Loading...
HomeMy WebLinkAboutload calcs_24.pdf 5075 Ute Lane Existing Load Calculation 6/13/17: 3,330 sq.ft. @ 3VA 9,990 VA Kitchen appliance X 2 3,000 VA Dishwasher 1,200 VA Disposal 1,200 VA Refrigerator 1,200 VA Microwave 1,200 VA Range 10,000 VA Washer 1,500 VA Dryer 5,000 VA Steamer 12,000 VA General Load Sub-Total 46,290 VA 1" 10kVA @ 100% 10,000 VA Remainder @ 40% 14,516 VA Total Net General Load 24,516 VA Boiler and pumps @ 100% 1,500 VA Heat Tape @ 100% 3,000 VA Total 29,016 VA Calculated Load for Service 29,016 VA/240 volts = 121 Amps Existing service size 200Amps 1 5075 Ute Lane Proposed Load Calculation 6/13/17: 5605 sq.ft. @ 3VA 16,815 VA Kitchen appliance X 2 3,000 VA Dishwasher 1,200 VA Disposal 1,200 VA Refrigerator 1,200 VA Microwave 1,200 VA Range 10,000 VA Washer x 2 3,000 VA Dryer x2 10,000 VA Hot Tub 10,000 VA Steamer 12,000 VA General Load Sub-Total 69,615 VA 1st 10kVA @ 100% 10,000 VA Remainder @ 40% 23,846 VA Total Net General Load 33,846 VA Boiler and pumps @ 100% 3,000 VA Heat Tape @ 100% 6,000 VA Total 42,846 VA Calculated Load for Service 42,846 VA/ 240 volts= 179 Amps Existing service size 200Amps Owner would like a New 320Amp Service 1