HomeMy WebLinkAboutVail Marriott Final 5th & 6th Floors-West 9-10-18 .pdfFire Protection Architecture
RONDINELLI LIFE SAFETY
15272 West Warren Drive – Lakewood, Colorado, 80228
Phone 303.807.3321 – Email rondo1RLS@gmail.com
September 10, 2018
Mike Vaughan
Fire Marshall – Town of Vail
2399 North Frontage Road West
Vail, CO 81657
RE: Marriott – Vail, CO
Fire Protection System – 5th & 6th Floors - West
Mr. Vaughan:
Rondinelli Life Safety was on-site on September 10, 2018, to perform testing of the fire
protection systems for the renovations of the 5th and 6th Floors – West Building. Testing began
with Alarm Specialists at approximately 10:00am and ended at 12:30pm. Below you will find my
comments and observations from today.
1. All smoke detectors located in the corridor were activated using aerosol smoke. Each
device successfully reported an alarm condition at the FACP as well as verified that the
device address and location matched the location in the FACP.
2. The smoke detectors located in the guest rooms were activated using aerosol smoke. All
sounder bases activated successfully, and the device location was confirmed at the
FACP.
3. In rooms with gas fireplaces, a combination smoke/carbon monoxide detector is
provided. All carbon monoxide devices were activated using CO aerosol. All sounder
bases on the devices successfully activated and the device location was confirmed at the
FACP.
4. Manual pull stations located in the corridor were activated and the location of the pull
station was confirmed at the FACP. All horns and strobes successfully activated, and all
strobes were in sync with each other.
Fire Protection Architecture
RONDINELLI LIFE SAFETY
15272 West Warren Drive – Lakewood, Colorado, 80228
Phone 303.807.3321 – Email rondo1RLS@gmail.com
Based upon Rondinelli Life Safety’s testing and observations, it is our belief the fire protection
system on the 5th and 6th floors -West Building is installed and properly working as designed.
If you have any questions or concerns, please feel free to contact me at 303.807.3321.
Report Prepared By:
_____________________________________________________________________________
Steve Rondinelli, AIA, Principal
Rondinelli Life Safety
Fire Protection Consultant
C.C. Cody O’Kelly
Principal
OCG: Design. Construct. Manage PO Box 5686
Eagle, CO 81631