ONE-LINE DIAGRAM
AND NOTES
E1.0
ELECTRICAL NOTES
1. ALL ELECTRICAL WORK SHALL BE DONE IN ACCORDANCE WITH CURRENT
NATIONAL ELECTRICAL CODES AND ALL LOCAL AND STATE CODE, LAWS. AND
CORDINANCES. PROVIDE ALL COMPONENTS AND WIRING SIZES AS REQUIRED TO
MEET NEC STANDARDS.
2. CONTRACTOR SHALL COORDINATE WITH LOCAL POWER COMPANY FOR
REQUIREMENTS OF POWER SERVICE LINE TO THE METER BASE, WHEN
REQUIRED. POWER SERVICE REQUIREMENT IS COMMERCIAL. AC NOMINAL 120/208
VOLT OR 120/240 VOLT, SINGLE PHASE WITH 200 AMP RATING. 3. CONTRACTOR
SHALL COORDINATE WITH LOCAL TELEPHONE COMPANY FOR SERVICE LINE
REQUIREMENTS TO TERMINATE AT THE PPC CABINET. 4. CONTRACTOR SHALL
FURNISH AND INSTALL ELECTRIC METER BASE AND 200A DISCONNECT SWITCH
PER SITE PLAN DETAIL DRAWINGS AND PER LOCAL UTILITY COMPANIES
SPECIFICATION, WHEN REQUIRED. THE METER BASE SHOULD BE LOCATED IN A
MANNER WHERE ACCESSIBLE BY THE LOCAL POWER COMPANY.
5. LOCAL POWER COMPANY SHALL PROVIDE 200 AMP ELECTRIC METER.
CONTRACTOR SHALL COORDINATE INSTALLATION OF METER WITH LOCAL POWER
COMPANY.
6. UNDERGROUND POWER AND TELCO SERVICE LINES SHALL BE ROUTED IN A
COMM0N TRENCH. ALL UNDERGROUND CONDUIT SHALL BE PVC SCHEDULE 40
AND CONDUIT EXPOSED AB0VE GROUND SHALL BE GALVANIZED RIGID STEEL
TUBING UNLESS OTHERWISE INDICATED.
7. ALL TELCO CONDUIT LINES SHALL BE 4" SCH. 40 PVC CONDUIT UNLESS
OTHERWISE INDICATED. THE TELCO CONDUIT FROM THE PPC SHALL BE ROUTED
AND TERMINATED AT DESIGNATED TELCO DEMARCATION OR 2-FEET OUTSIDE
FENCED AREA, NEAR UTILITY POLE (IN FENCED AREA), OR END CAP OFF AND
PROVIDE MARKER STAKE PAINTED BRIGHT ORANGE WITH DESIGNATION FOR
TELCO SERVICE.
8. CONDUITS INSTALLED AT PCS EQUIPMENT ENDS PRIOR TO THE EQUIPMENT
INSTALLATION SHALL BE STUBBED AND CAPPED AT 6" ABOVE GRADE OR
PLATFORM. IF SERVICE LINES CAN'T BE INSTALLED INITIALLY, PROVIDE NYLON
PULL CORD IN CONDUITS.
9. THE SPRINT CABINET, INCLUDING 200 AMP LOAD PANEL AND TELCO PANEL, SHALL
BE PROVIDED BY OWNER AND INSTALLED BY THE CONTRACTOR. CONTRACTOR IS
TO INSTALL BREAKER(S) NOT PROVIDED BY MANUFACTURER. SEE PANEL
SCHEDULE ON THIS SHEET FOR BREAKER REQUIREMENTS.
10. LOCATION OF ELECTRIC METER AND DISCONNECT SWITCH TO BE PROVIDED BY
GENERAL CONTRACTOR.
11. #2 WIRE TO BE UTILIZED IN ELECTRIC SERVICE RUNS EXCEEDING 100'.
12. CONTRACTOR SHALL INSPECT THE EXISTING CONDITIONS PRIOR TO SUBMITTING
BID. ANY QUESTIONS ARISING DURING THE BID PERIOD IN REGARDS TO THE
CONTRACTORS FUNCTIONS. THE SCOPE OF WORK, OR ANY OTHER ISSUE
RELATED TO THIS PROJECT SHALL BE BROUGHT UP DURING THE BID PERIOD
WITH THE PROJECT MANAGER FOR CLARIFICATION, NOT AFTER THE CONTRACT
HAS BEEN AWARDED.
13. LOCATION OF EQUIPMENT, CONDUIT AND DEVICES SHOWN ON THE DRAWINGS
ARE APPROXIMATE AND SHALL BE COORDINATED WITH FIELD CONDITIONS PRIOR
TO ROUGH-IN.
14. THE CONDUIT RUNS AS SHOWN ON THE PLANS ARE APPROXIMATE. EXACT
LOCATION AND ROUTING SHALL BE PER EXISTING FIELD CONDITLONS.
15. PROVIDE PULL BOXES AND JUNCTION BOXES WHERE SHOWN OR REQUIRED BY
NEC.
16. ALL CONDUITS SHALL BE MET WITH BENDS MADE IN ACCORDANCE WITH NEC
TABLE 346-10. NO RIGHT ANGLE DEVICE OTHER THAN STANDARD CONDUIT
ELBOWS WITH 12" MINIMUM INSIDE SWEEPS FOR ALL CONDUITS 2" OR LARGER.
17. ALL CONDUIT TERMINATIONS SHALL BE PROVIDED WITH PLASTIC THROAT
INSULATING GROUNDING BUSHINGS.
18. ALL WIRE SHALL BE "TYPE THWN, SOLID. ANNEALED COPPER UP TO SIZE 1/10
AWG (18 AND LARGER SHALL BE CONCENTRIC STRANDED) 75 DEGREE C, (167
DEGREES F), 98° CONDUCTIVITY. MINIMUM #12.
19. ALL WIRES SHALL BE TAGGED AT ALL PULL BOXES. J-BOXES, EQUIPMENT BOXES
AND CABINETS WITH APPROVED PLASTIC TAGS, ACTION CRAFT, BRADY, OR
APPROVED EQUAL.
20. ALL NEW MATERIAL SHALL HAVE A U.L. LABEL.
21. CONDUIT ROUGH-IN SHALL BE COORDINATED WITH THE MECHANICAL EQUIPMENT
TO AVOID LOCATION TO CONFLICTS. VERIFY WITH MECHANICAL CONTRACTOR
AND COMPLY AS REQUIRED.
(E) MMBS CABINET
(E) BBU CABINET
100A
100A
100A
15A
100A
(E) (3) #2 AWG, (1) #8 GND
IN 2" CONDUIT
(E) (3) #10 AWG, (1) #10 GND
IN 2" CONDUIT
(E) 100A SPRINT PPC CABINET
(TRANSFER SWITCH / LOAD CENTER)
(E) 100A GENERATOR RECEPTACLE
TO (E) COMMERCIAL
UTILITY POWER
SOURCE
22. ALL PANEL DIRECTORIES SHALL BE TYPEWRITTEN NOT HAND WRITTEN.
23. INSTALL AN EQUIPMENT GROUNDING CONDUCTOR IN ALL CONDUITS PER THE
SPECIFICATIONS AND NEC. THE EQUIPMENT GROUNDING CONDUCTORS SHALL BE
BONDED AT ALL JUNCTlON BOXES. PULLBOXES, AND ALL DISCONNECT SWITCHES,
STARTERS, AND EQUIPMENT CABINETS.
24. THE CONTRACTOR SHALL PREPARE AS-BUILT DRAWINGS. DOCUMENT ANY AND
ALL WIRING AND EQUIPMENT CONDITIONS AND CHANGES WHILE COMPLETING
THIS CONTRACT. SUBMIT AT SUBSTANTIAL COMPLETION.
25. ALL DISCONNECT SWITCHES AND OTHER CONTROLLING DEVICES SHALL BE
PROVIDED WITH ENGRAVED PHENOLIC NAMEPLATES INDICATING EQUIPMENT
CONTROLLED, BRANCH CIRCUITS INSTALLED ON, AND PANEL FIELD LOCATIONS
FED FROM (NO EXCEPTIONS.) PROVIDE SAMPLE FOR CONSTRUCTION MANAGER'S
APPROVAL.
26. ALL ELECTRICAL DEVICES AND INSTALLATIONS OF THE DEVICES SHALL COMPLY
WITH (ADA) AMERICANS WITH DISABILITIES ACT AS ADOPTED BY THE APPLICABLE
STATE.
27. PROVIDE CORE DRILLING AS NECESSARY FOR PENETRATIONS OR RISERS
THROUGH BUILDING. DO NOT PENETRATE STRUCTURAL MEMBERS WITHOUT
CONSTRUCTION MANAGERS APPROVAL. SLEEVES ANO/OR PENETRATIONS IN
FIRE RATED CONSTRUCTION SHALL BE PACKED WITH FIRE RATED MATERIAL
WHICH SHALL MAINTAIN THE FIRE RATING OF THE WALL OR STRUCTURE. FILL FOR
FLOOR PENETRATIONS SHALL PREVENT PASSAGE OF WATER, SMOKE, FIRE AND
FUMES. ALL MATERIAL SHALL BE UL APPROVED FOR THIS PURPOSE.
28. ELECTRICAL CHARACTERISTICS OF ALL EQUIPMENT (NEW AND EXISTING) SHALL
BE FIELD VERIFIED WITH THE OWNER'S REPRESENTATIVE AND EQUIPMENT
SUPPLIER PRIOR TO ROUGH-IN Of CONDUIT AND WIRE. ALL EQUIPMENT SHALL BE
PROPERLY CONNECTED ACCORDING TO THE NAMEPLATE DATA FURNISHED ON
THE EQUIPMENT (THE DESIGN OF THESE PLANS ARE BASED UPON BEST
AVAILABLE INFORMA110N AT THE TIME OF DESIGN AND SOME EQUIPMENT
CHARACTERISTICS MAY VARY FROM DESIGN AS SHOWN ON THESE DRAWINGS).
29. LOCATION OF ALL OUTLET, BOXES, ETC., AND THE TYPE OF CONNECTION (PLUG
OR DIRECT) SHALL BE CONFIRMED WITH THE OWNER'S REPRESENTATIVE PRIOR
TO ROUGH-IN.
ELECTRICAL NOTES