ISSUE LOG KEY:
# DATEISSUE LOG
ELECTRICAL SHEET INDEX
TITLE
COVER SHEETE-000 DESIGN DEVELOPMENT02.19.2018ISSUED AS PART OF A SET
' ' NOT PART OF SET
' ' ISSUED FOR INFORMATION ONLY*
√
√
√
√
√
ELECTRICAL SCHEDULESE-001
ELECTRICAL PLAN - PARKING LEVELE-201
ELECTRICAL PLAN - LEVEL 2E-203
ABBREVIATIONSPOWER SYMBOLS
SINGLE RECEPTACLE
DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
GFCI DUPLEX RECEPTACLE
DUPLEX RECEPTACLE; HALF SWITCHED
ISOLATED GROUND DUPLEX RECEPTACLE
WALL MOUNTED SPECIAL OUTLET AS NOTED
SPECIAL OUTLET AS NOTED
JUNCTION BOX
WALL MOUNTED JUNCTION BOX
FLOOR MOUNTED JUNCTION BOX
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTERC
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE
FLUSH FLOOR MOUNTED DOUBLE DUPLEX RECEPTACLE
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE; HALF SWITCHED
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE AND TELECOM
DIVISION 15 EQUIPMENT POWER CONNECTION
FUSED DISCONNECT
NON FUSED DISCONNECT
MOTOR STARTER
ENCLOSED CIRCUIT BREAKER
PULL BOX
PUSH BUTTON
TRANSFORMER
PANELBOARD OR LOADCENTER
CONTACTOR
ELECTRIC MOTOR
METER
THERMOSTAT
ATS AUTOMATIC TRANSFER SWITCH
ONE-LINE DIAGRAM SYMBOLS
CIRCUIT HOMERUN
CONDUIT RUN
CONDUIT RUN BELOW GRADE
CONDUIT UP
CONDUIT DOWN
DISCONNECT SWITCH
FUSE
CIRCUIT BREAKER
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
METER
SURGE PROTECTION DEVICE
VOLT-METER
SELECTOR SWITCH
GROUND
GF GROUND FAULT PROTECTION
AMP-METER
ST SHUNT TRIP
NORMALLY OPEN CONTACT
NORMALLY CLOSED CONTACT
COLD WATER GROUND CONNECTION
BUILDING STEEL GROUND CONNECTION
TIMER SWITCH
MULTI-OUTLET PLUG STRIP
TIME CLOCK
PHOTO-CELL
SWITCH
THERMAL OVERLOAD SWITCH
VARIABLE SPEED SWITCH
KEY SWITCH
LIGHTING FIXTURE SYMBOLS
RECESSED LIGHTING FIXTURE
WALL MOUNTED LIGHT
WALL MOUNTED UP-LIGHT
PENDANT MOUNTED LIGHT
SURFACE MOUNTED LIGHT
DIRECTIONAL/ADJUSTABLE RECESSED LIGHTING FIXTURE
MONO-POINT LIGHTING FIXTURE
RECESSED STEP LIGHT
FLUORESCENT STRIP LIGHT
WALL MOUNTED LINEAR FLUORESCENT LIGHT
RECESSED OR SURFACE MOUNTED FLUORESCENT TROFFER
FIXTURE WITH EMERGENCY BACKUP OR ON EM CIRCUIT
WALL MOUNTED EXIT SIGN W/ FACES & ARROWS AS SHOWN
EMERGENCY LIGHTS
CEILING MOUNTED EXIT SIGN W/ FACES & ARROWS AS SHOWN
SWITCH
THREE-WAY SWITCH
FOUR-WAY SWITCH
DOOR JAMB SWITCH
LIGHTING CONTROL SYMBOLS
EXTERIOR POLE MOUNTED LIGHT
EXTERIOR POST (BOLLARD) MOUNTED LIGHT
DAYLIGHT PHOTO SENSORDL
KEY SWITCH
LV
VARIABLE SPEED SWITCH
DIMMER
THREE-WAY DIMMER
LOW VOLTAGE SWITCH
WALL OCCUPANCY SENSOR/SWITCH
THERMAL OVERLOAD SWITCH
OCCUPANCY SENSOR - WALL MOUNTED
OCCUPANCY SENSOR - CORRIDOR CEILING MOUNTED
S
S3
ST
SO
D 3
D
SV
SK
SJ
S4
SK
SV
ST
S
PC
TC
TS
A
V
SPD
M
T
C
T
PB
CB
N
--
J
J
J
NOTE:
ALL SYMBOLS SHOWN ON LEGEND ARE
NOT NECESSARILY USED.
OS
OS OCCUPANCY SENSOR - CEILING MOUNTED
OS
NOTES:
· LIGHT LINEWEIGHT INDICATES EXISTING.
· HATCHED AREAS INDICATE DEMOLITION.
· 'C' ADJACENT TO A DEVICE INDICATES
MOUNTING ABOVE COUNTERTOP.
AFC
AFF
AFG
AHJ
- ABOVE FINISHED CEILING
- ABOVE FINISHED FLOOR
- ABOVE FINISHED GRADE
- AUTHORITY HAVING JURISDICTION
AL - ALUMINUM
AWG
AP - ACCESS POINT
- AMERICAN WIRE GAUGE
BFG
BMS
BAS - BUILDING AUTOMATION SYSTEM
- BELOW FINISH GRADE
- BUILDING MANAGEMENT SYSTEM
C
CATV
CCTV
- CONDUIT
- COMMUNITY (CABLE) ANTENNA TELEVISION SYSTEM
- CLOSED CIRCUIT TELEVISION
CKT - CIRCUIT
CPU - CENTRAL PROCESSING UNIT
CT - CURRENT TRANSFORMER
DISP - GARBAGE DISPOSAL
DW - DISHWASHER
(E) - EXISTING
EM - EMERGENCY
EWC - ELECTRIC WATER COOLER
FBO
GFI
FA
FACP
GRD
GC
- FIRE ALARM
- FIRE ALARM CONTROL PANEL
- FURNISHED BY OTHERS
- GENERAL CONTRACTOR
- GROUND FAULT CIRCUIT INTERRUPTER
- GROUND
IAW IN ACCORDANCE WITH-
IC
IDF
IG
IR
LAN
- INTERMEDIATE CROSS-CONNECT
- INTERMEDIATE DISTRIBUTION FRAME
- ISOLATED GROUND
- INFRARED
- LOCAL AREA NETWORK
NIC
MDF
(N)
MAIN DISTRIBUTION FRAME-
NEW-
NOT IN CONTRACT-
NL NIGHT LIGHT-
NTS NOT TO SCALE-
OC
PA
ON CENTER-
PUBLIC ADDRESS-
REF REFRIGERATOR-
TVSS
TTB TELECOMMUNICATIONS TERMINAL BOARD-
TRANSIENT VOLTAGE SURGE SUPPRESSOR-
TVTB TELEVISION TERMINAL BOARD-
UG
UNO
W
V
UNDERGROUND-
UNLESS NOTED OTHERWISE-
VOLT-
WATT-
WP
XP
WAN
WLAN
WAP
WIDE AREA NETWORK-
WIRELESS ACCESS POINT-
WIRELESS LOCAL AREA NETWORK-
WEATHERPROOF-
EXPLOSIONPROOF-
+18"
DEVICE ABOVE FINISH FLOOR (VERIFY W/ ARCH ELEVS)
MOUNTING HEIGHT TO CENTERLINE OF-
FIRE ALARM SYMBOLS
FIRE ALARM CONTROL PANEL
REMOTE ANNUNCIATOR PANEL
SMOKE DETECTOR
HEAT DETECTOR
COMBO SMOKE/HEAT DETECTOR
FIRE ALARM HORN
FIRE ALARM STROBE
FIRE ALARM COMBO HORN/STROBE
FIRE ALARM PULL STATION
S FIRE ALARM SPEAKER
S FIRE ALARM COMBO SPEAKER/STROBE
FIREMAN'S PHONE JACK
DUCT DETECTOR
SPRINKLER SYSTEM FLOW SWITCH
SPRINKLER SYSTEM TAMPER SWITCH
FIRE/SMOKE DAMPERFSD
FT
FF
F
F HH
ANN
FACP
H
SMOKE DETECTOR W/ SOUNDER BASESB
CO SMOKE DETECTOR W/ CARBON MONOXIDE
BD T
BD R
BEAM TYPE SMOKE DETECTOR TRANSMITTER
BEAM TYPE SMOKE DETECTOR RECEIVER
INDIVIDUAL ADDRESSABLE MODULE
MONITORED RELAY
POST-INDICATOR VALVE
CARBON MONOXIDE DETECTOR
PIV
MR
IAM
CO
FIRE ALARM CHIME
FIRE ALARM CHIME/STOBE
REMOTE TESTER SWITCHRTS
LOW TEMPERATURE SENSORLT
ELECTRICAL SYSTEMS LEGEND
ELECTRONIC SAFETY & SECURITY SYMBOLS
F
MULTI-OUTLET WIREWAY
VOICE/DATA SYMBOLS
COMBO PHONE/DATA OUTLET
TELEPHONE WALL OUTLET
DATA WALL OUTLET
TELEPHONE FLOOR OUTLET
DATA FLOOR OUTLET
COMBO PHONE/DATA FLOOR OUTLET
DOUBLE TELEPHONE WALL OUTLET
DATA WALL OUTLET
DOUBLE COMBO PHONE/DATA OUTLET
VOICE/DATA/FIBER OUTLETOF
POINT OF SALE (POS) OUTLETPOS
AUTOMATED TELLER MACHINE (ATM) STATIONATM
PUBLIC PAYPHONE OUTLETPP
ELEVATOR PHONE OUTLETE
POWER/TELECOM POLE
WIRELESS LAN (WI-FI) ACCESS POINT OUTLET
FAX/COPIER OUTLET
EMERGENCY SERVICES PHONE OUTLETEM
F
C
L
CEILING MOUNTED CAMERA
WALL MOUNTED CAMERA
MAGNETIC DOOR CONTACT SWITCH
ADA ACCESS CONTROL MAIN PANELADA
CRP CARD READER - PROXIMITY
S ELECTRIC LOCK - STRIKE
LM ELECTRIC LOCK - MAGNETIC
LR ELECTRIC LATCH / ROD RETRACTOR
SM MAGNETIC DOOR CONTACT SWITCH
PANIC BUTTONP
CORNER MOUNTED CAMERA
180° VIEW DOME CAMERA
360° VIEW DOME CAMERA
HEMISPHERIC DOME FISHEYE CAMERA
180°
360°
FE
INTRUSION MOTION SENSOR
SECURITY KEYPAD
MON CCTV MONITOR
ACCESS CONTROL MAIN PANELACP
EXIT PANIC/CRASH BAR SENSORREX
SECURITY CENTRAL PROCESSING UNITCPU
SECURITY/ACCESS CONTROL WORKSTATIONWS
K
I
CRS CARD READER - PROXIMITY
ELECTRICAL PLAN - LEVEL 1E-202
ELECTRICAL PLAN - LEVEL 3E-204
ELECTRICAL PLAN - LEVEL 4E-205
ELECTRICAL UNIT PLAN - 1 BRE-311
ELECTRICAL PLAN - ROOFE-206
ELECTRICAL UNIT PLAN - STUDIOE-301
ELECTRICAL UNIT PLAN - STUDIOE-302
ELECTRICAL UNIT PLAN - STUDIOE-304
ELECTRICAL UNIT PLAN - STUDIOE-303
ELECTRICAL UNIT PLAN - STUDIOE-305
ELECTRICAL UNIT PLAN - STUDIOE-306
ELECTRICAL UNIT PLAN - 1 BRE-308
ELECTRICAL UNIT PLAN - STUDIOE-307
ELECTRICAL UNIT PLAN - 1 BRE-309
ELECTRICAL UNIT PLAN - 1 BRE-310
ELECTRICAL UNIT PLAN - 1 BRE-312
ELECTRICAL UNIT PLAN - 1 BR
ELECTRICAL UNIT PLAN - 1 BR
ELECTRICAL UNIT PLAN - 1 BR
E-313
ELECTRICAL UNIT PLAN - 2 BR
E-314
E-315
E-316
ELECTRICAL DIAGRAMSE-400
ELECTRICAL DIAGRAMSE-401
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√√
√
√
GENERAL NOTES:
1. THESE DRAWINGS ACCOMPANY THE PUBLISHED CONSTRUCTION DOCUMENT SPECIFICATION BOOK (PROJECT MANUAL).
2. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON ARCHITECTURAL DRAWINGS AND IN FIELD PRIOR TO COMMENCEMENT OF WORK.
3. REVIEW ARCHITECTURAL, MECHANICAL AND OTHER DRAWINGS PRIOR TO BID.
4. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT.
5. WORK, MATERIALS, AND EQUIPMENT SHALL CONFORM TO THE LATEST EDITIONS OF LOCAL, STATE, AND NATIONAL CODES AND ORDINANCES.
6. PROVIDE PERMITS AND INSPECTIONS REQUIRED.
7. CONTRACTOR'S FAILURE TO ORDER OR RELEASE ORDER FOR MATERIALS AND/OR EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO
SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT, OR INSTALLATION METHODS.
8. VERIFY EXACT LOCATIONS OF EXISTING AND NEW UNDERGROUND UTILITIES, PIPING AND RACEWAY SYSTEMS PRIOR TO TRENCHING. PROVIDE
NECESSARY TRENCHING, BACKFILL, EXCAVATION, SUPPORTS, SERVICE FEEDERS (CONDUIT AND/OR WIRE), PULLBOXES, TRANSFORMER PADS,
SAWCUTTING AND PATCHING, CONCRETE/PAVING, ETC. REQUIRED. BACKFILL TRENCHES TO 90 PERCENT COMPACTION AND PATCH TO MATCH
EXISTING. CONTRACTOR SHALL OBTAIN AND VERIFY EXACT UTILITY COMPANY DRAWINGS AND REQUIREMENTS. ELECTRICAL CONTRACTOR IS
TO SUBMIT A COMPLETE CONSTRUCTION DRAWING SET TO THE ELECTRICAL UTILITY COMPANY WITH-IN 10 DAYS OF AWARD OF CONTRACT.
COORDINATE TIMELINE OF THEIR REVIEW, APPROVAL, CONSTRUCTION SCHEDULING AND INSTALLATION OF THE UTILITY TRANSFORMER WITH
THE UTILITY COMPANY. NOTIFY OWNER OF ANY SCHEDULING CONFLICTS.
9. VERIFY EXACT LOCATION OF EQUIPMENT TO BE FURNISHED BY OTHERS PRIOR TO ROUGH-IN.
10. INSTALL ALL MATERIALS IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ANY DEVIATIONS SHALL BE BROUGHT TO THE
ARCHITECT/ENGINEER'S ATTENTION PRIOR TO INSTALLATION.
11. FINAL CONNECTIONS TO EQUIPMENT SHALL BE IN ACCORDANCE WITH MANUFACTURER'S APPROVED WIRING DIAGRAMS, DETAILS, AND
INSTRUCTIONS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENT
ACTUALLY SUPPLIED.
12. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING EQUIPMENT WHICH IS DAMAGED DUE TO INCORRECT FIELD WIRING PROVIDED UNDER
THIS SECTION, OR FACTORY WIRING IN EQUIPMENT PROVIDED UNDER THIS SECTION.
13. ALL ELECTRICAL SYSTEMS COMPONENTS SHALL BE LISTED OR LABELED BY U.L. OR OTHER RECOGNIZED TESTING FACILITY.
14. WIRING DEVICES SHALL BE SPECIFICATION GRADE AND RATED AT 20 AMPERES FOR LIGHT SWITCHES, AND 20 AMPERES FOR DUPLEX
RECEPTACLES. THE COLOR OF THE DEVICES AND COVER PLATES SHALL BE AS DIRECTED BY ARCHITECT.
15. ALL WIRING SHALL BE INSTALLED IN LISTED METALLIC RACEWAYS, UNLESS NOTED OTHERWISE. CONNECTORS SHALL BE INSULATED THROAT
TYPE. MINIMUM RACEWAY SIZE IS 3/4”. ALL FEEDERS SHALL BE INSTALLED IN RACEWAY CONFIGURATIONS SHOWN ON ONE-LINE. BRANCH
CIRCUITS 25A AND LARGER SHALL BE INSTALLED IN INDIVIDUAL RACEWAYS. BRANCH CIRCUITS 20A AND SMALLER MAY BE GROUPED INTO
RACEWAYS AS TO NOT EXCEED 6 CURRENT-CARRYING 75-DEGREE CONDUCTORS, OR 9 CURRENT-CARRYING 90-DEGREE CONDUCTORS, IN A
SINGLE RACEWAY. METAL CLAD CABLE IS PERMITTED.
16. ALL EMPTY RACEWAY SYSTEMS SHALL HAVE A 200LB NYLON PULL STRING OR EQUAL, AND SHALL BE IDENTIFIED AT ALL JUNCTION, PULL AND
TERMINATION POINTS, USING PERMANENT METALLIC TAGS. TAG SHALL INDICATE INTENDED USE OF CONDUIT, ORIGINATION, AND TERMINATION
POINTS OF EACH INDIVIDUAL CONDUIT.
17. WIRE SHALL BE COPPER, 75 DEGREE CELSIUS RATED FOR GENERAL USE. WIRING WITHIN 3 INCHES OF FLUORESCENT BALLASTS WIRE SHALL BE
COPPER, MINIMUM 90 DEGREE CELSIUS RATED. SIZES INDICATED ARE FOR INSTALLATION IN A MAXIMUM 30 DEGREE CELSIUS AMBIENT.
CONDUCTOR AMPACITY SHALL BE DERATED FOR HIGHER AMBIENT INSTALLATIONS.
18. PANEL DIRECTORIES SHALL BE REMOVABLE. ROOM NAMES AND NUMBERS SHALL BE AS DIRECTED BY OWNER. DIRECTORIES SHALL BE TYPED
AND INSTALLED UNDER CLEAR PLASTIC COVERS.
19. FINAL CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER VIBRATING EQUIPMENT SHALL BE SEAL TITE FLEX AND APPROVED FITTINGS.
DO NOT SECURE CONDUITS, DISCONNECTS, OR DEVICES TO DUCTWORK OR MECHANICAL EQUIPMENT.
20. FIRE ALARM, SOUND, TELEPHONE, COMPUTER AND SIMILAR SYSTEMS CONDUITS LARGER THAN 1” SHALL HAVE LONG RADIUS SWEEPS (12 TIMES
THE DIAMETER).
21. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTS SHOW THAT WORK IS DEFECTIVE, CONTRACTOR SHALL MAKE CORRECTIONS
NECESSARY AT NO COST TO OWNER.
22. GUARANTEE THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP WHICH MAY OCCUR UNDER NORMAL USAGE FOR A
PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. DEFECTS SHALL BE PROMPTLY REMEDIED WITHOUT COST TO THE OWNER.
23. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS OPERATION. LIGHTS, SWITCHES, RECEPTACLES, MOTORS, ETC.
SHALL BE CONNECTED AND OPERABLE.
√
√PERMIT ISSUE√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√
√√
√
√
√
√07.24.2018TECHNOLOGY ENLARGED PLANSE-402
TECHNOLOGY RISER DIAGRAMSE-500
TECHNOLOGY RISER DIAGRAMSE-501
TECHNOLOGY DIAGRAMSE-600
√
√
√
√
ELECTRICAL SITE PLANE-100 √
TECHNOLOGY DIAGRAMSE-601 √
ELECTRICAL SCHEDULESE-002 √
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-000
ELECTRICAL
COVER SHEET
09/21/18
MECHANICAL EQUIPMENT SCHEDULE
MARK DESCRIPTION VOLT /
PHASE HP WATTS FLA MCA MOCP DISCONNECT/
FUSE SIZE FEEDER CIRCUIT SPECIFIC NOTES
B-1 BOILER 120/1 - 600 5.0 15.0 20A1P 1P MOTOR RATED
SWITCH 20A(2WG) M1-1 M1-3 M1-5
WH-1 DOMESTIC HOT WATER 120/1 - 480 4.0 5.0 20A1P 1P MOTOR RATED
SWITCH 20A(2WG) M1-7 M1-9
P-1 HEATING WATER CIRC PUMP 208/1 - 1,380 6.6 8.3 20A2P 30A, 2P, NF 20A(3WG) SEE PLANS
P-2 BOILER INJECTION PUMP 208/3 - 1,350 3.8 4.7 20A3P 30A, 3P, NF 20A(4WG) SEE PLANS
P-3 WATER HEATER INJECTION PUMP 120/1 - 400 3.3 4.2 20AP 1P MOTOR RATED
SWITCH 20A(2WG) M1-37 M1-39
P-4 DOMESTIC HOT WATER RECIRC
PUMP 120/1 - 280 2.3 2.9 20A1P 1P MOTOR RATED
SWITCH 20A(2WG)M1-2
P-5 SNOW MELT CIRC PUMP 208/3 - 600 1.7 2.1 20A3P 30A, 3P, NF 20A(4WG) M1-4,6,8
P-6 ELEVATOR SUMP PUMP 120/1 1/2 1,176 9.8 12.3 20A1P 1P MOTOR RATED
SWITCH 20A(2WG) M1-10
GF-1 GLYCOL FEEDER 120/1 - 84 0.7 0.9 20A1P 1P MOTOR RATED
SWITCH 20A(2WG) M1-12
MAU-1 CORRIDOR MAKE-UP AIR UNIT 208/1 3/4 2,392 7.6 11.5 20A2P 30A, 2P, FUSED 20A(3WG) M1-30,32
MAU-2 LAUNDRY MAKE-UP AIR UNIT 208/3 2 3,922 7.5 10.9 20A3P 30A, 3P, FUSED 20A(4WG) M1-34,36,38
EF-1 CEILING EXHAUST FAN #1 120/1 - 17 0.1 0.2 20A1P 1P MOTOR RATED
SWITCH 20A(2WG) SEE PLANS
EF-2 CEILING EXHAUST FAN #2 120/1 - 27 0.2 0.3 20A1P 1P MOTOR RATED
SWITCH 20A(2WG) SEE PLANS
EF-3 WALL EXHAUST FAN #3 120/1 1/4 696 5.8 7.3 20A1P 1P MOTOR RATED
SWITCH 20A(2WG) M1-40
EF-4 WALL EXHAUST FAN #4 120/1 1/20 96 0.8 1.0 20A1P 1P MOTOR RATED
SWITCH 20A(2WG) M1-40
EF-5 CEILING EXHAUST FAN #5 120/1 - 126 1.1 1.3 20A1P 1P MOTOR RATED
SWITCH 20A(2WG) SEE PLANS
EF-6 DRYER EXHAUST FAN #6 120/1 - 72 0.6 0.8 20A1P 1P MOTOR RATED
SWITCH 20A(2WG) M1-28
UH-1 UNIT HEATER #1 120/1 - 16 0.1 0.2 20A1P 1P MOTOR RATED
SWITCH 20A(2WG) SEE PLANS
CUH-1 RECESSED CABINET UNIT HEATER #1 120/1 1/10 192 1.6 2.0 20A1P 1P MOTOR RATED
SWITCH 20A(2WG) M1-26
CUH-3 CEILING CABINET UNIT HEATER #3 120/1 1/15 132 1.1 1.4 20A1P 1P MOTOR RATED
SWITCH 20A(2WG) M1-22
CUH-4 CEILING CABINET UNIT HEATER #4 120/1 1/10 192 1.6 2.0 20A1P 1P MOTOR RATED
SWITCH 20A(2WG) M1-24
GENERAL NOTES:
A. SEE SPECIFICATIONS FOR ELECTRICAL DIVISION AND MECHANICAL DIVISION MOTOR STARTER COORDINATION.
B. PROVIDE PHASE PROTECTION FOR ALL THREE PHASE MOTORS ABOVE 7-1/2 HP.
C. PROVIDE ALL EXTERIOR DISCONNECTS WITH NEMA 3R RATING.
D. WHEN EQUIPMENT IS LISTED WITH ONLY A HORSEPOWER RATING THE DISCONNECT AND FEEDER ARE SIZED PER THE N.E.C.
SPECIFIC NOTES:
(1)
(2)
(3)
(4)
LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING RECESS
DEPTH
LAMPS INPUT WATTS VOLT MANUFACTURER CATALOG NUMBER SPECIFIC
NOTESQTY TYPE LUMENS
G1 GARAGE PENDANT WITH INTEGRAL MOTION SENSOR,
TYPE 5 DISTRIBUTION, 3000K PENDANT - -LED AS SUPPLIED,
3000K 4,575 37 120-277 LITHONIA DSXPG LED 20C 530 30K T5M MVOLT
PIR
S1 SURFACE MOUNTED ROUND FIXTURE, 90 CRI, 3000K SURFACE - -LED AS SUPPLIED,
3000K 1,800 20 120-277 JUNO JSF 13IN 18LM 30K 90CRI MVOLT ZT WH
S2 2' SURFACE MOUNTED LINEAR FIXTURE, 90 CRI, 3000K WALL - -LED AS SUPPLIED,
3000K 1,490 19.5 120-277 WAC LIGHTING WS-63724-30 AL
S3 3' SURFACE MOUNTED LINEAR FIXTURE, 90 CRI, 3000K WALL - -LED AS SUPPLIED,
3000K 2,330 28.5 120-277 WAC LIGHTING WS-63736-30 AL
S4 4' LED STRIP LIGHT, 80 CRI, 3500K SURFACE - -LED AS SUPPLIED,
3500K 4,146 38 120-277 LITHONIA CDS L48 MVOLT DM 35K 80CRI WH
S5 ELEVATOR PIT LIGHT SURFACE - -LED AS SUPPLIED,
4000K 6,000 45 120 LITHONIA FEM L48 6000LM LPAFL MD 120 GZ10
40K 80CRI WLFEND
X1 EXIT SIGN SURFACE - - LED AS SUPPLIED - 0.8 120-277 LITHONIA EXR LED M6
GENERAL NOTES:
A. THE LUMINAIRE SCHEDULE CAN NOT BE USED INDEPENDENTLY OF THE DRAWINGS AND SPECIFICATIONS TO OBTAIN LUMINAIRE COSTS. THE INDIVIDUAL ESTABLISHING LUMINAIRE COSTS SHALL NOT QUOTE PRICING WITHOUT
FIRST SEEING APPLICABLE ELECTRICAL DRAWINGS AND ELECTRICAL DIVISION SPECIFICATIONS. THE CONTRACTOR IS REPONSIBLE FOR PROVIDING NECESSARY DRAWINGS AND SPECIFICATIONS TO THE INDIVIDUAL QUOTING
LUMINAIRE PRICING.
B. REFER TO DRAWINGS FOR FIXTURES REQUIRING EMERGENCY BATTERY BACKUP OPTION (SHOWN BY HATCH IN/OVER SYMBOL). MINIMUM LIGHT OUTPUT FOR EM BALLAST SHALL BE 600 LUMENS.
C. ALL FLUORESCENT LAMPS ARE TO BE 3500° KELVIN COLOR TEMPERATURE
SPECIFIC NOTES:
(1)
(2)
(3)
(4)
SITE LUMINAIRE SCHEDULE
TYPE DESCRIPTION MOUNTING LAMPS INPUT WATTS VOLT MANUFACTURER CATALOG NUMBER SPECIFIC
NOTESQTY TYPE LUMENS
E1 EXTERIOR WALL SCONCE WALL -LED AS SUPPLIED,
3000K 3,276 25 120-277 LITHONIA WST LED P2 30K VW MVOLT PIR
E2 EXTERIOR PATH LIGHT SURFACE -LED AS SUPPLIED,
3000K 435 12 120 STRUCTURA MAC-42-L30-SO-S*-C*-120-STD
R1 EXTERIOR RECESSED CAN ABOVE DOORS RECESSED -LED AS SUPPLIED,
3000K 1,020 14 120-277 LITHONIA WF6 LED 30K MVOLT
GENERAL NOTES:
A. THE LUMINAIRE SCHEDULE CAN NOT BE USED INDEPENDENTLY OF THE DRAWINGS AND SPECIFICATIONS TO OBTAIN LUMINAIRE COSTS. THE INDIVIDUAL ESTABLISHING LUMINAIRE COSTS SHALL NOT QUOTE
PRICING WITHOUT FIRST SEEING APPLICABLE ELECTRICAL DRAWINGS AND ELECTRICAL DIVSION SPECIFICATIONS. THE CONTRACTOR IS REPONSIBLE FOR PROVIDING NECESSARY DRAWINGS AND
SPECIFICATIONS TO THE INDIVIDUAL QUOTING LUMINAIRE PRICING.
B. REFER TO DRAWINGS FOR FIXTURES REQUIRING EMERGENCY BATTERY BACKUP OPTION (SHOWN BY HATCH IN/OVER SYMBOL). MINIMUM LIGHT OUTPUT FOR EM BALLAST SHALL BE 600 LUMENS.
SPECIFIC NOTES:
(1)
(2)
(3)
(4)
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-001
ELECTRICAL
SCHEDULES
09/21/18
DISTRIBUTION PANEL:VOLTAGE:
120/208V, 3PH, 4W
SWB MINIMUM BUS:
2000
LOCATION: MAIN:
ELEC ROOM 2000/3 CB
MOUNTING: MINIMUM AIC:
SURFACE 65,000
PANELS/RISERS MOTORS/EQUIPMENT PANEL
SUBTOTAL DEMAND PANEL TOTALMARK: M1 P1 L1 P3 DP1 DP3 ELEV-1
OCPD: 200/3 CB 250/3 CB 70/3 CB 250/3 CB 600/3 CB 600/3 CB 110/3 CB
RESIDENTIAL 0 0 0 0 175,482 180,924 356406 100% 356406
LIGHTING 0 144 4,259 0 0 0 0 4403 125% 5504
RECEPTACLES 0 10,800 0 3,070 0 0 0 13870 NEC 220 11935
LARGEST MOTOR 3,921 0 0 0 0 0 16,625 16625 25% 4156
MOTORS 17,799 0 0 0 0 0 0 34424 100% 34424
EQUIPMENT 3,468 6,000 0 13,654 0 0 0 23122 100% 23122
APPLIANCES 0 15,000 0 15,000 0 0 0 30000 >6 19500
PANEL TOTAL (KVA): 455.0
PANEL TOTAL (A): 1264
PANEL: M1 VOLTAGE: 120/208V, 3PH, 4W
MINIMUM BUS: 150
LOCATION: ELEC ROOM MAIN: MLO
MOUNTING: SURFACE MINIMUM AIC: 42,000
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B C POLE TRIP A B C TRIP POLE A B C
1 600 E B-1 1 20 + 20 1 M P-4 280 2
3 600 E B-1 1 20 + 20 3 M P-5 200 4
5 600 E B-1 1 20 + - - M - 200 6
7 480 E WH-1 1 20 + - - M - 200 8
9 480 E WH-1 1 20 + 20 1 M P-6 1176 10
11 690 M P-1 2 20 + 20 1 M GF-1 84 12
13 690 M - - - + 20 1 E UH-1 (x8) 128 14
15 690 M P-1 2 20 + 20 1 E UH-1 (x4) 64 16
17 690 M - - - + 20 1 M EF-2 - TRASH 27 18
19 450 M P-2 2 20 + 20 1 M EF-5/EF-1/EF-2 - MECH 197 20
21 450 M - - - + 20 1 E CUH-3 132 22
23 450 M - - - + 20 1 E CUH-4 192 24
25 450 M P-2 2 20 + 20 1 E CUH-1 192 26
27 450 M - - - + 20 1 M EF-6 (x10) 720 28
29 450 M - - - + 20 2 M MAU-1 1196 30
31 450 M P-2 2 20 + - - M - 1196 32
33 450 M - - - + 20 3 LM MAU-2 1307 34
35 450 M - - - + - - LM - 1307 36
37 400 M P-3 1 20 + - - LM - 1307 38
39 400 M P-3 1 20 + 20 1 M EF-3/EF-4 792 40
41 SPARE 1 20 + 20 1 SPARE 42
43 SPARE 1 20 + 20 1 SPARE 44
45 SPARE 1 20 + 20 1 SPARE 46
47 SPARE 1 20 + 20 1 SPARE 48
49 SPACE + SPACE 50
51 SPACE + SPACE 52
53 SPACE + SPACE 54
55 SPACE + SPACE 56
57 SPACE + SPACE 58
59 SPACE + SPACE 60
LOAD TYPE PANEL TOTAL FEED THRU
TOTAL
SUBFEED
TOTAL
FEEDER
SUBTOTAL DEMAND FEEDER TOTAL GENERAL NOTES:
A.
(L) LIGHTING 0 0 125% 0 B.
(R) RECEPTACLES 0 0 NEC 220 0 C.
(LM) LARGEST MOTOR 3921 3921 25% 980 D.
(M) MOTORS (ALL) 17799 17799 100% 17799 E.
(E) EQUIPMENT 3468 3468 100% 3468 SPECIFIC NOTES:
(A) APPLIANCES 0 0 0 0 (1)
PANEL TOTAL (KVA): 22.2
(2)
(3)
PANEL TOTAL (A): 62 (4)
(5)
PANEL: P1 VOLTAGE: 120/208V, 3PH, 4W
MINIMUM BUS: 150
LOCATION: ELEC ROOM MAIN: MLO
MOUNTING: SURFACE MINIMUM AIC: 42,000
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B C POLE TRIP A B C TRIP POLE A B C
1 1080 R PARKING LEVEL 1 20 + 20 1 R LEVEL 1 CORRIDOR 720 2
3 1620 R PARKING LEVEL 1 20 + 20 1 R LEVEL 1 LOBBY 720 4
5 900 R MECH ROOM 1 20 + 20 1 R LEVEL 1 ELEC ROOM 360 6
7 900 R ELEC ROOM 1 20 + 20 1 R LEVEL 1 OFFICE 900 8
9 180 R EAST STAIR 1 20 + 20 1 R LEVEL 2 CORRIDOR 720 10
11 180 R WEST STAIR 1 20 + 20 1 R LEVEL 2 ELEC ROOM 360 12
13 1260 R EXTERIOR 1 20 + 20 1 A LEVEL 2 - DRYER (1) 1500 14
15 360 R ELEVATOR REC 1 20 + 20 1 A LEVEL 2 - DRYER (1) 1500 16
17 1500 A LEVEL 1 - DRYER (1) 1 20 + 20 1 A LEVEL 2 - DRYER (1) 1500 18
19 1500 A LEVEL 1 - DRYER (1) 1 20 + 20 1 A LEVEL 2 - WASHER (1) 1500 20
21 1500 A LEVEL 1 - DRYER (1) 1 20 + 20 1 A LEVEL 2 - WASHER (1) 1500 22
23 1500 A LEVEL 1 - WASHER (1) 1 20 + 20 1 E LEVEL 2 - VENDING 1500 24
25 1500 A LEVEL 1 -WASHER (1) 1 20 + 20 1 E LEVEL 2 - VENDING 1500 26
27 1500 E LEVEL 1 - VENDING 1 20 + 20 1 R LEVEL 2 - LAUNDRY 180 28
29 1500 E LEVEL 1 - VENDING 1 20 + 20 1 L SITE LIGHTING 144 30
31 180 R LEVEL 1 - LAUNDRY 1 20 + 20 1 R GENERATOR REC 180 32
33 SPARE 1 20 + 20 1 SPARE 34
35 SPARE 1 20 + 20 1 SPARE 36
37 SPARE 1 20 + 20 1 SPARE 38
39 SPARE 1 20 + 20 1 SPARE 40
41 SPARE 1 20 + 20 1 SPARE 42
LOAD TYPE PANEL TOTAL FEED THRU
TOTAL
SUBFEED
TOTAL
FEEDER
SUBTOTAL DEMAND FEEDER TOTAL GENERAL NOTES:
A.
(L) LIGHTING 144 144 125% 180 B.
(R) RECEPTACLES 10800 10800 NEC 220 10400 C.
(LM) LARGEST MOTOR 0 0 25% 0 D.
(M) MOTORS (ALL) 0 0 100% 0 E.
(E) EQUIPMENT 6000 6000 100% 6000 SPECIFIC NOTES:
(A) APPLIANCES 15000 15000 >6 9750 (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
PANEL TOTAL (KVA): 26.3 (2)
(3)
PANEL TOTAL (A): 73 (4)
(5)
PANEL: L1 VOLTAGE: 120/208V, 3PH, 4W
MINIMUM BUS: 100
LOCATION: ELEC ROOM MAIN: 70/3 CB
MOUNTING: SURFACE MINIMUM AIC: 22,000
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B C POLE TRIP A B C TRIP POLE A B C
1 654 L PARKING GARAGE 1 20 + 20 1 L ELEVATOR 90 2
3 798 L PARKING LEVEL 1 20 + 20 1 L LEVEL 1 558 4
5 486 L EXTERIOR 1 20 + 20 1 L LEVEL 2 358 6
7 285 L WEST STAIR 1 20 + 20 1 L LEVEL 3 358 8
9 314 L EAST STAIR 1 20 + 20 1 L LEVEL 4 358 10
11 SPARE 1 20 + 20 1 SPARE 12
13 SPARE 1 20 + 20 1 SPARE 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
LOAD TYPE PANEL TOTAL FEED THRU
TOTAL
SUBFEED
TOTAL
FEEDER
SUBTOTAL DEMAND FEEDER TOTAL GENERAL NOTES:
A.
(L) LIGHTING 4259 4259 125% 5324 B.
(R) RECEPTACLES 0 0 NEC 220 0 C.
(LM) LARGEST MOTOR 0 0 25% 0 D.
(M) MOTORS (ALL) 0 0 100% 0 E.
(E) EQUIPMENT 0 0 100% 0 SPECIFIC NOTES:
(A) APPLIANCES 0 0 0 0 (1)
PANEL TOTAL (KVA): 5.3 (2)
(3)
PANEL TOTAL (A): 15 (4)
(5)
PANEL: P3 VOLTAGE: 120/208V, 3PH, 4W
MINIMUM BUS: 250
LOCATION: LVL 3 ELEC CLOSET MAIN: 250/3 CB
MOUNTING: SURFACE MINIMUM AIC: 22,000
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B C POLE TRIP A B C TRIP POLE A B C
1 720 R LEVEL 3 CORRIDOR 1 20 + 20 1 R LEVEL 4 CORRIDOR 720 2
3 360 R LEVEL 3 ELEC ROOM 1 20 + 20 1 R LEVEL 4 ELEC ROOM 360 4
5 938 E ROOF HEAT TRACE (1) 2 30 + 30 2 E ROOF HEAT TRACE (1) 938 6
7 938 E - - - + - - E - 938 8
9 1028 E ROOF HEAT TRACE (1) 2 30 + 30 2 E ROOF HEAT TRACE (1) 923 10
11 1028 E - - - + - - E - 923 12
13 1500 A LEVEL 3 - DRYER (2) 1 20 + 20 1 A LEVEL 4 - DRYER (2) 1500 14
15 1500 A LEVEL 3 - DRYER (2) 1 20 + 20 1 A LEVEL 4 - DRYER (2) 1500 16
17 1500 A LEVEL 3 - DRYER (2) 1 20 + 20 1 A LEVEL 4 - DRYER (2) 1500 18
19 1500 A LEVEL 3 - WASHER (2) 1 20 + 20 1 A LEVEL 4 - WASHER (2) 1500 20
21 1500 A LEVEL 3 - WASHER (2) 1 20 + 20 1 A LEVEL 4 - WASHER (2) 1500 22
23 1500 E LEVEL 3 - VENDING 1 20 + 20 1 E LEVEL 4 - VENDING 1500 24
25 1500 E LEVEL 3 - VENDING 1 20 + 20 1 E LEVEL 4 - VENDING 1500 26
27 180 R LEVEL 3 - LAUNDRY 1 20 + 20 1 R LEVEL 4 - LAUNDRY 180 28
29 550 R ATTIC REC/LTG 1 20 + 30 2 SPARE (1) 30
31 SPARE (1) 2 30 + - - - 32
33 - - - + 30 2 SPARE (1) 34
35 SPARE (1) 2 30 + - - - 36
37 - - - + 20 1 SPARE 38
39 SPARE 1 20 + 20 1 SPARE 40
41 SPARE 1 20 + 20 1 SPARE 42
LOAD TYPE PANEL TOTAL FEED THRU
TOTAL
SUBFEED
TOTAL
FEEDER
SUBTOTAL DEMAND FEEDER TOTAL GENERAL NOTES:
A.
(L) LIGHTING 0 0 125% 0 B.
(R) RECEPTACLES 3070 3070 NEC 220 3070 C.
(LM) LARGEST MOTOR 0 0 25% 0 D.
(M) MOTORS (ALL) 0 0 100% 0 E.
(E) EQUIPMENT 13654 13654 100% 13654 SPECIFIC NOTES:
(A) APPLIANCES 15000 15000 >6 9750 (1) PROVIDE 30-mA GFEP CIRCUIT BREAKER.
PANEL TOTAL (KVA): 26.5 (2) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
(3)
PANEL TOTAL (A): 74 (4)
(5)
LOAD SUMMARY - DP1 (600 AMPS - 208 VOLTS)
VOLTAGE: 208 NUMBER OF PANEL LOAD UNIT TOTAL LOAD
PHASE: 3 UNITS (VA) (VA)
UNIT
STUDIO 17 17,599.0 299,183
STUDIO + 2 17,659.0 35,318
1BR 10 17,798.0 177,980
2BR 2 17,950.0 35,900
TOTAL NUMBER OF UNITS 31
CALCULATED RESIDENTIAL LOAD 548,381 VA
DEMAND FACTOR (PER TABLE 220.84) 0.32
DEMANDED RESIDENTIAL LOAD 175,482 VA
487.1 AMPS
Note:
LOAD SUMMARY - DP3 (600 AMPS - 208 VOLTS)
VOLTAGE: 208 NUMBER OF PANEL LOAD UNIT TOTAL LOAD
PHASE: 3 UNITS (VA) (VA)
UNIT
STUDIO 18 17,599.0 316,782
STUDIO + 2 17,659.0 35,318
1BR 12 17,798.0 213,576
2BR 2 17,950.0 35,900
TOTAL NUMBER OF UNITS 34
CALCULATED RESIDENTIAL LOAD 601,576 VA
DEMAND FACTOR (PER TABLE 220.84) 0.30
DEMANDED RESIDENTIAL LOAD 180,473 VA
500.9 AMPS
Note:
PANEL: DP3 VOLTAGE: 120/208V, 3PH, 4W
MINIMUM BUS: 600
LOCATION: LVL 3 ELEC CLOSET MAIN: 600/3 CB
MOUNTING: SURFACE MINIMUM AIC: 42,000
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B C POLE TRIP A B C TRIP POLE A B C
1 UNIT 301 STUDIO 2 100 + 100 2 UNIT 401 STUDIO 2
3 - - - + - - - 4
5 UNIT 302 ONE BR 2 100 + 100 2 UNIT 402 ONE BR 6
7 - - - + - - - 8
9 UNIT 303 ONE BR 2 100 + 100 2 UNIT 403 ONE BR 10
11 - - - + - - - 12
13 UNIT 304 TWO BR 2 100 + 100 2 UNIT 404 TWO BR 14
15 - - - + - - - 16
17 UNIT 305 STUDIO 2 100 + 100 2 UNIT 405 STUDIO 18
19 - - - + - - - 20
21 UNIT 306 STUDIO 2 100 + 100 2 UNIT 406 STUDIO 22
23 - - - + - - - 24
25 UNIT 307 STUDIO 2 100 + 100 2 UNIT 407 STUDIO 26
27 - - - + - - - 28
29 UNIT 308 STUDIO 2 100 + 100 2 UNIT 408 STUDIO 30
31 - - - + - - - 32
33 UNIT 309 STUDIO + 2 100 + 100 2 UNIT 409 STUDIO + 34
35 - - - + - - - 36
37 UNIT 310 ONE BR 2 100 + 100 2 UNIT 410 ONE BR 38
39 - - - + - - - 40
41 UNIT 311 ONE BR 2 100 + 100 2 UNIT 411 ONE BR 42
43 - - - + - - - 44
45 UNIT 312 STUDIO 2 100 + 100 2 UNIT 412 STUDIO 46
47 - - - + - - - 48
49 UNIT 313 STUDIO 2 100 + 100 2 UNIT 413 STUDIO 50
51 - - - + - - - 52
53 UNIT 314 STUDIO 2 100 + 100 2 UNIT 414 STUDIO 54
55 - - - + - - - 56
57 UNIT 315 STUDIO 2 100 + 100 2 UNIT 415 STUDIO 58
59 - - - + - - - 60
61 UNIT 316 ONE BR 2 100 + 100 2 UNIT 416 ONE BR 62
63 - - - + - - - 64
65 UNIT 317 ONE BR 2 100 + 100 2 UNIT 417 ONE BR 66
67 - - - + - - - 68
69 SPARE 2 100 + 100 2 SPARE 70
71 - - - + - - - 72
73 SPARE 2 100 + 100 2 SPARE 74
75 - - - + - - - 76
77 SPARE 2 100 + 100 2 SPARE 78
79 - - - + - - - 80
81 SPARE 2 100 + 100 2 SPARE 82
83 - - - + - - - 84
LOAD TYPE PANEL TOTAL FEED THRU
TOTAL
SUBFEED
TOTAL
FEEDER
SUBTOTAL DEMAND FEEDER TOTAL GENERAL NOTES:
A.
(L) LIGHTING 0 0 125% 0 B.
(R) RECEPTACLES 0 0 NEC 220 0 C.
(LM) LARGEST MOTOR 0 0 25% 0 D.
(M) MOTORS (ALL) 0 0 100% 0 E.
(E) EQUIPMENT 0 0 100% 0 SPECIFIC NOTES:
(A) APPLIANCES 0 0 0 0 (1)
PANEL TOTAL (KVA): 180.5 (2)
REFER TO 'LOAD SUMMARY - DP3' ON THIS SHEET
FOR MORE INFORMATION.
(3)
PANEL TOTAL (A): 501 (4)
(5)
PANEL: DP1 VOLTAGE: 120/208V, 3PH, 4W
MINIMUM BUS: 600
LOCATION: ELEC ROOM MAIN: MLO
MOUNTING: SURFACE MINIMUM AIC: 65,000
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B C POLE TRIP A B C TRIP POLE A B C
1 UNIT 101 STUDIO 2 100 + 100 2 UNIT 201 STUDIO 2
3 - - - + - - - 4
5 UNIT 102 ONE BR 2 100 + 100 2 UNIT 202 ONE BR 6
7 - - - + - - - 8
9 UNIT 103 ONE BR 2 100 + 100 2 UNIT 203 ONE BR 10
11 - - - + - - - 12
13 UNIT 104 TWO BR 2 100 + 100 2 UNIT 204 TWO BR 14
15 - - - + - - - 16
17 UNIT 105 STUDIO 2 100 + 100 2 UNIT 205 STUDIO 18
19 - - - + - - - 20
21 UNIT 106 STUDIO 2 100 + 100 2 UNIT 206 STUDIO 22
23 - - - + - - - 24
25 UNIT 107 STUDIO 2 100 + 100 2 UNIT 207 STUDIO 26
27 - - - + - - - 28
29 UNIT 108 ADA STUDIO + 2 100 + 100 2 UNIT 208 STUDIO 30
31 - - - + - - - 32
33 UNIT 109 ONE BR 2 100 + 100 2 UNIT 209 STUDIO + 34
35 - - - + - - - 36
37 UNIT 110 STUDIO 2 100 + 100 2 UNIT 210 ADA ONE BR 38
39 - - - + - - - 40
41 UNIT 111 STUDIO 2 100 + 100 2 UNIT 211 ONE BR 42
43 - - - + - - - 44
45 UNIT 112 STUDIO 2 100 + 100 2 UNIT 212 STUDIO 46
47 - - - + - - - 48
49 UNIT 113 STUDIO 2 100 + 100 2 UNIT 213 STUDIO 50
51 - - - + - - - 52
53 UNIT 114 ONE BR 2 100 + 100 2 UNIT 214 STUDIO 54
55 - - - + - - - 56
57 SPARE 2 100 + 100 2 UNIT 215 STUDIO 58
59 - - - + - - - 60
61 SPARE 2 100 + 100 2 UNIT 216 ONE BR 62
63 - - - + - - - 64
65 SPARE 2 100 + 100 2 UNIT 217 ONE BR 66
67 - - - + - - - 68
69 SPARE 2 100 + 100 2 SPARE 70
71 - - - + - - - 72
73 SPARE 2 100 + 100 2 SPARE 74
75 - - - + - - - 76
77 SPARE 2 100 + 100 2 SPARE 78
79 - - - + - - - 80
81 SPARE 2 100 + 100 2 SPARE 82
83 - - - + - - - 84
LOAD TYPE PANEL TOTAL FEED THRU
TOTAL
SUBFEED
TOTAL
FEEDER
SUBTOTAL DEMAND FEEDER TOTAL GENERAL NOTES:
A.
(L) LIGHTING 0 0 125% 0 B.
(R) RECEPTACLES 0 0 NEC 220 0 C.
(LM) LARGEST MOTOR 0 0 25% 0 D.
(M) MOTORS (ALL) 0 0 100% 0 E.
(E) EQUIPMENT 0 0 100% 0 SPECIFIC NOTES:
(A) APPLIANCES 0 0 0 0 (1)
PANEL TOTAL (KVA): 175.5 (2)
REFER TO 'LOAD SUMMARY - DP1' ON THIS SHEET
FOR MORE INFORMATION.
(3)
PANEL TOTAL (A): 487 (4)
(5)
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-002
ELECTRICAL
SCHEDULES
09/21/18
UP(22R)
FIRE EXCAB
FIRE EXCAB
5
UP
UP
UP
DN
T
1. UTILITY TRANSFORMER.
2. REFER TO ELECTRICAL ONE-LINE DIAGRAM ON
SHEET E-400 FOR FEEDER SIZE.
3. ELECTRICAL SERVICE ENTRANCE EQUIPMENT
LOCATED IN THIS ROOM.
4. BOLLARDS SHALL BE CONTROLLED VIA EXTERIOR
LIGHTING CONTROL PANEL WITH ASTRONOMIC TIME
CLOCK AND PHOTOCELL.
5. GENERATOR LOCATED UNDER THIS PORTION OF
THE BUILDING. PROVIDE WEATHERPROOF DUPLEX
RECEPTACLE AT GENERATOR. CIRCUIT
RECEPTACLE TO P1-32.
SCALE: 1 ELECTRICAL SITE PLAN
1/16" = 1'-0"
4
E2
P1-30
4
E2P1-30
4
E2
P1-30
20A(2WG)
(3)4"C.
VOICE/DATA PEDESTAL
CATV PEDESTAL
1
4 E2
4E2
4E2
4 E2 4E2
4E2
4E2
4E2
FLAG NOTES:X
5
4 E2
3
2
20A(2WG)
P1-30
P1-30
P1-30
P1-30
P1-30 P1-30
P1-30
P1-30
P1-30
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL SITE
PLAN
E-100
09/21/18
UP
(22R)
FIRE EXCAB
FIRE EXCAB
UP
UP
18/2
18/2
29
1
K
J
F
E
D
B
A
9 10 2 4 6 12 15
16
17
18
19
20
21
22
YF Y
YH
YL
YJ
YM
16
17
18
19
20
21
22
YK
YE
YD
7
5 1
2
L
M
3 7
6
9 10
G
H
SCALE:
ELECTRICAL PLAN - PARKING LEVELS
1/8" = 1'-0"
+48"
+48"
+48"
+48"
+48"
WP
WP
WP
G1 G1
G1 G1
G1 G1
G1 G1
G1 G1
G1 G1
E1 E1
OS J P1-2
J
S4S S4 S4
S4S4
S4S4
S4
S4
S4
S4
S4
S4
S4
S4
S4
S4
S4
S4
S4
S4
S4
S4
S4
S4
S4 S4
S4 S4
S+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"
+48"SS
OS
OS
OS
S
S
OS
OS
WP
'SWB'
S3
S3
S3 S3
S3
E1
E1
E1
E1
E1
E1
G1
G1
G1
G1
G1
G1
P1-1
P1-1
P1-1
P1-1
P1-3
P1-3
P1-3
P1-3
P1-3
P1-3
P1-3
P1-3
P1-3
P1-5
P1-5
P1-5
P1-5
SOP1-5
P1-7
P1-7
P1-7
P1-7
P1-9
P1-11
P1-13
P1-13
P1-13
P1-13
OS
OS
SK
S K
OS
SK
S1
S5 P1-15
L1-1
L1-1
L1-1 L1-1
L1-1
L1-3
L1-3
L1-3
L1-3
L1-5
L1-5
L1-5
L1-5
L1-2
L1-7
L1-9
'M1'
'P1'
'L1'
'ATS-E'
'ATS-S'
1. ALL LIGHTING ON THIS SHEET IS ON EMERGENCY
GENERATOR UNLESS NOTED OTHERWISE.
2. ALL EXIT SIGNS SHALL BE CIRCUITED TO LOCAL
LIGHTING CIRCUIT.
NOTES:
1. RECEPTACLE MOUNTED IN ELEVATOR PIT.
2. LIGHT MOUNTED IN ELEVATOR PIT.
3. PROVIDE 20A, 120V ELECTRICAL FEED TO JUNCTION
BOX FOR MOTORIZED GARAGE DOOR. GARAGE
DOOR SHALL BE CONTROLLED VIA KEYPAD FOR
ENTRY AND MOTION DETECTOR FOR EXIT.
COORDINATE EXACT POWER REQUIREMENTS AND
CONTROLS WITH GARAGE DOOR REVIEWED
SUBMITTAL PRIOR TO ROUGH-IN. COORDINATE
EXACT LOCATION OF CONTROLS WITH GENERAL
CONTRACTOR AND ARCHITECT PRIOR TO ROUGH-IN.
4. PROVIDE 1" CONDUIT WITH PULL STRING FROM THIS
LOCATION TO 'ELEC ROOM' ON THIS LEVEL FOR
ELECTRIC UTILITY METER REPEATER. ELECTRICAL
CONTRACTOR SHALL PROVIDE SELF-ADHESIVE
PRINTED LABEL INDICATING CONDUIT IS TO BE USED
BY ELECTRIC UTILITY ONLY.
5. PUSH BUTTON TO CONTROL SHUNT TRIP
DISCONNECT IN 'ELEC ROOM'. PROVIDE PROTECTIVE
COVER TO PREVENT ACCIDENTAL PRESSING. PUSH
BUTTON SHALL BE CLEARLY LABELED AS THE MAIN
DISCONNECT.
6. ALL EXTERIOR LIGHTS SHALL BE CONTROLLED VIA
EXTERIOR LIGHTING CONTROL PANEL WITH
ASTRONOMIC TIME CLOCK AND PHOTOCELL.
7. SURFACE MOUNT CCTV CAMERA - IP MEGAPIXEL
DOME.
8. PROVIDE EMERGENCY SHUT-OFF PUSH BUTTON FOR
GENERATOR IN THIS LOCATION. PROVIDE
PROTECTIVE COVER TO PREVENT ACCIDENTAL
PRESSING. PUSH BUTTON SHALL BE CLEARLY
LABELED AS THE DISCONNECT FOR THE
GENERATOR.
9. PROVIDE 1" CONDUIT WITH PULL STRING TO THIS
LOCATION FROM GARAGE DOOR
CONTROLLER/MOTOR. RE: FLAG NOTE #3 ON THIS
SHEET FOR MORE INFORMATION.
10. PROVIDE ACUITY WSD PDT DUAL-TECHNOLOGY,
1-POLE WALL SENSOR SWITCH OR EQUIVALENT.
11. PROVIDE ACUITY CMR-PDT-10-2P
DUAL-TECHNOLOGY, 2-POLE WALL, CEILING MOUNT,
OCCUPANCY SENSOR OR EQUIVALENT.
FLAG NOTES:#
1 2
3
J
4 5 8
6
6
6
7
7
9
11
10
11 11
11
11
11
11
11
7
7
7
P
6
P
1
P
2
P
2
P
2
P
3P
3
P
4
P
5
P
1
EF
4
EF
3
EF
2
EF
1
EF
5
EF
2
EF
2
CUH
1
UH
1
UH
1
UH
1
UH
1
UH
1
UH
1
UH
1
UH
1
B
1
B
1
B
1
WH
1
WH
1
UH
1
UH
1
UH
1
CUH
3
CUH
4
UH
1
M1-11,13
M1-15,17
M1-19,21,23
M1-25,27,29
M1-31,33,35
GF
1
M1-14
M1-14
M1-14
M1-14
M1-14
M1-14
M1-14
M1-14
M1-16
M1-16
M1-16
M1-16
M1-18
M1-20
M1-20
M1-20
M1-20
X1
X1
+48"P1-1
P1-1 X1
X1X1
X1
L1-5
6
X1 1
1
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH31 AUG. 2018
PERMIT RESPONSES
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL PLAN
- PARKING
LEVELS
E-201
09/21/18
SCALE:
ELECTRICAL PLAN - LEVEL 1
1/8" = 1'-0"
UP
DN
UP
DN
DN
D/W
1
K
J
F
E
D
B
A
8 10 2 4 6 12 15
16
17
18
19
20
21
22
YB
YA
YC
YD
YF YG
YH
YL
YJ
YM
16
17
18
19
20
21
22
YK
YE
YD
7
5 1
2
L
M
3 7
6
8 10
G
H
D/W
D/WD/WD
OS SOSK
SK SK
S3 S3
S3
S3
S1
S1
S1
S1 S1
S1 S1
S1
S1
S1 S1
S1
S1 S1
S1
S1
S1
S1
S1
S1
S1
S1
S1
R1
E1
E1
X1
X1
X1
X1
X1
X1
S1
S1
S
OS
S1
SO
S4
X1
P1-2
P1-2
P1-2
P1-2
P1-4
P1-4
P1-4
P1-4
P1-6
P1-8
P1-8
P1-8 P1-8
L1-5
L1-5
L1-7
L1-9
L1-4
L1-4
L1-4
L1-4
L1-4
1. ALL LIGHTING ON THIS SHEET IS ON EMERGENCY
GENERATOR UNLESS NOTED OTHERWISE.
2. ALL EXIT SIGNS SHALL BE CIRCUITED TO LOCAL
LIGHTING CIRCUIT.
NOTES:
1. ALL EXTERIOR LIGHTS SHALL BE CONTROLLED VIA
EXTERIOR LIGHTING CONTROL PANEL WITH
ASTRONOMIC TIME CLOCK AND PHOTOCELL.
2. SURFACE MOUNT CCTV CAMERA - IP MEGAPIXEL
DOME.
3. WIRELESS ACCESS POINT (WI-FI). MOUNT 2-PORT
BISCUIT JACK ABOVE CEILING. PROVIDE ACCESS
PANEL AS REQUIRED.
4. GENERATOR ANNUNCIATOR PANEL.
5. PROVIDE ACUITY CMR-PDT-10-2P
DUAL-TECHNOLOGY, 2-POLE, CEILING MOUNT,
OCCUPANCY SENSOR OR EQUIVALENT.
6. PROVIDE ACUITY WSD PDT DUAL-TECHNOLOGY,
1-POLE WALL SENSOR SWITCH OR EQUIVALENT.
7. RE: DIAGRAM 2/E-402 FOR MDF INFORMATION.
FLAG NOTES:#
1
1
2
180
2
3
3
3
3
3
3
ANN4
5
5
6
6
7
P1-27 P1-29
P1-17
P1-19 P1-21P1-23P1-25P1-31WP
P1-13
WP
P1-13
WP P1-13
X1
1
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH31 AUG. 2018
PERMIT RESPONSES
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELETRICAL PLAN -
LEVEL 1
E-202
09/21/18
SCALE:
ELECTRICAL PLAN - LEVEL 2
1/8" = 1'-0"
UP
DN
UP
DN
D/W
1
K
J
F
E
D
B
A
8 10 2 4 6 12 15
16
17
18
19
20
21
22
YB
YA
YC
YD
YF YG
YH
YL
YJ
YM
16
17
18
19
20
21
22
YK
YE
YD
7
5 1
2
L
M
3 7
6
8 10
G
H
D/W
D/WD/WSKSK
SK
S3 S3
S3
S3
S
OS
X1
X1
X1
X1
X1
S1
S1
S1
S1 S1
S1 S1
S1
S1
S1
S1
S1
S1
S1
S1
S1
S4
SO
P1-10
P1-10
P1-10
P1-10
P1-12
L1-7
L1-9
L1-6 L1-6
L1-6
1. ALL LIGHTING ON THIS SHEET IS ON EMERGENCY
GENERATOR UNLESS NOTED OTHERWISE.
2. ALL EXIT SIGNS SHALL BE CIRCUITED TO LOCAL
LIGHTING CIRCUIT.
NOTES:
1. WIRELESS ACCESS POINT (WI-FI). MOUNT 2-PORT
BISCUIT JACK ABOVE CEILING. PROVIDE ACCESS
PANEL AS REQUIRED.
2. PROVIDE ACUITY CMR-PDT-10-2P
DUAL-TECHNOLOGY, 2-POLE, CEILING MOUNT,
OCCUPANCY SENSOR OR EQUIVALENT.
3. PROVIDE ACUITY WSD PDT DUAL-TECHNOLOGY,
1-POLE WALL SENSOR SWITCH OR EQUIVALENT.
FLAG NOTES:#
2
3
1
1
1
1
1
1
P1-24 P1-26
P1-14
P1-16 P1-18P1-20P1-22P1-28Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL PLAN
- LEVEL 2
E-203
09/21/18
SCALE:
ELECTRICAL PLAN - LEVEL 3
1/8" = 1'-0"
UP
DN
UP
DN
D/W
1
K
J
F
E
D
B
A
8 10 2 4 6 12 15
16
17
18
19
20
21
22
YB
YA
YC
YD
YF YG
YH
YL
YJ
YM
16
17
18
19
20
21
22
YK
YE
YD
7
5 1
2
L
M
3 7
6
8 10
G
H
D/W
D/W D/WD/WS3
S3
S3
S3
SK
SK
X1
X1
X1
X1
X1
SO
S1
S1
S1
S1
S1 S1
S1 S1 S1
S1
S1
S1
S1
S1
S1
S1
S4
S
OS
'DP3'
P3-1
P3-3
P3-1
P3-1
P3-1
L1-7
L1-9
L1-8 L1-8
L1-8SK'P3'
1. ALL LIGHTING ON THIS SHEET IS ON EMERGENCY
GENERATOR UNLESS NOTED OTHERWISE.
2. ALL EXIT SIGNS SHALL BE CIRCUITED TO LOCAL
LIGHTING CIRCUIT.
NOTES:
1. WIRELESS ACCESS POINT (WI-FI). MOUNT 2-PORT
BISCUIT JACK ABOVE CEILING. PROVIDE ACCESS
PANEL AS REQUIRED.
2. PROVIDE ACUITY CMR-PDT-10-2P
DUAL-TECHNOLOGY, 2-POLE, CEILING MOUNT,
OCCUPANCY SENSOR OR EQUIVALENT.
3. PROVIDE ACUITY WSD PDT DUAL-TECHNOLOGY,
1-POLE WALL SENSOR SWITCH OR EQUIVALENT.
FLAG NOTES:#
2
3
1
1
1
1
1
1
P3-23 P3-25
P3-13
P3-15 P3-17P3-19P3-21P3-27Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL PLAN
- LEVEL 3
E-204
09/21/18
SCALE:
ELECTRICAL PLAN - LEVEL 4
1/8" = 1'-0"
DN
H
GF
DN
1
K
J
F
E
D
B
A
8 10 2 4 6 12 15
16
17
18
19
20
21
22
YB
YA
YC
YD
YF YG
YH
YL
YJ
YM
16
17
18
19
20
21
22
YK
YE
YD
7
5 1
2
L
M
3 7
6
8 10
G
H
D/W
D/W
D/W D/WD/WSS3 S3
S3
S3
SK
SK
X1
X1
X1
X1
X1
S1
S1
S1
S1
S1
S1 S1
S1
S1
S1 S1
S1
S1
S1
S1
S1
S4
SOS
OS
S5
P1-15
P3-2
P3-2
P3-2
P3-2
P3-4
L1-2
L1-7
L1-9
SKL1-10
L1-10L1-10
1. ALL LIGHTING ON THIS SHEET IS ON EMERGENCY
GENERATOR UNLESS NOTED OTHERWISE.
2. ALL EXIT SIGNS SHALL BE CIRCUITED TO LOCAL
LIGHTING CIRCUIT.
NOTES:
1. WIRELESS ACCESS POINT (WI-FI). MOUNT 2-PORT
BISCUIT JACK ABOVE CEILING. PROVIDE ACCESS
PANEL AS REQUIRED.
2. PROVIDE ACUITY CMR-PDT-10-2P
DUAL-TECHNOLOGY, 2-POLE, CEILING MOUNT,
OCCUPANCY SENSOR OR EQUIVALENT.
3. PROVIDE ACUITY WSD PDT DUAL-TECHNOLOGY,
1-POLE WALL SENSOR SWITCH OR EQUIVALENT.
4. RECEPTACLE MOUNTED IN TOP OF ELEVATOR SHAFT.
5. LIGHT MOUNTED IN TOP OF ELEVATOR SHAFT.
FLAG NOTES:#
4
5
3
4
1
1
1
1
1
1
P3-24 P3-26
P3-14
P3-16 P3-18P3-20P3-22P3-28Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL PLAN
- LEVEL 4
E-205
09/21/18
1
K
J
F
E
D
B
A
9 10 2 4 6 12 15
16
17
18
19
20
21
22
Y
YF YG
YH
YL
YJ
YM
16
17
18
19
20
21
22
YK
YE
YD
7
5 1
2
L
M
3 7
6
9 10
G
H
SCALE:
ELETRICAL PLAN - ROOF
1/8" = 1'-0"
1. PROVIDE 12W/FT, 208 VOLT ELECTRICAL, SELF
REGULATING, HEATING CABLE IN ALL GUTTERS
AND DOWNSPOUTS. ELECTRIC HEATING CABLE
SHALL BE UL AND CSA LISTED SPECIFICALLY AS
ELECTRIC ROOF AND GUTTER DE-ICING AND
SNOWMELTING EQUIPMENT. CABLE BE QUALIFIED
FOR PROLONGED UV EXPOSURE TO THE SUN PER
IEEE 515-1997 AND TO WITHSTAND CONTINUOUS
SUBMERSION IN WATER PER IEEE 515.1-1997.
PROVIDE ALL ELECTRICAL CONNECTION KITS,
SUPPORTS, DOWNSPOUT HANGERS, CONTROLS,
AND OTHER APPERTENANCES FOR A COMPLETE
AND OPERABLE SYSTEM IN COMPLIANCE WITH
MANUFACTURER'S RECOMENDATIONS.
2. OVERCURRENT PROTECTION FOR ELECTRIC
HEATING CABLE CIRCUITS SHALL BE 30-mA-TRIP
GROUND FAULT TYPE CIRCUIT BREAKERS.
3. PROVIDE ELECTRIC HEATING CABLE IN DRAINAGE
VALLEYS, AS SHOWN ON PLAN. ROUTE ELECTRIC
HEATING CABLE A MINIMUM OF 8” INTO ROOF
DRAIN.
4. CONTRACTOR SHALL PROVIDE COMPLETE AND
OPERABLE CONTROL SYSTEM. SYSTEM SHALL
CONSIST OF AMBIENT THERMOSTAT AND
MOISTURE SENSOR WITH CONTACTOR(S).
5. CONTRACTOR SHALL SUBMIT SHOP DRAWING
SUBMITTAL WITH ALL EQUIPMENT, CONTROLS,
CONTACTORS AND ACCESSORY DATA SHEETS.
DATA SHEETS SHALL BE MARKED INDICATING THE
ACTUAL MODEL, VOLTAGE, RATINGS, AND
ACCESSORIES BEING PROPOSED TO BE PROVIDED.
SHOP DRAWING SHALL INCLUDE LAYOUT PLAN
INDICATING ZONING, CONTROL INTENT, AND
ESTIMATED CIRCUIT LENGHTS. PARTIAL OR
INCOMPLETE SUBMITTALS WILL NOT BE ACCEPTED.
6. ACTUAL INSTALLED HEAT TRACE CIRCUIT LENGTH
MAY VARY FROM DESIGN OR PLANNED FOR
CIRCUIT LENGTHS. CONTRACTOR SHALL MEASURE
AND RECORD ACTUAL CIRCUIT LENGTHS AND
PROVIDE THE CIRCUIT LENGTHS AS PART OF TEST
REPORTS. CIRCUIT LENGTH SHALL NOT EXCEED
THE MANUFACTURER'S RECOMMENDED LENGTH
FOR THE OVERCURRENT PROTECTION RATING.
CONTACT ARCHITECT/ENGINEER IF ACTUAL
INSTALLED ELECTRIC HEATING CABLE LENGTHS
EXCEED THE MANUFACTURER'S RECOMMENDED
LENGTH FOR THE OVERCURRENT PROTECTION
RATING.
7. CONTRACTOR SHALL PROVIDE ALL TESTING AND
FIELD QUALITY CONTROL MEASURES
RECOMMENDED BY MANUFACTER. INCLUDING, BUT
NOT LIMITED TO, MEGER TEST ALL ELECTRIC
HEATING CABLE CIRCUITS. AFTER INSTALLATION
ALL HEATING CABLE CIRCUITS SHALL BE TESTED
WITH A 2500 VDC MEGOHMMETER, INSULATION
RESISTANCE FROM THE CONDUCTORS TO THE
SHIELD SHALL BE GREATER THAN 1000 MEGOHMS.
CONTRACTOR SHALL RECORD ALL TESTS AND
PROVIDE TEST REPORTS TO
ARCHITECT/ENGINEER, PRIOR TO PROJECT
CLOSEOUT OR FINAL PUNCH REQUESTS, AS PART
OF THE PROJECT CLOSEOUT DOCUMENTS.
ROOF HEAT
TRACE NOTES:
J
J
J
J
1
1
1
1
1. PROVIDE 30A, 208V ELECTRICAL CIRCUIT TO
WEATHERPROOF JUNCTION BOX FOR ROOF HEAT
TRACE. REFER TO ROOF HEAT TRACE NOTES ON
THIS SHEET FOR MORE INFORMATION.
2. PROVIDE (1) RUN OF 12W/FT, SELF-REGULATING
HEATING CABLE IN GUTTER AND (1) RUN OF 12W/FT,
SELF-REGULATING HEATING CABLE IN DOWNSPOUT.
REFER TO ROOF HEAT TRACE NOTES ON THIS SHEET
FOR MORE INFORMATION.
3. MECHANICAL EQUIPMENT LOCATED IN ATTIC SPACE.
4. LOCATE SWITCH AT HATCH TO ATTIC SPACE.
5. LIGHT FIXTURES SHALL BE LOCATED IN ATTIC SPACE.
6. LOCATE JUNCTION BOX IN ATTIC SPACE FOR FUTURE
HEAT TRACE. PROVIDE 1" CONDUIT FROM PANEL 'P3'
TO JUNCTION BOX FOR FUTURE HEAT TRACE
CONDUCTORS. ELECTRICAL CONTRACTOR SHALL
CLEARLY LABEL JUNCTION BOX WITH SELF-ADHESIVE
PRINTED LABEL INDICATING JUNCTION BOX IS FOR
FUTURE HEAT TRACE CONNECTION.
7. PROVIDE (1) RUN OF 12W/FT, SELF-REGULATING
HEATING CABLE IN GUTTER AND (1) RUN OF 12W/FT,
SELF-REGULATING HEATING CABLE IN DOWNSPOUT.
EXTEND HEATING CABLE 5 FEET INTO STORM DRAIN.
REFER TO ROOF HEAT TRACE NOTES ON THIS SHEET
FOR MORE INFORMATION.
FLAG NOTES:#
7
7
2
2
P3-5,7
P3-9,11
P3-6,8
P3-10,12
MAU
1
MAU
2
EF
6
EF
6
EF
6
EF
6
EF
6
EF
6
EF
6
EF
6
EF
6
EF
6
3 3
3
S4 S4 S4 S4 S4
S
4
5 5 5 5 5
P3-29
P3-29 P3-29
J
J
J
J
6
6
6
6
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL PLAN
- ROOF
E-206
09/21/18
SCALE: 1 ELECTRICAL PLAN - TYPE STUDIO ( NO SHAFT) @ LEVELS 1-4
1/2"= 1'-0"
S1
S1
S2
S1
S1
S1
S1
SSS SS
REF
1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. MOUNT RECEPTACLE WITHIN 10" OF TOP OF
COUNTERTOP.
5. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:
1
C
DISP S2
3
4
C
S
+72"
RANGE
MW
TV
DW1
5
'UNIT LOAD CENTER'
EF
1
1
3
5,7
9
11
2
13
6
6
6
8 6
8
8
8
8
6
10
10
10
12
1212
14
UNIT TYPE: STUDIO (NO SHAFT) @ LEVELS 1-4 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1080 6
7 4500 A - - - + 20 1 R REC 900 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 100 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 360 R KITCHEN 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- STUDIO 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
448 3 = 1344 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4344 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 470 VA
Over 120,000VA 25% = 0 VA
3470.4 VA x 100% = 3470 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 19517 VA
TOTAL DEMAND ELECTRICAL LOAD: 17149 VA
MINIMUM ELECTRICAL SERVICE SIZE: 82.4 AMPS
C
4
C
13
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL
PLAN - STUDIO
E-301
09/21/18
SCALE: 1 ELECTRICAL PLAN - TYPE STUDIO (NO SHAST) OPP HAND @ LEVELS 1-4
1/2"= 1'-0"
S2
S1
S1
S S
S1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. MOUNT RECEPTACLE WITHIN 10" OF TOP OF
COUNTERTOP.
5. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#
S1
REF
1
C
DISP
S2
3
4
C
S
RANGE
+72"
MW
DW
1
TV
5
'UNIT LOAD CENTER'
EF
1
S1
S1
S1
SS
1
3
5,7
9
11
13
13
6
6
6
6
6
8
8
8
8
8
10
10
10
12
12
12
14
UNIT TYPE: STUDIO (NO SHAFT) OPP HAND @ LEVELS 1-4 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1080 6
7 4500 A - - - + 20 1 R REC 900 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 100 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 360 R KITCHEN 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- STUDIO 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
449 3 = 1347 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4347 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 471 VA
Over 120,000VA 25% = 0 VA
3471.45 VA x 100% = 3471 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 19520 VA
TOTAL DEMAND ELECTRICAL LOAD: 17150 VA
MINIMUM ELECTRICAL SERVICE SIZE: 82.5 AMPS
C 2
C 4
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL
PLAN - STUDIO
E-302
09/21/18
SCALE: 1 ELECTRICAL PLAN - STUDIO x01 @ LEVELS 1-4
1/2"= 1'-0"
S2
S1
S1
SS S
S1
REF
1
C
DISPS
2
3
4
C
S
1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. MOUNT RECEPTACLE WITHIN 10" OF TOP OF
COUNTERTOP.
5. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#
RANGE
MW
+72"
DW
1
TV
'UNIT LOAD CENTER'
5
EF
1
S1
S1
S1
SS
1
3
5,7
9
11
13
13
6
6
6
6
6
8
8
8
8
8
10
10
10
12
12
14
12
UNIT TYPE: STUDIO x01 @ LEVELS 1-4 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1080 6
7 4500 A - - - + 20 1 R REC 900 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 100 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 360 R KITCHEN 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
DC
1
18
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- STUDIO 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
450 3 = 1350 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4350 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 473 VA
Over 120,000VA 25% = 0 VA
3472.5 VA x 100% = 3473 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 19523 VA
TOTAL DEMAND ELECTRICAL LOAD: 17152 VA
MINIMUM ELECTRICAL SERVICE SIZE: 82.5 AMPS
C 2
C 4
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL
PLAN - STUDIO
E-303
09/21/18
SCALE: 1 ELECTRICAL PLAN - STUDIO x07 @ LEVELS 1-4
1/2"= 1'-0"
S2
S1
S1
SS S
1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. MOUNT RECEPTACLE WITHIN 10" OF TOP OF
COUNTERTOP.
5. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:
S1
REF
1
C
DISP
S2
3
4
C
S
RANGE
+72"
MW
DW
1
TV
5
'UNIT LOAD CENTER'
EF
1S1
S1
S1
SS
1
3
5,7
9
11
13
13
6
6
6
6
6
8
8
8
8
8
10
10
10
12
12
12
14
UNIT TYPE: STUDIO x07 @ LEVELS 1-4 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1080 6
7 4500 A - - - + 20 1 R REC 900 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 100 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 360 R KITCHEN 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- STUDIO 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
449 3 = 1347 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4347 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 471 VA
Over 120,000VA 25% = 0 VA
3471.45 VA x 100% = 3471 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 19520 VA
TOTAL DEMAND ELECTRICAL LOAD: 17150 VA
MINIMUM ELECTRICAL SERVICE SIZE: 82.5 AMPS
C 2
C 4
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:
#
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL
PLAN - STUDIO
E-304
09/21/18
SCALE: 1 ELECTRICAL PLAN - STUDIO x08 @ LEVELS 1-4
1/2"= 1'-0"
S2
S1
S1 S SS
1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. MOUNT RECEPTACLE WITHIN 10" OF TOP OF
COUNTERTOP.
5. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#
S1
REF
1
C
DISP
S2
3
4
C
S
RANGE
+72"
MW
DW
1
TV
5
'UNIT LOAD CENTER'
HRV
1
S1
S1
S1
SS
1
3
5,7
9
11
1313
6
6
6
6
6 8
8
8
8
8
12
12
10
10
10
16
12
UNIT TYPE: STUDIO x08 @ LEVELS 1-4 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1080 6
7 4500 A - - - + 20 1 R REC 900 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 100 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 360 R KITCHEN 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- STUDIO 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
449 3 = 1347 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4347 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 471 VA
Over 120,000VA 25% = 0 VA
3471.45 VA x 100% = 3471 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 19520 VA
TOTAL DEMAND ELECTRICAL LOAD: 17150 VA
MINIMUM ELECTRICAL SERVICE SIZE: 82.5 AMPS
C
2
C
4
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL
PLAN - STUDIO
E-305
09/21/18
SCALE: 1 ELECTRICAL PLAN - TYPE STUDIO + x09 UNITS @ LEVELS 1-4
1/2"= 1'-0"
1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#
UNIT TYPE: STUDIO + x09 @ LEVELS 1-4 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1080 6
7 4500 A - - - + 20 1 R REC 900 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 100 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 SPARE 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPACE + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- STUDIO 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
504 3 = 1512 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4512 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 529 VA
Over 120,000VA 25% = 0 VA
3529.2 VA x 100% = 3529 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 19685 VA
TOTAL DEMAND ELECTRICAL LOAD: 17208 VA
MINIMUM ELECTRICAL SERVICE SIZE: 82.7 AMPS
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:S SSSS
S1
S1
S1
S1
S2
S1
S1
REF
1
2
DISP
S3
4
C
S
C
RANGE
MW
+72"
DW
1
TV
5
'UNIT LOAD CENTER'
EF
1
1
3
5,7
9
11
13
13
6
6
6
6
68
8
8
8
8
10
10
10
12
12
12
14
C
2
C
4
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL
PLAN - STUDIO
E-306
09/21/18
MAX.SCALE: 1 ELECTRICAL PLAN - ACCESSIBLE STUDIO + @ LEVEL 1
1/2"= 1'-0"SSS
S
S
S1
S1
S1
S1
S2
S1
S1
1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. MOUNT RECEPTACLE WITHIN 10" OF TOP OF
COUNTERTOP.
5. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#
REF
1
2
DISP
S3
4
C
S
C
RANGE
MW
+72"
DW 1
TV
5
'UNIT LOAD CENTER'
EF
1
1
3
5,7
9
11
13
13
6
6
6
6
68
8
8
8
8
10
10
10
12
12
12
14
UNIT TYPE: ADA STUDIO + VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1080 6
7 4500 A - - - + 20 1 R REC 900 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 100 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 360 R KITCHEN 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- STUDIO + 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
505 3 = 1515 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4515 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 530 VA
Over 120,000VA 25% = 0 VA
3530.25 VA x 100% = 3530 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 19688 VA
TOTAL DEMAND ELECTRICAL LOAD: 17209 VA
MINIMUM ELECTRICAL SERVICE SIZE: 82.7 AMPS
C
2
C
4
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL
PLAN - STUDIO
E-307
09/21/18
D/WSCALE: 1 ELECTRICAL PLAN - ONE BR x02 @ LEVELS 1-4
1/2"= 1'-0"SSS1
S2
S1
S1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. MOUNT RECEPTACLE WITHIN 10" OF TOP OF
COUNTERTOP.
5. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#
5
'UNIT LOAD CENTER'SS1
6
8
8
14
12
10
UNIT TYPE: ONE BR x02 @ LEVELS 1-4 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1620 6
7 4500 A - - - + 20 1 R REC 1620 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 100 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 360 R KITCHEN 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- STUDIO + 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
635 3 = 1905 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4905 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 667 VA
Over 120,000VA 25% = 0 VA
3666.75 VA x 100% = 3667 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 20078 VA
TOTAL DEMAND ELECTRICAL LOAD: 17346 VA
MINIMUM ELECTRICAL SERVICE SIZE: 83.4 AMPS
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:
SS S1
S1
DW DISP SCC
C
REF+72"
MW
RANGE
1
1 3
2
TV
TV
EF
1
1 3
5,7
9 11 2 4 6
6
4
66
6 6
6
8
88
10
10
12
C13
S1
C13
8
8
8
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL
PLAN - STUDIO
E-308
09/21/18
D/WSCALE: 1 ELECTRICAL PLAN - ONE BR x03 @ LEVELS 1-4
1/2"= 1'-0"
S SSSSS1
S2
S1
S1 S1
S1
S1
DWDISP SC C
C
REF +72"
MW
RANGE
1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#
1
13
2
C S TV
TV
4
'UNIT LOAD CENTER'
EF
1
1 3
5,7
9 1124
6
6
6
4
6
66
6
6
6
8
8
88
8
8
8
10
10
10
10
12
12
12
14
UNIT TYPE: ONE BR x03 @ LEVELS 1-4 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1800 6
7 4500 A - - - + 20 1 R REC 1620 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 100 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 540 R KITCHEN 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- 1BR 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
637 3 = 1911 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4911 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 669 VA
Over 120,000VA 25% = 0 VA
3668.85 VA x 100% = 3669 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 20084 VA
TOTAL DEMAND ELECTRICAL LOAD: 17348 VA
MINIMUM ELECTRICAL SERVICE SIZE: 83.4 AMPS
C13
13
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:
8
C13
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
ELECTRICAL
PLAN - 1 BR
E-309
09/21/18
D/WSCALE: 1 ELECTRICAL
PLAN - ONE BR - UNITS 310 & 410
1/2"= 1'-0"
S SS SSSS1
S2
S1 S1 S1
S1
S1
S1
1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#
DW DISP SCC
C
REF+72"
MW
RANGE
1
1 3
2
CSTV
TV
4
'UNIT LOAD CENTER'
EF
1
1 3
5,7
911 2 4
4
6
6
6
6
6
6
6
6
88
8
8
88
8
10
10
10
10
10
12
1214
12
UNIT TYPE: ONE BR - UNITS 310 & 410 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1620 6
7 4500 A - - - + 20 1 R REC 1440 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 120 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 540 R KITCHEN 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- 1BR 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
654 3 = 1962 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4962 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 687 VA
Over 120,000VA 25% = 0 VA
3686.7 VA x 100% = 3687 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 20135 VA
TOTAL DEMAND ELECTRICAL LOAD: 17366 VA
MINIMUM ELECTRICAL SERVICE SIZE: 83.5 AMPS
C13
13
8
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:
C13
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-310
ELECTRICAL
PLAN - 1 BR
09/21/18
D/WSCALE: 1 ELECTRICAL PLAN - TYP ONE BR @ LEVELS 1-4
1/2"= 1'-0"
SSSSS SS1
S2
S1
S1 S1
S1
S1
S1
DWDISP SC C
C
REF +72"
MW
RANGE
1
13
2
C
1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#STV
TV
4
'UNIT LOAD CENTER'
HRV
1
1 3
5,7
9 1124
4
6
6
6
6
66
6
88
8
8
8
8
8
8 10
10
10
10
10
12
12
14
12
UNIT TYPE: ONE BR @ LEVELS 1-4 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1440 6
7 4500 A - - - + 20 1 R REC 1620 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 120 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 360 R KITCHEN 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- 1BR 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
654 3 = 1962 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4962 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 687 VA
Over 120,000VA 25% = 0 VA
3686.7 VA x 100% = 3687 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 20135 VA
TOTAL DEMAND ELECTRICAL LOAD: 17366 VA
MINIMUM ELECTRICAL SERVICE SIZE: 83.5 AMPS
13 C
13
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:
13 C
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-311
ELECTRICAL
PLAN - 1 BR - B
09/21/18
D/W
SCALE: 1 ELECTRICAL PLAN - ONE BR x16 @ LEVELS 1-4
1/2"= 1'-0"
SSSS SS1
S2
S1
S1 S1
S1
S1
DWDISP SC C
C
REF +72"
MW
RANGE
1
13
2
C S 1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#
TV
TV
4
1 3
5,7
9 112 4
4
6
6
6
6
66
6
8
8
8
8
8
8
88
10
10
10
10
12
12
EF
1
12
14
UNIT TYPE: ONE BR x16 @ LEVELS 1-4 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1620 6
7 4500 A - - - + 20 1 R REC 1620 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 120 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 540 R KITCHEN 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- 1BR 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
613 3 = 1839 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4839 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 644 VA
Over 120,000VA 25% = 0 VA
3643.65 VA x 100% = 3644 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 20012 VA
TOTAL DEMAND ELECTRICAL LOAD: 17323 VA
MINIMUM ELECTRICAL SERVICE SIZE: 83.3 AMPS
C
13
13
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:
C
13
S1
'UNIT LOAD
CENTER'
6
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-312
ELECTRICAL
PLAN - 1 BR - B
09/21/18
D/W
SCALE: 1 ELECTRICAL PLAN - ONE BR x17 @ LEVELS 2-4
1/2"= 1'-0"SS S1
S2
S1
S1S1
S1
S1
SS SC
1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#
REF
1
+72"
2
MW
RANGE
DW
1
C SDISP
3 C
C S TV
TV
4
EF
1
135,7
9
11
2 4
4
6
6
6
6
6 6
6
6
8
8 8
8
8
8
8
10
10
1010
12
12
12
14
UNIT TYPE: ONE BR x17 @ LEVELS 2-4 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1620 6
7 4500 A - - - + 20 1 R REC 1620 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 120 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 540 R KITCHEN 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- 1BR 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
623 3 = 1869 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4869 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 654 VA
Over 120,000VA 25% = 0 VA
3654.15 VA x 100% = 3654 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 20042 VA
TOTAL DEMAND ELECTRICAL LOAD: 17333 VA
MINIMUM ELECTRICAL SERVICE SIZE: 83.3 AMPS
C
13
13
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:
C
13
S1
'UNIT LOAD
CENTER'
8
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-313
ELECTRICAL
PLAN - 1 BR - S
09/21/18
D/WSCALE: 1 ELECTRICAL PLAN - ONE BR, TYPE S @ LEVEL 4
1/2"= 1'-0"SS S1
S2
S1 S1 S1
S1
S1
SS SC
REF
1
+72"
2
MW
RANGE
DW
1
C SDISP
3 C
C STV
TV
4
EF
1
135,7
9
11
2 4
4
6
6
6
6
6 6
6
6
8
8 8
8
8
8
8
10
10
1010
12
12
12
14
C
13
13
C
13
'UNIT LOAD
CENTER'
8
1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. MOUNT RECEPTACLE WITHIN 10" OF TOP OF
COUNTERTOP.
5. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:UNIT TYPE: ONE BR, TYPE S @ LEVEL 4 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1620 6
7 4500 A - - - + 20 1 R REC 1620 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 100 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 540 R KITCHEN 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- 1BR 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
635 3 = 1905 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4905 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 667 VA
Over 120,000VA 25% = 0 VA
3666.75 VA x 100% = 3667 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 20078 VA
TOTAL DEMAND ELECTRICAL LOAD: 17346 VA
MINIMUM ELECTRICAL SERVICE SIZE: 83.4 AMPS
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-314
ELECTRICAL
PLAN - 1 BR - S
09/21/18
SCALE: 1 ELECTRICAL PLAN - NE TWO BR @LEVELS 2 & 3
1/2"= 1'-0"SSS1
S2S1
S1 S1
S1
S1
S2
S
SSSC
REF
1
+72"
2
RANGE
MW
C C
S
DISP
3
DISP
1
C
C
STV
TV
TV
4
EF
1
1 3 5,7
9 1142
4
6
6
6
6 6
6
6
6
8
8
8
8
1010
10
10
1212
12
12
12
14 14
1414
14
16
C 13
88
S1 SS1
S1
'UNIT LOAD
CENTER'S8S10
C
13
C 13
10
12
1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- 2BR 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
782 3 = 2346 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
5346 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 821 VA
Over 120,000VA 25% = 0 VA
3821.1 VA x 100% = 3821 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 20519 VA
TOTAL DEMAND ELECTRICAL LOAD: 17500 VA
MINIMUM ELECTRICAL SERVICE SIZE: 84.1 AMPS
UNIT TYPE: NE TWO BR @ LEVELS 2 & 3 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1620 6
7 4500 A - - - + 20 1 R REC 1440 8
9 864 A DISPOSAL 1 20 + 20 1 R REC 1260 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 L LIGHTING 160 12
13 540 R KITCHEN 1 20 + 20 1 R BATHROOMS 436 14
15 SPARE 1 20 + 20 1 R MEDIA CABINET 1800 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + 20 1 SPARE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-315
ELECTRICAL
PLAN - 2 BR
09/21/18
SCALE: 1 ELECTRICAL PLAN - ACCESSIBLE ONE BR @ LEVEL 2
1/2"= 1'-0"
S SS SSS1
S2
S1S1S1
S1
S1
DW DISP SCC
C
REF+72"
MW
RANGE
1
1 3
2
CSTV
TV
4
'UNIT LOAD CENTER'
EF
1
1 3
5,7
911 2 4
4
6
6
6
6
6
6
6
6
8
8
8
8
88
8
10
10
10
10
12
12
14
12
C13
13
C 13
8
1. PROVIDE 5-mA GFCI CIRCUIT BREAKER IN PANEL
SERVING THIS RECEPTACLE.
2. PROVIDE 60A, 208V RECEPTACLE FOR ELECTRIC
RANGE. COORDINATE EXACT POWER
REQUIREMENTS WITH MANUFACTURER'S
INSTALLATION INSTRUCTIONS PRIOR TO ROUGH-IN.
3. PROVIDE GFCI RECEPTACLE FOR GARBAGE
DISPOSAL.
4. STRUCTURED MEDIA CABINET FOR UNIT
TECHNOLOGY SYSTEMS. PROVIDE DUPLEX
RECEPTACLE INSIDE MEDIA CABINET.
FLAG NOTES:#
1. PROVIDE ARC-FAULT CIRCUIT-INTERRUPTER
(AFCI) CIRCUIT BREAKERS FOR ALL BRANCH
CIRCUITS SERVING OUTLETS OR DEVICES IN
RESIDENCE, EXCEPT FOR GARAGE AND
BATHROOMS, PER NEC 210.12.
2. PROVIDE TAMPER-RESISTANT TYPE
RECEPTACLES IN ALL AREAS REQUIRED IN NEC
406.12.
3. VERIFY ALL EQUIPMENT AND APPLIANCE
ELECTRICAL POWER CONNECTION
REQUIREMENTS WITH GC PRIOR TO ROUGH-IN,
FOR THE EXACT MODELS MAY HAVE CHANGED
SINCE DESIGN.
4. REFER TO ARCHITECTURAL PLANS AND INTERIOR
ELEVATIONS FOR RECEPTACLE AND DEVICE
PLACEMENT. COORDINATE ALL RECEPTACLE
MOUNTING LOCATIONS WITH FIXTURES,
APPLIANCES, CABINETRY, AND OTHER
EQUIPMENT.
5. COORDINATE EXACT POWER CONNECTION AND
DEVICE REQUIREMENTS FOR TELECOM, AV, DATA,
AND SECURITY EQUIPMENT WITH LOW VOLTAGE
SYSTEMS PLANS. OR WITH ARCHITECT AND LOW
VOLTAGE CONTRACTOR IF NO LOW VOLTAGE
SYSTEMS PLANS ARE AVAILABLE.
6. COORDINATE 120 VOLT POWER CONNECTIONS
FOR FIRE ALARM SYSTEM AND DEVICES, AND
CARBON MONOXIDE DEVICES.
7. ALL EQUIPMENT, DEVICES AND CONDUCTORS
SHALL BE IN NEW CONDITION AND RATED FOR
THE APPLICATION.
8. COORDINATE POWER CONNECTIONS FOR
MECHANICAL EQUIPMENT, OWNER PROVIDED
EQUIPMENT AND APPLIANCES, AND ALL OTHER
EQUIPMENT PROVIDED BY OTHER DIVISIONS
WITH SUBMITTAL DATA CUT SHEETS, WIRING
DIAGRAMS, MANUFACTURER'S INSTALLATION
INSTRUCTIONS. FIELD COORDINATE EXACT
LOCATIONS OF EQUIPMENT AND POWER
CONNECTIONS WITH GC AND OTHER
DIVISIONS/CONTRACTORS.
9. CONTRACTOR SHALL PROVIDE A “BOX
WALK” WITH ARCHITECT AND/OR OWNER'S
REPRESENTATIVE AFTER ELECTRICAL DEVICE
BOXES HAVE BEEN ROUGHED-IN OR INSTALLED
AND PRIOR TO WIRING AND INSTALLATION OF
DEVICES. CONTRACTOR SHALL INCLUDE IN THEIR
PRICE THE RELOCATION AND ADJUSTMENTS OF
ELECTRICAL DEVICE BOXES TO MEET THE
ARCHITECT'S/OWNER'S REQUIREMENTS.
10. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR
FIELD COORDINATING THE LOCATION OF
ELECTRICAL EQUIPMENT, JUNCTION BOXES,
DISCONNECTS, ETC. EC SHALL BE RESPONSIBLE
FOR COORDINATION AND THE ROUTING OF
FEEDERS, AND BRANCH CIRCUITS.
11. THE NUMBER NEXT TO ELECTRICAL DEVICES,
RECEPTACLES, AND SWITCHES INDICATES THE
CIRCUIT IN THE UNIT LOAD CENTER SERVING
THAT DEVICE.
12. REFER TO MECHANICAL EQUIPMENT SCHEDULE
SHEET E-001 FOR SAFETY SWITCH SIZE AND
CONDUCTOR SIZES COORDINATE FINAL
CONNECTIONS WITH MECHANICAL CONTRACTOR
AND REVIEWED SUBMITTALS.
RESIDENTIAL DWELLING
UNIT NOTES:UNIT TYPE: ACCESSIBLE ONE BR @ LEVEL 2 VOLTAGE: 120/208V, 1PH, 3W
MOUNTING: RECESSED BUS: 100
AIC: (2) MAIN: MLO
NO. LOAD TYPE LOAD DESCRIPTION BREAKER BUS BREAKER TYPE LOAD DESCRIPTION LOAD NO.A B POLE TRIP A B TRIP POLE A B
1 1440 E REF (1) 1 20 + 20 1 A SMALL APP 1500 2
3 1580 A MW 1 20 + 20 1 A SMALL APP 1500 4
5 4500 A RANGE 2 60 + 20 1 R REC 1620 6
7 4500 A - - - + 20 1 R REC 1440 8
9 864 A DISPOSAL 1 20 + 20 1 L LIGHTING 100 10
11 1080 A DISHWASHER (1) 1 20 + 20 1 R BATHROOM 237 12
13 540 R KITCHEN 1 20 + 20 1 R MEDIA CABINET 180 14
15 SPARE 1 20 + 20 1 SPARE 16
17 SPARE 1 20 + 20 1 SPARE 18
19 SPACE + SPACE 20
21 SPACE + SPACE 22
23 SPACE + SPACE 24
GENERAL NOTES: SPECIFIC NOTES:
A. (1) PROVIDE 5-mA GFCI CIRCUIT BREAKER.
B. (2) RE: 'UNIT LOAD CENTER SCHEDULE'/E-400 FOR AIC RATING.
C.
D.(3)
E. (4)
N.E.C. LOAD CALCULATION FOR DWELLING UNITS (STANDARD) BY: BAS
DATE: 7/21/2018
PROJECT NAME: Solar Vail
BUILDING: UNIT #: VOLTAGE: PHASE:
- 1BR 208 1
LIGHTING & GENERAL RECEPTACLES: (NEC 220.12, via NEC 220.42)
AREA(S.F.): VA / S.F. LOAD
656 3 = 1968 VA
SMALL APPLIANCES: (NEC 220.52(A))
2 1500 = 3000 VA
LAUNDRY CIRCUITS: (NEC 220.52(B))
0 1500 = 0 VA
4968 VA
First 3000VA 100% = 3000 VA
From 3001 to 120,000VA 35% = 689 VA
Over 120,000VA 25% = 0 VA
3688.8 VA x 100% = 3689 VA
ELECTRIC COOKING APPLIANCES: (NEC 220.55)
Range 1 9000 VA = 9000 VA
9000 VA x 100% = 9000 VA
APPLIANCES: (NEC 220.53)
APPLIANCE # LOAD TOTAL
Refrigerator 1 1440 VA = 1440 VA
Dishwasher 1 1080 VA = 1080 VA
Disposal 1 1656 VA = 1656 VA
Microwave 1 1800 VA = 1800 VA
5976 VA x 75% = 4482 VA
MECHANICAL EQUIPMENT:
EF-1 1 17 VA = 17 VA
0 0 VA = 0 VA
17 X 100% = 17 VA
MISCELLANEOUS EQUIPMENT:
IT 1 180 VA = 180 VA
180 X 100% = 180 VA
TOTAL PRE-DEMAND ELECTRICAL LOAD: 20141 VA
TOTAL DEMAND ELECTRICAL LOAD: 17368 VA
MINIMUM ELECTRICAL SERVICE SIZE: 83.5 AMPS
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-316
ELECTRICAL
PLAN - 2 BR
09/21/18
SPACE200A/3PSWB
2000A
208Y/120V, 3ø, 4W
2000/3MCCB
M
'M1' 150A/3P'P1'
PARKING LEVEL
LEVEL 1
600A/2PUNIT
LOAD
CENTER
TYPICAL OF 14
LEVEL 2
UNIT
LOAD
CENTER
TYPICAL OF 17 600A/3PLEVEL 3
'DP3'
UNIT
LOAD
CENTER
TYPICAL OF 17 250A/3P'P3'
LEVEL 4
UNIT
LOAD
CENTER
TYPICAL OF 17
#3/0 GROUNDING ELECTRODE
CONDUCTORS SIZED PER
SERVICE WIRING SCHEDULE.
BLDG. STEEL I.A.W.
N.E.C. 250-52(A)(2)
WATER SERVICE I.A.W.
N.E.C. 250-52(A)(1)
20 L.F. OF #4CU
ENCASED IN MIN. 2"
OF CONCRETE. I.A.W.
N.E.C. 250-52(A)(3)
N
G 70A/3P'L1'
N
L
E N
L 110A/3P110A/3P
70A/3P
15HP
ELEV-1
E
106kVA NATURAL
GAS GENERATOR.T
SCALE: 1 ELECTRICAL ONE-LINE DIAGRAM
NOT TO SCALE
SERVICE WIRING SCHEDULE
AMPS
ALUMINUM
(4W) GROUNDING ELECTRODE CONDUCTOR
3Ø, 4 WIRE W.P. M.F. C.E.C. G.RING G. ROD
2000 7[(4-500 KCMIL) 3 1/2"C] #3/0 CU #3/0 CU #3/0 CU #3/0 CU #6 CU
CONDUIT SIZES ARE BASED ON NEC TABLE 4 (RNC) AND TABLE 5 (THHN INSULATION).
ABBREVIATIONS: W.P. - WATER PIPE; M.F. - METAL FRAME OR STRUCTURE; C.E.C. - CONCRETE ENCASED ELECTRODE; G.RING. - GROUND
RING; G.ROD - GROUND ROD, PIPE OR PLATE ELECTRODE
WIRING SCHEDULE - ALUMINUM
AMPS (2WG) (3WG) (4WG)
1Ø, 2 WIRE, GROUND 1Ø, 3 WIRE, GROUND OR 3Ø, 3 WIRE, GROUND 3Ø, 4 WIRE, GROUND
125 (2#2/0 & 1#4 G) 1 1/2"C (3#2/0 & 1#4 G) 2"C (4#2/0 & 1#4 G) 2"C
150 (2#3/0 & 1#4 G) 1 1/2"C (3#3/0 & 1#4 G) 2"C (4#3/0 & 1#4 G) 2 1/2"C
200 (2-250 KCMIL & 1#4 G) 2"C (3-250 KCMIL & 1#4 G) 2 1/2"C (4-250 KCMIL & 1#4 G) 3"C
250 (2-350 KCMIL & 1#2 G) 2 1/2"C (3-350 KCMIL & 1#2 G) 3"C (4-350 KCMIL & 1#2 G) 3"C
600 2[(2-500 KCMIL & 1#2/0 G) 2 1/2"C] 2[(3-500 KCMIL & 1#2/0 G) 3"C] 2[(4-500 KCMIL & 1#2/0 G) 3 1/2"C]
CONDUCTOR SIZES ARE BASED ON 75° TERMINATIONS.
CONDUIT SIZES ARE BASED ON NEC TABLE 4 (RNC) AND TABLE 5 (THHN INSULATION).
WIRING SCHEDULE - COPPER
AMPS (2WG) (3WG) (4WG)
1Ø, 2 WIRE, GROUND 1Ø, 3 WIRE, GROUND OR 3Ø, 3 WIRE, GROUND 3Ø, 4 WIRE, GROUND
20 (2#12 & 1#12 G) 3/4"C (3#12 & 1#12 G) 3/4"C (4#12 & 1#12 G) 3/4"C
30 (2#10 & 1#10 G) 3/4"C (3#10 & 1#10 G) 3/4"C (4#10 & 1#10 G) 3/4"C
40 (2#8 & 1#10 G) 3/4"C (3#8 & 1#10 G) 3/4"C (4#8 & 1#10 G) 1"C
50 (2#6 & 1#10 G) 3/4"C (3#6 & 1#10 G) 1"C (4#6 & 1#10 G) 1"C
60 (2#4 & 1#10 G) 1"C (3#4 & 1#10 G) 1"C (4#4 & 1#10 G) 1 1/4"C
70 (2#4 & 1#8 G) 1"C (3#4 & 1#8 G) 1 1/4"C (4#4 & 1#8 G) 1 1/4"C
80 (2#2 & 1#8 G) 1"C (3#2 & 1#8 G) 1 1/4"C (4#2 & 1#8 G) 1 1/2"C
90 (2#2 & 1#8 G) 1"C (3#2 & 1#8 G) 1 1/4"C (4#2 & 1#8 G) 1 1/2"C
100 (2#1 & 1#8 G) 1 1/4"C (3#1 & 1#8 G) 1 1/2"C (4#1 & 1#8 G) 1 1/2"C
110 (2#1 & 1#6 G) 1 1/4"C (3#1 & 1#6 G) 1 1/2"C (4#1 & 1#6 G) 1 1/2"C
CONDUCTOR SIZES ARE BASED ON 60° TERMINATIONS LESS THAN 100A AND 75° TERMINATIONS GREATER THAN 100A
CONDUIT SIZES ARE BASED ON NEC TABLE 4 (RNC) AND TABLE 5 (THHN INSULATION).150A(4WG)AL150A(4WG)AL600A(4WG)AL250A(4WG)AL70A(4WG)CU110A(4WG)CU110A(4WG)CU2000A(4W)ALUTILITY TRANSFORMER
ATS-E. 125A, 4-POLE
AUTOMATIC TRANSFER
SWITCH
ATS-S. 70A, 4-POLE
AUTOMATIC TRANSFER
SWITCH
110A/3PSEPARATELY ENCLOSED
CIRCUIT BREAKER WITH
SHUNT TRIP.
HD ST
1. HEAT DETECTOR ACTIVATION IN ELEVATOR SHAFT
OR AT ELEVATOR CONTROLLER LOCATION SHALL
ACTIVATE SHUNT TRIP TO SHUT DOWN ELEVATOR
POWER.
2. PUSH BUTTON TO ACTIVATE SHUNT TRIP CIRCUIT
BREAKER LOCATED ON EXTERIOR OF BUILDING.
REFER TO SHEET E-201 FOR LOCATION.
3. REFER TO 'UNIT LOAD CENTER SCHEDULE' ON THIS
SHEET FOR FEEDER SIZE.
4. REFER TO 'UNIT LOAD CENTER SCHEDULE' ON THIS
SHEET FOR SHORT-CIRCUIT RATING OF LOAD
CENTER.
5. FEEDER UPSIZED FOR VOLTAGE DROP.
FLAG NOTES:#
1
ST
2
70A(4WG)CU
3
3
UNIT LOAD CENTER
SCHEDULE
UNIT FEEDER SIZE AIC RATING OF
LOAD CENTER
101 125A(3WG)AL 10,000
102 125A(3WG)AL 10,000
103 125A(3WG)AL 10,000
104 125A(3WG)AL 10,000
105 125A(3WG)AL 10,000
106 125A(3WG)AL 10,000
107 125A(3WG)AL 10,000
108 125A(3WG)AL 22,000
109 125A(3WG)AL 22,000
110 125A(3WG)AL 10,000
111 125A(3WG)AL 10,000
112 125A(3WG)AL 10,000
113 125A(3WG)AL 10,000
114 125A(3WG)AL 10,000
201 125A(3WG)AL 10,000
202 200A(3WG)AL 10,000
203 125A(3WG)AL 10,000
204 125A(3WG)AL 10,000
205 125A(3WG)AL 10,000
206 125A(3WG)AL 10,000
207 125A(3WG)AL 10,000
208 125A(3WG)AL 10,000
209 125A(3WG)AL 10,000
210 125A(3WG)AL 22,000
211 125A(3WG)AL 22,000
212 125A(3WG)AL 10,000
213 125A(3WG)AL 10,000
214 125A(3WG)AL 10,000
215 125A(3WG)AL 10,000
216 125A(3WG)AL 10,000
217 125A(3WG)AL 10,000
301 125A(3WG)AL 22,000
302 125A(3WG)AL 10,000
303 125A(3WG)AL 10,000
304 125A(3WG)AL 10,000
305 125A(3WG)AL 10,000
306 125A(3WG)AL 22,000
307 125A(3WG)AL 22,000
308 125A(3WG)AL 22,000
309 125A(3WG)AL 22,000
310 125A(3WG)AL 10,000
311 125A(3WG)AL 22,000
312 200A(3WG)AL 22,000
313 125A(3WG)AL 10,000
314 200A(3WG)AL 10,000
315 125A(3WG)AL 10,000
316 200A(3WG)AL 10,000
317 200A(3WG)AL 22,000
401 125A(3WG)AL 22,000
402 125A(3WG)AL 10,000
403 125A(3WG)AL 10,000
404 200A(3WG)AL 22,000
405 125A(3WG)AL 10,000
406 125A(3WG)AL 22,000
407 125A(3WG)AL 22,000
408 125A(3WG)AL 22,000
409 125A(3WG)AL 22,000
410 125A(3WG)AL 10,000
411 125A(3WG)AL 10,000
412 200A(3WG)AL 10,000
413 200A(3WG)AL 10,000
414 200A(3WG)AL 10,000
415 200A(3WG)AL 10,000
416 225A(3WG)AL 10,000
417 225A(3WG)AL 10,000
SHORT CIRCUIT / VOLTAGE DROP CALCULATION SUMMARY
POINTTAG VOLTAGE /
PHASE
LENGTH
(FT)
COPPER /
ALUMINUM CONDUIT WIRE
SIZE
# OF
SETS
FEEDER
VOLTAGE
DROP (%)
TOTAL
VOLTAGE
DROP (%)
Isc
AVAILABLE
UPSTREAM
Isc (FAULT)
F1 SWB 208V, 3Ø 120 A N 500 7 0.8% 0.8% 99,500 59,794
F2 M1 208V, 3Ø 20 A S 3X 1 0.1% 1.0% 59,794 28,095
F3 P1 208V, 3Ø 20 A S 3X 1 0.2% 1.0% 59,794 28,095
F4 ATS-S 208V, 3Ø 20 C S 4 1 0.1% 0.9% 59,794 16,534
F5 L1 208V, 3Ø 30 C S 4 1 0.1% 1.0% 16,534 7,929
F6 ATS-E 208V, 3Ø 20 C S 1 1 0.1% 0.9% 59,794 25,276
F7 ELEV-1 208V, 3Ø 100 C S 1 1 0.6% 1.6% 25,276 6,504
F8 DP1 208V, 3Ø 20 A S 500 2 0.2% 1.0% 59,794 47,250
F9 UNIT 101 LC 208V, 1Ø 100 A S 2X 1 1.1% 2.1% 47,250 6,453
F10 UNIT 102 LC 208V, 1Ø 130 A S 2X 1 1.5% 2.5% 47,250 5,125
F11 UNIT 103 LC 208V, 1Ø 120 A S 2X 1 1.4% 2.3% 47,250 5,503
F12 UNIT 104 LC 208V, 1Ø 120 A S 2X 1 1.4% 2.3% 47,250 5,503
F13 UNIT 105 LC 208V, 1Ø 100 A S 2X 1 1.1% 2.1% 47,250 6,453
F14 UNIT 106 LC 208V, 1Ø 85 A S 2X 1 1.0% 2.0% 47,250 7,413
F15 UNIT 107 LC 208V, 1Ø 95 A S 2X 1 1.1% 2.1% 47,250 6,744
F16 UNIT 108 LC 208V, 1Ø 60 A S 2X 1 0.7% 1.7% 47,250 9,857
F17 UNIT 109 LC 208V, 1Ø 40 A S 2X 1 0.5% 1.5% 47,250 13,389
F18 UNIT 110 LC 208V, 1Ø 70 A S 2X 1 0.8% 1.8% 47,250 8,709
F19 UNIT 111 LC 208V, 1Ø 70 A S 2X 1 0.8% 1.8% 47,250 8,709
F20 UNIT 112 LC 208V, 1Ø 90 A S 2X 1 1.0% 2.0% 47,250 7,063
F21 UNIT 113 LC 208V, 1Ø 80 A S 2X 1 0.9% 1.9% 47,250 7,800
F22 UNIT 114 LC 208V, 1Ø 100 A S 2X 1 1.1% 2.1% 47,250 6,453
F23 UNIT 201 LC 208V, 1Ø 120 A S 2X 1 1.4% 2.3% 47,250 5,503
F24 UNIT 202 LC 208V, 1Ø 150 A S 250 1 0.9% 1.9% 47,250 7,135
F25 UNIT 203 LC 208V, 1Ø 120 A S 2X 1 1.4% 2.3% 47,250 5,503
F26 UNIT 204 LC 208V, 1Ø 130 A S 2X 1 1.5% 2.5% 47,250 5,125
F27 UNIT 205 LC 208V, 1Ø 110 A S 2X 1 1.2% 2.2% 47,250 5,940
F28 UNIT 206 LC 208V, 1Ø 90 A S 2X 1 1.0% 2.0% 47,250 7,063
F29 UNIT 207 LC 208V, 1Ø 100 A S 2X 1 1.1% 2.1% 47,250 6,453
F30 UNIT 208 LC 208V, 1Ø 75 A S 2X 1 0.8% 1.8% 47,250 8,229
F31 UNIT 209 LC 208V, 1Ø 80 A S 2X 1 0.9% 1.9% 47,250 7,800
F32 UNIT 210 LC 208V, 1Ø 60 A S 2X 1 0.7% 1.7% 47,250 9,857
F33 UNIT 211 LC 208V, 1Ø 55 A S 2X 1 0.6% 1.6% 47,250 10,553
F34 UNIT 212 LC 208V, 1Ø 80 A S 2X 1 0.9% 1.9% 47,250 7,800
F35 UNIT 213 LC 208V, 1Ø 75 A S 2X 1 0.8% 1.8% 47,250 8,229
F36 UNIT 214 LC 208V, 1Ø 95 A S 2X 1 1.1% 2.1% 47,250 6,744
F37 UNIT 215 LC 208V, 1Ø 90 A S 2X 1 1.0% 2.0% 47,250 7,063
F38 UNIT 216 LC 208V, 1Ø 110 A S 2X 1 1.2% 2.2% 47,250 5,940
F39 UNIT 217 LC 208V, 3Ø 110 A S 2X 1 1.2% 2.2% 47,250 6,728
F40 P3 208V, 3Ø 80 A S 350 1 0.3% 1.1% 59,794 16,737
F41 DP3 208V, 3Ø 80 A S 500 2 0.8% 1.6% 59,794 28,999
F42 UNIT 301 LC 208V, 1Ø 40 A S 2X 1 0.5% 2.0% 28,999 11,363
F43 UNIT 302 LC 208V, 1Ø 75 A S 2X 1 0.9% 2.4% 28,999 7,416
F44 UNIT 303 LC 208V, 1Ø 65 A S 2X 1 0.7% 2.3% 28,999 8,233
F45 UNIT 304 LC 208V, 1Ø 80 A S 2X 1 0.9% 2.5% 28,999 7,066
F46 UNIT 305 LC 208V, 1Ø 60 A S 2X 1 0.7% 2.2% 28,999 8,713
F47 UNIT 306 LC 208V, 1Ø 40 A S 2X 1 0.5% 2.0% 28,999 11,363
F48 UNIT 307 LC 208V, 1Ø 30 A S 2X 1 0.3% 1.9% 28,999 13,400
F49 UNIT 308 LC 208V, 1Ø 40 A S 2X 1 0.5% 2.0% 28,999 11,363
F50 UNIT 309 LC 208V, 1Ø 20 A S 2X 1 0.2% 1.8% 28,999 16,328
F51 UNIT 310 LC 208V, 1Ø 70 A S 2X 1 0.8% 2.4% 28,999 7,803
F52 UNIT 311 LC 208V, 1Ø 40 A S 2X 1 0.5% 2.0% 28,999 11,363
F53 UNIT 312 LC 208V, 1Ø 90 A S 250 1 0.6% 2.1% 28,999 9,445
F54 UNIT 313 LC 208V, 1Ø 60 A S 2X 1 0.7% 2.2% 28,999 8,713
F55 UNIT 314 LC 208V, 1Ø 105 A S 250 1 0.6% 2.2% 28,999 8,491
F56 UNIT 315 LC 208V, 1Ø 75 A S 2X 1 0.9% 2.4% 28,999 7,416
F57 UNIT 316 LC 208V, 1Ø 125 A S 250 1 0.8% 2.3% 28,999 7,483
F58 UNIT 317 LC 208V, 1Ø 95 A S 250 1 0.6% 2.1% 28,999 9,104
F59 UNIT 401 LC 208V, 1Ø 55 A S 2X 1 0.6% 2.2% 28,999 9,253
F60 UNIT 402 LC 208V, 1Ø 85 A S 2X 1 1.0% 2.5% 28,999 6,747
F61 UNIT 403 LC 208V, 1Ø 70 A S 2X 1 0.8% 2.4% 28,999 7,803
F62 UNIT 404 LC 208V, 1Ø 90 A S 250 1 0.6% 2.1% 28,999 9,445
F63 UNIT 405 LC 208V, 1Ø 70 A S 2X 1 0.8% 2.4% 28,999 7,803
F64 UNIT 406 LC 208V, 1Ø 50 A S 2X 1 0.6% 2.1% 28,999 9,863
F65 UNIT 407 LC 208V, 1Ø 40 A S 2X 1 0.5% 2.0% 28,999 11,363
F66 UNIT 408 LC 208V, 1Ø 50 A S 2X 1 0.6% 2.1% 28,999 9,863
F67 UNIT 409 LC 208V, 1Ø 30 A S 2X 1 0.3% 1.9% 28,999 13,400
F68 UNIT 410 LC 208V, 1Ø 80 A S 2X 1 0.9% 2.5% 28,999 7,066
F69 UNIT 411 LC 208V, 1Ø 70 A S 2X 1 0.8% 2.4% 28,999 7,803
F70 UNIT 412 LC 208V, 1Ø 100 A S 250 1 0.6% 2.2% 28,999 8,787
F71 UNIT 413 LC 208V, 1Ø 100 A S 250 1 0.6% 2.2% 28,999 8,787
F72 UNIT 414 LC 208V, 1Ø 115 A S 250 1 0.7% 2.3% 28,999 7,955
F73 UNIT 415 LC 208V, 1Ø 120 A S 250 1 0.7% 2.3% 28,999 7,712
F74 UNIT 416 LC 208V, 1Ø 135 A S 250 1 0.8% 2.4% 28,999 7,064
F75 UNIT 417 LC 208V, 1Ø 140 A S 250 1 0.9% 2.4% 28,999 6,871
** FOR DESIGN PURPOSES, A 500KVA UTILITY TRANSFORMER WITH A MAXIMUM AVAILABLE (SYMMETRICAL) FALUT AT THE SECONDARY OF 99,500 AMPS
HAS BEEN ASSUMED. ACTUAL TRANSFORMER AND FAULT CURRENT INFORMATION SHALL BE PROVIDED TO THE ELECTRICAL ENGINEER, PRIOR TO
PURCHASING ANY ELECTRICAL EQUIPMENT, TO ALLOW VERIFICATION OF THESE CALCULATIONS. SHORT CIRCUIT CALCULATIONS ARE FURNISHED FOR
ALL FAULT LEVELS ABOVE 10,000 AMPS @ 208 VOLT. ANY FAULT CURRENT BELOW THIS LEVEL IS CONSIDERED SAFE FOR THE ELECTRICAL SYSTEM TO
CLEAR OR EQUIPMENT IS BUILT TO WITHSTAND THIS LEVEL OF FAULT SAFELY.
F1
F2 F3
F37
F36
F5
F4 F6
F7
4
4
4
4
4
'DP1' 600A(4WG)ALF8
70A(4WG)CU
#1/0 CU GROUNDING
ELECTRODE CONDUCTORS.
BLDG. STEEL I.A.W.
N.E.C. 250-52(A)(2)
WATER SERVICE I.A.W.
N.E.C. 250-52(A)(1)
20 L.F. OF #4CU
ENCASED IN MIN. 2"
OF CONCRETE. I.A.W.
N.E.C. 250-52(A)(3)
N
G
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-400
ELECTRICAL
DIAGRAMS
09/21/18
GUTTERMELT CONTROL DIAGRAM
NO SCALE
120 VOLT
N
H
PANEL
ICESTOP CABLE
ICESTOP CABLE
ICESTOP CABLE
CONTACTOR
30-mA GFCI CIRCUIT BREAKERS.
GUTTERMELT TEMPERATURE
SENSOR TO LOCK-OUT
GUTTERMELT ABOVE 40°F (ADJ.)
OR (MOISTURE/TEMPERATURE
SENSOR).
EXTERIOR LIGHTING CONTROL DIAGRAM
NO SCALE
120V
TC
TO EXTERIOR LIGHTS
PC
PHOTOCELL (WPS-5527K)
MOUNTED ON ROOF
FACING NORTH.
DOUGLAS LIGHTING
CONTROL PANEL
#WPAK-33518-S
TYPICAL
SYSTEM
CLOCK
NO SCALE
TYPICAL DEVICE ALIGNMENT
EQ EQ
6"MIN.
℄
℄
℄
DOOR WINDOW
EQ EQ
℄LIGHTING
CONTROL
℄
℄
OFFSET COMMUNICATIONS
DEVICES FROM POWER
DEVICES TO EITHER
OPPOSITE SIDE OF STUD BAY,
OR ADJACENT STUD BAY.
NOTES:
1. IF ALIGNMENT OF DEVICES INDICATED HERE IS IN CONFLICT
WITH ADA REQUIREMENTS DUE TO INSTALLATION DETAIL, ADA
DIMENSIONS SHALL GOVERN.
2. REFERENCE ARCHITECTURAL INTERIOR ELEVATIONS.
LOCATIONS SHOWN ON INTERIOR ELEVATIONS SHALL
SUPERCEDE LOCATIONS SHOWN HERE, UNLESS LOCATIONS
SHOWN ON INTERIOR ELEVATIONS ARE NOT CODE COMPLIANT.
EQ
BACKSPLASH
ABOVE
COUNTER
DEVICE
RECEPTACLE
COUNTERTOP
EQ
FINISHED FLOOR
FINISHED CEILING
6"
MIN.
20"
MAX.
ALIGN DEVICES (OUTLETS,
CONTROLS, ETC.)
VERTICALLY. DO NOT
VERTICALLY ALIGN POWER
AND COMMUNICATIONS
DEVICES SIMULTANEOUSLY.
18"
48"64"
78"
90"
78"
64"
90"
6"MIN
FIRE ALARM DEVICES
48"
ELECTRICAL DEVICES
96"
NOTES:
1. IF MOUNTING HEIGHT OF DEVICES INDICATED HERE IS IN
CONFLICT WITH ADA REQUIREMENTS DUE TO INSTALLATION
DETAIL, ADA DIMENSIONS SHALL GOVERN.
2. REFERENCE ARCHITECTURAL INTERIOR ELEVATIONS.
LOCATIONS SHOWN ON INTERIOR ELEVATIONS SHALL
SUPERCEDE LOCATIONS SHOWN HERE, UNLESS LOCATIONS
SHOWN ON INTERIOR ELEVATIONS ARE NOT CODE
COMPLIANT.
WALL-MOUNT
NO SCALE
TYPICAL DEVICE MOUNTING HEIGHTS
OC
DLV S
CBC
TS TC
ANN
FACP
SH
SH
F
120"
MAX.
80"
MIN.
96"
MAX.
TOP OF DEVICE
9'-0"+ CEILING
8'-0" CEILING
TOP OF CABINET
TOP OF CABINET
TOP OF DEVICE
CL OF DEVICE
TOP OF DEVICE
TOP OF CABINET
TOP OF CABINET
BOTTOM OF DEVICE
MINIMUM, TOP OF DEVICE
FINISHED FLOOR
FINISHED CEILING
18"
TOP OF DEVICE
48"
MINIMUM, TOP OF DEVICE
BOTTOM OF DEVICE
TOP OF CABINET
TOP OF CABINET
90"
6"MIN.
96"
NOTES:
1. IF MOUNTING HEIGHT OF DEVICES INDICATED HERE IS IN
CONFLICT WITH ADA REQUIREMENTS DUE TO INSTALLATION
DETAIL, ADA DIMENSIONS SHALL GOVERN.
2. REFERENCE ARCHITECTURAL INTERIOR ELEVATIONS.
LOCATIONS SHOWN ON INTERIOR ELEVATIONS SHALL
SUPERCEDE LOCATIONS SHOWN HERE, UNLESS LOCATIONS
SHOWN ON INTERIOR ELEVATIONS ARE NOT CODE COMPLIANT.
TYPICAL DEVICE MOUNTING HEIGHTS
I
I
CR
FINISHED FLOOR
48"
84"
FINISHED CEILING
90"
78"
64"
24"
NO SCALE
I
WALL-MTDCABINET
CPUAPS ACP
K C VCT CK
MAV TV
S ANN
FACP
SH
SH
F
80"
MIN.
96"
MAX.
120"
MAX.
CL OF DEVICE
CL OF DEVICE
TOP OF DEVICE
TOP OF CABINET
8'-0" CEILING
9'-0"+ CEILING
CL OF DEVICE
LOW VOLTAGE DEVICES FIRE ALARM DEVICES
A
B
ICESTOP CABLE
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-401
ELECTRICAL
DIAGRAMS
09/21/18
1. 3/4" PLYWOOD - 'AC' GRADE. COAT WITH FIRE
RETARDANT PAINT. 'A' SIDE SHALL FACE INTERIOR OF
ROOM.
2. LADDER-STYLE CABLE RUNWAY - 12" WIDE. PROVIDE
CHATSWORTH PRODUCTS OR EQUAL.
3. PRIMARY BONDING BUSBAR (PBB). PROVIDE 12"X4"
BUSBAR BY HARGER, CHATSWORTH, OR EQUAL.
4. (3) 4" C. FROM SERVICE PROVIDER PEDESTAL,
ROUTED THROUGH THE GARAGE. RE: ELECTRICAL
SITE PLAN/E-100. EXTEND CONDUIT 3" INTO ER/MDF.
PROVIDE FIRESTOPPING AS REQUIRED.
5. CATV AND VOICE/DATA DEMARC POINT.
6. 45U 4-POST EQUIPMENT RACK FRAME - FLOOR
MOUNT. PROVIDE CHATSWORTH OR EQUAL.
7. (3) 4" C. SLEEVES TO ABOVE ACCESSIBLE CEILING.
EXTEND SLEEVES 3" ON EITHER SIDE OF WALL
ASSEMBLY. PROVIDE FIRESTOPPING AS REQUIRED.
8. VERTICAL CABLE MANAGEMENT - 6" WIDE,
DOUBLE-SIDED. PROVIDE CHATSWORTH "VELOCITY"
OR EQUAL.
9. WALL MOUNT EQUIPMENT CABINET. PROVIDE
CHATSWORTH OR EQUAL.
10. 66-BLOCK PUNCH DOWN FOR PHONE SYSTEM.
FLAG NOTES:#
1. PROVIDE CONDUIT SLEEVES THROUGH WALLS TO
STRUCTURE TO FACILITATE CABLING. PROVIDE
FIRE-RATED PATHWAYS WHERE REQUIRED.
2. ALL LOW VOLTAGE CONDUIT STUBBED OUT ABOVE
FINISHED CEILINGS SHALL HAVE LONG RADIUS
SWEEPS.
3. CABLE TIES SHALL BE RELEASABLE AND COMPOSED
OF HOOK AND LOOP, RUBBER OR SOFT POLYMER.
ZIP-TIES OR EQUAL SHALL NOT BE USED.
4. ROUTE ALL CABLING NOT IN CONDUIT VIA J-HOOKS,
ARLINGTON LOOPS OR SLINGS SUSPENDED FROM
STRUCTURE. CABLING SHALL NOT RUN
UNSUPPORTED FOR LENGTHS GREATER THAN 5'-0".
5. ALL VOICE/DATA CABLING SHALL BE TERMINATED ON
RACK MOUNTED PATCH PANELS.
6. ALL INFRASTRUCTURE SUPPORTING VOICE/DATA
STRUCTURED CABLING SYSTEMS (RACKING,
GROUNDING, PATHWAYS, ETC.) SHALL MEET BICSI
STANDARDS.
7. ALL TELECOMMUNICATIONS CABLING SHALL BE
HOMERUN TO THE NEAREST SERVING TR/IDF.
NOTES:
6
3
4
1
2
7
SCALE:1 MDF ENLARGED PLAN
1/2" = 1'-0"
CABLE RUNWAY,
BOTTOM AT +90"AFF.
SCALE:2 MDF -RACK ELEVATIONS
1/2" = 1'-0"
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
VERTICAL CABLE MGMTFOUR-POST DIST RACK
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
VERTICAL CABLE MGMTFOUR-POST DIST RACKRESERVED FOR OWNER EQUIPMENT.VERTICAL CABLE MANAGER.
CHATSWORTH VELOCITY 6"
WIDE DOUBLE-SIDED,
TYPICAL.
HORIZONTAL
CABLE MGMT
8 , TYP.
2U HORIZONTAL CABLE
MANAGEMENT. PROVIDE
CHATSWORTH OR EQUAL.
TYPICAL.
5
48 PORT POE LAN SWITCH
10
2
E-402
48 PORT PATCH PANEL
48 PORT POE LAN SWITCH
48 PORT PATCH PANEL
HORIZONTAL
CABLE MGMT
48 PORT POE LAN SWITCH
48 PORT PATCH PANEL
48 PORT POE LAN SWITCH
48 PORT PATCH PANEL
HORIZONTAL
CABLE MGMT
DATA PATCHPANEL.
PROVIDE BLUE
CONNECTORS, TYPICAL.
CCTV CONNECTORS
SHALL BE GREEN.
UPS PROVIDED BY
OTHERS.
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-402
TECHNOLOGY
ENLARGED
PLANS
09/21/18
LEVEL 4
LEVEL 3
LEVEL 2
LEVEL 1
PARKING LEVEL
ER/MDF
2"C.
ROOF
SCALE:1 PATHWAYS
& SPACES RISER DIAGRAM
NOT TO SCALE
WEATHERHEAD TERMINATION
(FUTURE USE)
1. CABLING MAY BE ROUTED VIA CABLE TRAY,
J-HOOKS, ARLINGTON LOOPS OR EQUAL ABOVE
ACCESSIBLE CEILING.
2. PROVIDE LONG RADIUS SWEEPS (4X) ON ALL
COMMUNICATIONS CONDUIT PATHWAYS.
3. CABLING WITHIN RESIDENTIAL UNITS MAY BE
RUN "WILD" FROM STRUCTURED MEDIA
CABINET TO COMMUNICATIONS OUTLET BOX.
NOTES:
RESIDENTIAL UNIT
TYPICAL STRUCTURED
MEDIA CABINET.
RESIDENTIAL UNIT
RESIDENTIAL UNIT
RESIDENTIAL UNIT
4" CONDUIT SLEEVES, QTY. AS
REQUIRED, TYPICAL. PROVIDE
FIRESTOPPING AS REQUIRED
FOR FIRE RATED PARTITIONS.
TYPICAL.
LEVEL 2
LEVEL 1
PARKING LEVEL
ER/MDF
SCALE: 2 COMMUNICATIONS BONDING DIAGRAM
NOT TO SCALE
ACCESSIBLE CEILING
ACCESSIBLE CEILING
ACCESSIBLE CEILING
ACCESSIBLE CEILING
PBB
G
BOND TO BUILDING
STEEL, TYPICAL.
TELECOMMUNICATIONS
BONDING CONDUCTOR (TBC).
#2/0 AWG INSULATED COPPER.
BOND TO GROUNDING BUS IN
ELECTRICAL PANEL. FIELD
COORDINATE WORK WITH
ELECTRICAL CONTRACTOR.
DATA
PHONE
CATV
CABLETRAY, TYPICAL.
NETWORK RACK, TYPICAL.
BONDING NOTES:
1. ALL BONDING CONNECTIONS SHALL BE MADE WITH
HEAVY DUTY 2-HOLE COMPRESSION LUGS WITH
STAINLESS STEEL SCREWS AND LOCKING NUTS, TWO
SCREWS & NUTS PER LUG.
2. PROVIDE BONDING BUSBARS IN ALL COMMUNICATION
CLOSETS. BOND PRIMARY BUSBAR (PBB) TO BUILDING
MAIN ELECTRICAL SERVICE GROUND WITH #2/0 AWG
INSULATED STRANDED COPPER CONDUCTOR AND #2/0
BETWEEN BUSBARS. BONDING TO BUILDING
STRUCTURE, CONDUITS, UTILITY PIPING, OR
ELECTRICAL SUB-PANELS IN LIEU OF BONDING TO
BUILDING MAIN ELECTRICAL SERVICE GROUND IS NOT
ACCEPTABLE.
3. BONDING CONDUCTOR BETWEEN PBB AND END
BUSBAR SHALL BE CONTINUOUS. PROVIDE C-TYPE
COMPRESSION TAPS TO FEED INTERMEDIATE
BUSBARS.
4. BOND EACH CONDUIT IN ALL COMMUNICATIONS
ROOMS WITH #6 AWG INSULATED STRANDED COPPER
BONDING CONDUCTOR TO BONDING BUSBAR. ROUTE
CONDUCTOR IN CABLE RUNWAY TO BONDING BUSBAR.
5. BOND CABLE TRAY AND RUNWAY WITH #6 AWG
INSULATED STRANDED COPPER BONDING
CONDUCTOR TO BONDING BUSBAR.
TWO-HOLE COMPRESSION
LUGS, TYPICAL.FRONT ELEVATION
#6 AWG INSULATED BONDING
COND. TO COMM. EQUIP.
MOUNTING BRACKET,
TYPICAL.
BONDING BUSBAR,
TYPICAL.
INSULATOR, TYPICAL.
#2/0 AWG INSULATED
BONDING COND. FROM TBB.
PLAN SYMBOL:
CONNECT TO:
· CABLE RUNWAY AND CABLE TRAY
· BUILDING STEEL OR CONDUIT RISER
· EACH DATA RACK
#6 AWG,
TYPICAL.
TO TELECOMMUNICATIONS
BONDING BACKBONE (TBB).
TO TELECOMMUNICATIONS
BONDING CONDUCTOR (TBC).4"VARIES: 12" - 20"
CONNECT TO:
· CABLE RUNWAY AND CABLE TRAY
· BUILDING STEEL OR CONDUIT RISER
· EACH DATA RACK
· PARALLEL END-OF-LINE SBB
(BACKBONE BONDING CONDUCTOR)
#6 AWG,
TYPICAL.
TO TELECOMMUNICATIONS
BONDING BACKBONE (TBB). 2"12"
#2/0
#2/0
#2/0
TYPICAL SBB
TYPICAL PBB
SCALE: 3 COMMUNICATIONS BONDING BUSBAR DIAGRAM
NOT TO SCALE
TO COMM. SERVICE
PROVIDER PEDESTALS.
TO CATV SERVICE
PROVIDER PEDESTAL.
(2) 4"C.
(1) 4"C. 1"C., TYPICAL.
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-500
TECHNOLOGY
RISER
DIAGRAMS
09/21/18
SCALE: 1 COMMUNICATIONS RISER DIAGRAM
NOT TO SCALE
PHONE
DATA
MCC
NETWORKING EQUIPMENT
BY OWNER (TYPICAL).
TO SERVICE
PROVIDER
PEDESTAL.
ER/MDF
SERVICE PROVIDER
DEMARCATION POINT.
RACK MOUNT 48-PORT RJ45
PATCH PANEL, TYPICAL.
TERMINATE 568B.
TERMINATE HORIZONTAL
CABLING ON APPROPRIATE
PATCH PANEL.
25PR CAT5E UTP
BY CONTRACTOR.
12STR SMOF BY
CONTRACTOR.
CAT6
CAT6
TYPICAL
VOICE/DATA
OUTLETS.
1. ALL ANALOG VOICE OUTLETS SHALL BE SERVED
FROM THE ER/MDF.
NOTES:
SCALE: 2 CATV RISER DIAGRAM
NOT TO SCALE
TO SERVICE
PROVIDER
PEDESTAL.
ER/MDF
SERVICE PROVIDER
DEMARCATION POINT.
CATV
TYPICAL RESIDENTIAL UNIT
CAT6 TYPICAL
UNIT DATA
OUTLETS.4PR CAT6
4PR CAT6
TYPICAL RESIDENTIAL UNIT
TYPICAL
UNIT TV
OUTLETS.
TV
TV
RG6/U
RG6/U
RG6/U
PROVIDE 75 OHM
TERMINATION FOR
UNUSED PORTS.
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
E-501
TECHNOLOGY
RISER
DIAGRAMS
09/21/18
COMMUNICATIONS OUTLET BOX DIAGRAM
THREADED NIPPLE WITH
PROTECTIVE BUSHING.
COMMUNICATIONS CABLING.
CONDUIT PATHWAY, UP OR
DOWN FROM OUTLET BOX.
SINGLE DEVICE MUD-RING.
LARGE CAPACITY OUTLET BOX;
HUBBELL HBL260 OR EQUAL.
4-11/16" x 4-11/16" x 3-1/4",
TYPICAL UNO.
NO SCALE
DOUBLE DATA OUTLET DIAGRAM
COR
MODULAR CAT6 CONNECTOR
(BLUE). TERMINATE T568B.
BLANK MODULAR INSERT,
MATCH FACEPLATE COLOR.
3-PORT MODULAR COMMUNICATIONS
FACEPLATE, COLOR TO MATCH
RECEPTACLES.
(2) 4PRCAT6 UTP
CABLE(BLUE
JACKET).
PLAN SYMBOL:NO SCALE
OUTLET LABEL
OUTLET LABEL
NOTES:
1. PROVIDE LEVEL 1 ADMINISTRATION
PER ANSI/TIA/EIA-606.
2. PROVIDE LABEL ON FRONT OF
FACEPLATE.
1" C.
WALL PHONE OUTLET DIAGRAM
NOTES:
1. PROVIDE LEVEL 1 ADMINISTRATION
PER ANSI/TIA/EIA-606.
2. PROVIDE LABEL ON FRONT OF
FACEPLATE.
W
CAT3 CONNECTOR (BLUE).
TERMINATE T568B.
STAINLESS STEEL WALL PHONE
MOUNT PLATE, WITH RECESSED
JACK PORT.
PLAN SYMBOL:NO SCALE
4PR CAT3 UTP CABLE
(BLUE JACKET).
1" C.
WIRELESS ACCESS POINT OUTLET DIAGRAM
PLAN SYMBOL:NO SCALE
SURFACE MOUNT "BISCUIT"
JACK W/ (1) CAT6 JACK.4PR CAT6A UTP CABLING
(BLUE ). ROUTE TO
SERVING IDF.
STRUCTURE.
WAP #1
J-HOOK OR EQUAL.
PROVIDE 15'-0" CABLE COILED
FOR FIELD-ADJUSTMENT OF
OUTLET LOCATION.
ACCESS POINTS AND PATCH
CABLES OWNER PROVIDED.
ACCESSIBLE CEILING.12"T568B STANDARD
8-POSITION / 8-CONDUCTOR DEVICE WIRING DIAGRAM
1
1
PAIR 2
PAIR 2
4
5
1
2
PIN
MODULAR CONNECTOR PINOUTS
87 6 4 5 3 2
7 2 3 5 4 6
PAIR 1
PAIR 3
PAIR 3
PAIR 1
8
PAIR 4
PAIR 4
2
3
4
1
PAIR COLOR CODE
2
3
4
1
3
6
7
8
BLUE
WHITE/BLUE
WHITE/ORANGE
ORANGE
WHITE/GREEN
GREEN
WHITE/BROWN
BROWN
NO SCALE
1 002
1 003
1 001
1 001
SEQUENTIALLY NUMBERED
PORT IDENTIFIER
TYPICAL OUTLET & CABLING LABELING CONVENTION
NO SCALE
JACK 'A' PORT #
JACK 'C' PORT #
JACK 'B' PORT #
NOTES:
1. ALL LABELS SHALL BE MACHINE
PRINTED.
2. LABELING CONVENTION APPLIES TO
BOTH FACEPLATE AND CABLING.
3. PROVIDE COLOR CODED JACK FOR
INTENDED USE.
0001
TYPICAL PATCH PANEL LABELING CONVENTION
NO SCALE
NOTES:
1. ALL LABELS SHALL BE MACHINE
PRINTED.
2. LABELING CONVENTION APPLIES TO
BOTH PATCH PANEL AND HORIZONTAL
CABLING.
3. MULTIPLE PATCHPANELS CONTINUE
SEQUENTIALLY NUMBERED PORT
IDENTIFIER, I.E. PORT 1 ON SECOND
PATCHPANEL WILL BE IDENTIFIED AS
'0049', ETC.
RACK MOUNT 48-PORT
RJ-45 (8P8C) PATCH
PANEL.
PORT
IDENTIFIER.
1 2 3 4 5 6
25 26 27 28 29 30
A
B
C
JACK IDENTIFIER
1 001
SEQUENTIALLY NUMBERED
PORT IDENTIFIER
0002 0003 0004 0005 0006
0025 0026 0027 0028 0029 0030
BUILDING LEVEL
IDENTIFIER:
0 - BASEMENT
1 - 1ST FLOOR
ETC.
BUILDING LEVEL
IDENTIFIER:
0 - BASEMENT
1 - 1ST FLOOR
ETC.
HORIZONTAL CABLE LABELING CONVENTION
NO SCALE
NOTES:
1. ALL LABELS SHALL BE MACHINE PRINTED
AND SHALL WRAP COMPLETELY AROUND
CABLE.
2. LABELING SHALL BE PAPER WITH
THERMOPLASTIC WRAP.
PATCH
PANEL.
4PR UTP CABLE.
6" MAX.
8P8C RJ-45
CONNECTOR.
1 001
WALLPLATE
OR BISCUIT
OUTLET.
4PR UTP CABLE.
6" MAX.
8P8C RJ-45
CONNECTOR.
1 001
BUILDING LEVEL
IDENTIFIER:
0 - BASEMENT
1 - 1ST FLOOR
ETC.
SEQUENTIALLY NUMBERED
PORT IDENTIFIER
1 001
1 001
BUILDING LEVEL
IDENTIFIER:
0 - BASEMENT
1 - 1ST FLOOR
ETC.
SEQUENTIALLY NUMBERED
PORT IDENTIFIER
TYPICAL PATCH CABLE LABELING CONVENTION
NO SCALE
NOTES:
1. ALL LABELS SHALL BE MACHINE PRINTED
AND SHALL WRAP COMPLETELY AROUND
CABLE.
2. LABELING SHALL BE PAPER WITH
THERMOPLASTIC WRAP.
01 001 TO PATCH
PANEL.
TO LAN
SWITCH.
4PR UTP
CABLE.
8P8C RJ-45
CONNECTOR.
6" MAX.
6" MAX.
LAN SWITCH # PORT #
01 001
001
SEQUENTIALLY NUMBERED
PATCH PANEL PORT
IDENTIFIER
001
8P8C RJ-45
CONNECTOR.
1 001
A
B
JACK 'A' PORT #
JACK 'B' PORT #
JACK IDENTIFIER
2-PORT SURFACE
MOUNT BISCUIT
JACK.
TYPICAL BISCUIT JACK LABELING CONVENTION
NO SCALE
NOTES:
1. ALL LABELS SHALL BE MACHINE
PRINTED.
2. LABELING CONVENTION APPLIES TO
BOTH FACEPLATE AND CABLING.
3. PROVIDE COLOR CODED JACK FOR
INTENDED USE.
1 001
SEQUENTIALLY NUMBERED
PORT IDENTIFIER
BUILDING LEVEL
IDENTIFIER:
0 - BASEMENT
1 - 1ST FLOOR
ETC.
4PR UTP CABLE.
OUTLET PATHWAY DIAGRAM - DRYWALL PARTITION
OUTLET ASSEMBLY.
CONDUIT STUBBED ABOVE
ACCESSIBLE CEILING.
6" RADIUS MINIMUM
CONDUIT SWEEP.
FINISHED FLOOR.
WALL SURFACE (GYP BD).
ACCESSIBLE CEILING.
PROVIDE INSULATED BUSHING
ON END OF CONDUIT.
ADHERE TO ONE OF THE FOLLOWING
METHODS FOR ROUTING CONDUIT FROM
OUTLET:
1. STUB INTO SPACE ABOVE
ACCESSIBLE CEILING;
2. ROUTE TO NEAREST ARLINGTON
LOOP PATHWAY;
3. ROUTE TO SERVING IDF/MDF.
NO SCALE
FIRE-RATED PATHWAY DIAGRAM
NO SCALE
FIRE-RATED
PARTITION.
FIRE-RATED PATHWAY
BY HILTI OR STI.
HORIZONTAL
CABLING.
J-HOOK, ARLINGTON
LOOP OR CABLE TRAY.
12"12"
FINISHED CEILING.
A
B
C
D
E
F
G
H
J
K
L
M
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
TECHNOLOGY
DIAGRAMS
E-600
09/21/18
RF DISTRIBUTION MODULE /
SPLITTER, BY OTHERS.
AC DUAL POWER MODULE.
(LEVITON 47605-DP)
NETGEAR GS-105PE PoE-POWERED
5-PORT SWITCH (10/100/1000 OR
EQUIVALENT. PROVIDE LEVITON
MOUNTING BRACKETS FOR
INSTALLATION INTO MEDIA CABINET.
STRUCTURED MEDIA CENTER, INCLUDE
FLUSH MOUNT COVER.
(LEVITON 47605-28W) OR EQUIVALENT.
12-PORT CATEGORY 6 STRUCTURED
MEDIA PANEL, FOR VOICE/DATA.
(LEVITON 476TM-612)
STRUCTURED MEDIA CABINET ELEVATION
PLAN SYMBOL:
1"C FROM SERVING
TELECOM ROOM/IDF.
CEILING SURFACE MOUNT CAMERA DIAGRAM
3/4"C. HOMERUN TO
NEAREST CABLETRAY
OR TELECOM ROOM.
4PR CAT6 UTP CABLE (YELLOW).
TERMINATE WITH MALE 8P8C PLUG.
PROVIDE 36" SLACK COILED AT
PATCHPANEL.
HOMERUN TO CCTV
PATCHPANEL IN
SERVING IDF.
CAMERA BACKBOX.
FINISHED SURFACE.
CAMERA.
PLAN SYMBOL:NO SCALE
A
B
Sheet Number
Date:VAIL, COLORADO953 S. Frontage Rd. West
Vail, Colorado 81657
tel: 970.476.1147
gpslarchitects.com
SOLAR VAIL501 NORTH FRONTAGE ROAD WESTLOT 8B, BLK 2, VAIL POTATO PATCH24 JUL. 2018
ALL SHEETS
VE PERMIT ISSUE
ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www ˛bgbuildingworks˛com
Project No. 9911.00 Copyright 2018
Sheet Title
TECHNOLOGY
DIAGRAMS
E-601
09/21/18