C103.2 Plans, specifications, and/or ❑Complies
[PR8]1 calculations provide all information ❑Does Not
with which compliance can be
determined for the exterior lighting [Not Observable
and electrical systems and equipment ❑Not Applicable
and document where exceptions to
the standard are claimed. Information
provided should include exterior
lighting power calculations, wattage of
bulbs and ballasts,transformers and
control devices.
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: WESTWIND POOL REMODEL Report date: 03/12/18
Data filename: Untitled.cck Page 3 of 7
Section
# Rough-In Electrical Inspection Complies? Comments/Assumptions
& Req.ID
C405.2.1 I Lighting controls installed to uniformly ❑Complies
[EL15]1 :reduce the lighting load by at least ❑Does Not
50%. [Not Observable
; ENot Applicable
C405.2.1 ;Occupancy sensors installed in ❑Complies
[EL18]1 'required spaces. ❑Does Not
[Not Observable
ENot Applicable
C405.2.1, ;Independent lighting controls installed I❑Complies
C405.2.2. per approved lighting plans and all I❑Does Not
3manual controls readily accessible and
[EL23]2
3 !
visible to occupants. ❑Not Observable
ENot Applicable
C405.2.2. ;Automatic controls to shut off all ;❑Complies
1 :building lighting installed in all ❑Does Not
[EL22]2 ;buildings. III
Not Observable
; ❑Not Applicable
0 .3 Daylight zones provided with ❑Complies
individual controls that control the ❑Does Not
lights independent of general area
lighting. ❑Not Observable
❑Not Applicable
C405.2.3, 'Primary sidelighted areas are ❑Complies
C405.2.3. equipped with required lighting ❑Does Not
1, controls.
C405.2.3. [Not Observable
2 ❑Not Applicable
[EL20]1
1
C405.2.3, Enclosed spaces with daylight area ;❑Complies
C405.2.3. under skylights and rooftop monitors ❑Does Not
1, ;are equipped with required lighting
C405.2.3. ;controls. ENot Observable
3 ❑Not Applicable
[EL21]1
C405.2.4 Separate lighting control devices for ❑Complies
[EL4]1 specific uses installed per approved I❑Does Not
lighting plans.
ENot Observable
E Not Applicable
C405.2.4 Additional interior lighting power ❑Complies
[EL8]1 allowed for special functions per the ❑Does Not
approved lighting plans and is
automatically controlled and ❑Not Observable
separated from general lighting. ;❑Not Applicable
1
C405.2.5 Automatic lighting controls for exterior ❑Complies
[EL25]nu° lighting installed. Controls will be ❑Does Not
daylight controlled, set based on
business operation time-of-day, or ['Not Observable
reduce connected lighting > 30%. ENot Applicable
I
C405.3 Exit signs do not exceed 5 watts per ❑Complies
[EL6]1 face. ❑Does Not
E Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 'Medium Impact(Tier 2) 13 I Low Impact(Tier 3)
Project Title: WESTWIND POOL REMODEL Report date: 03/12/18
Data filename: Untitled.cck Page 4 of 7
1 High Impact(Tier 1) 2 Medium Impact(Tier 2) 3 Low Impact(Tier 3)
Project Title: WESTWIND POOL REMODEL Report date: 03/12/18
Data filename: Untitled.cck Page 5 of 7
Section
# Final Inspection Complies? Comments/Assumptions
& Req.ID
C303.3, :Furnished O&M instructions for ❑Complies
C408.2.5. 'systems and equipment to the ❑Does Not
2 building owner or designated
[F117]3 representative. [Not Observable
❑Not Applicable
C405.4.1 Interior installed lamp and fixture ❑Complies See the Interior Lighting fixture schedule for values.
[F118]1 lighting power is consistent with what ❑Does Not
is shown on the approved lighting
plans, demonstrating proposed watts [Not Observable
are less than or equal to allowed ❑Not Applicable
watts.
C405.5.1 Exterior lighting power is consistent ;❑C mo p ieil s See the Exterior Lighting fixture schedule for values.
[F119]1 with what is shown on the approved ❑Does Not
lighting plans, demonstrating
proposed watts are less than or equal ['Not Observable
to allowed watts. ;❑Not Applicable
C408. Furnished as-built drawings for EComplies
1 electric power systems within 90 days ❑Does Not
[F116]3 of system acceptance.
'❑Not Observable
❑Not Applicable
C408.3 Lighting systems have been tested to ❑Complies
[F133]1 ensure proper calibration, adjustment, ❑Does Not
programming, and operation.
❑Not Observable
❑Not Applicable
Additional Comments/Assumptions:
1 High Impact(Tier 1) 2 'Medium Impact(Tier 2) 13 I Low Impact(Tier 3)
Project Title: WESTWIND POOL REMODEL Report date: 03/12/18
Data filename: Untitled.cck Page 6 of 7
Project Title: WESTWIND POOL REMODEL Report date: 03/12/18