HomeMy WebLinkAboutE18-0123 engineering report.pdf Office Copy Monroe & Newell Engineers,Inc. Vail • Denver September 6, 2018 Town of Vail Transportation Department 75 South Frontage Rd Vail, CO 81657 TSchollAvailgov.com Attn.: Mr. Todd Scholl Re: Town of Vail Police Department Generator Room Opening, Vail Municipal Building, Vail, Colorado (M&N #11311) Mr. Scholl, Monroe & Newell Engineers, Inc. has reviewed the existing structural drawings by Boyle Engineering, Inc. dated January 18, 2008 of the emergency generator room addition on the east side of the Vail Police Department Building. It is our understanding that the Town of Vail has to enlarge the existing 30"x30" louver opening on the east side of the generator room to 30" wide x 60" high for the installation of a new generator with a larger exhaust fan. Monroe and Newell Engineers, Inc. has determined that the proposed enlarged louver opening in the existing 8" CMU wall is structurally acceptable. The contractor shall follow the structural specifications and information in the attached General Notes and structural detail SX1 when increasing the size of the existing opening. In addition to the new opening the contractor will have to enlarge an existing louver opening to a width of 55 inches and a height of 70 inches. To accomplish this the bottom and one side of the existing opening can be cut out as shown in the attached section SX2. The contractor shall verify after cutting that wall reinforcement was not cut. After the new openings have been cut the contractor shall grout all cells that are located on all 4 sides of the new openings. www.monroe-newell.com 70 Benchmark Road • Suite 204 • P.O. Box 1597 • Avon, Colorado 81620 (970) 949-7768 • FAX (970) 949-4051 • email: avon@monroe-newell.com After installation of the new openings the east wall of the Generator Building will be in adequate structural state for the support of all structural wall loads per the requirements of the International Building Code, 2015 Edition. Please contact our office with any questions. Very truly yours, MONROE & NEWELL ENGINEERS, INC. sktu .\/ L.cFti��t►► ,.....,sem•���' 20 99 =: Hannes Spaeh, P.E; : G Principal 4 ?VI� Monroe 8 Newell Engineers,Inc.. 2 Project Town of Vail Generator Room September 6,2018 (M&N#11311) I PROJECT: VAIL PD GENERATOR ROOM M&N # 11311 DATE: 06-25-2018 GENERAL NOTES 1. LIVE LOADS USED IN DESIGN: A. ROOF 100 PSF B. TYPICAL FLOOR 125 PSF C. RISK CATEGORY II SEISMIC FACTOR IE 1.0 SNOW FACTOR Is 1.0 D. WIND WIND SPEED, Vuit 115 MPH (ULTIMATE) WIND SPEED, Vasd 90 MPH (ASD) EXPOSURE B E. LIVE LOADS ARE REDUCED PER CODE IF APPLICABLE. F. CODE USED IN DESIGN: INTERNATIONAL BUILDING CODE, 2015 EDITION. 2. TESTING, INSPECTIONS AND OBSERVATIONS: A. THE STRUCTURAL ENGINEER DOES NOT PROVIDE INSPECTIONS OF CONSTRUCTION. STRUCTURAL ENGINEER MAY MAKE PERIODIC OBSERVATIONS OF THE CONSTRUCTION; SUCH OBSERVATIONS SHALL NOT REPLACE REQUIRED INSPECTIONS BY THE GOVERNING AUTHORITIES OR SERVE AS"SPECIAL INSPECTIONS"AS MAY BE REQUIRED BY CHAPTER 17 OF THE INTERNATIONAL BUILDING CODE. 3. NON-STRUCTURAL ELEMENTS A. ELEMENTS SUCH AS NON-BEARING PARTITIONS, ETC.ATTACHED TO AND/OR SUPPORTED BY THE STRUCTURE SHALL TAKE INTO ACCOUNT DEFLECTIONS AND OTHER STRUCTURAL MOVEMENTS. B. FIRE PROTECTION FOR ALL STRUCTURAL PARTS SHALL BE PROVIDED AND SHALL MEET ALL CODE REQUIREMENTS FOR THE TYPE OF CONSTRUCTION SPECIFIED BY THE ARCHITECTURAL DRAWINGS. 4. GENERAL A. ENGINEER'S ACCEPTANCE MUST BE SECURED FOR ALL STRUCTURAL SUBSTITUTIONS. B. VERIFY ALL OPENINGS THROUGH FLOORS, ROOF AND WALLS WITH MECHANICAL AND ELECTRICAL CONTRACTORS. VERIFICATION OF LOCATIONS, SIZES, LINTELS AND REQUIRED CONNECTIONS ARE CONTRACTOR'S COMPLETE RESPONSIBILITY. C. PRIOR TO INSTALLATION OF MECHANICAL AND ELECTRICAL EQUIPMENT OR OTHER 1 ITEMS TO BE ATTACHED TO THE STRUCTURE, ENGINEER'S APPROVAL OF CONNECTIONS AND SUPPORTS SHALL BE OBTAINED. UNLESS SPECIFICALLY DETAILED ON ARCHITECTURAL AND STRUCTURAL DRAWINGS, RESPECTIVE SUBCONTRACTOR SHALL FURNISH ALL HANGERS, CONNECTIONS, ETC., REQUIRED FOR INSTALLATION OF HIS ITEMS. D. ALL DIMENSIONS ON STRUCTURAL DRAWINGS SHALL BE CHECKED AGAINST FIELD CONDITIONS AND ARCHITECTURAL DRAWINGS. E. CONTRACTOR SHALL VERIFY ALL ASSUMED EXISTING CONDITIONS. IF CONDITIONS ARE DIFFERENT THAN ASSUMED, NOTIFY ENGINEER. F. ALL HOUSEKEEPING PAD LOCATIONS AND EXTENTS SHALL BE COORDINATED WITH ARCHITECTURAL AND MECHANICAL DRAWINGS. 2 , 1 • . P • Jos Vt ACHECKED BY Monroe & Newell Engineers,Inc. ?D 6W\Wilki\111-' PIOLYIA 41-1 1 311 SHEET NO. CALCULATED BY Lls/j OF DATE -2-C-le DATE • SCALE . 1 . I I • 1 I . . 1 1 • :••• . I . I I . i I ! • 2 1 i i 1 I . : , 1. !. .1 3 ; i 1 • 1 . ;I I j 1 .• I ; 1 - I - - . . , i --1.-• . =- -4 I 1 • i I I I 1 I 1 ; ; • ; 1 3 1 ; I I 1 I I 1 I 1 I • • I i • . : I , 3 I ..1 j s i 1 ; ! 1 .4 ; i.-.• .. -. ., - : ,.1. I ; 1 .- I i 1 I 1 • 1- r s ' ! . 1 1 . . . I . , . I i I 1 . ! 1 I • i• I I! ; ; •1 :1••• :1 -II • i . : I : I . I I , , , : i i : , I i i • 1 . . ! 4 i •I-- . ii . 4 3 I . 3 1 . ; 1 • 1 . ; ; i -3- -4— i ' • 4- -' 1 __I 1 ;... r . = .4 i I t ; I 1. j — I . ! .1— si • ! . ; 1 t I• . .• .• 1 I 1 ! 1 I I 1 • 1 • • i i 1 i i l •" i . : / 1 r. ,. ...I.. . f. I 2 i i I i 1 i ! I : • . . i . i • : 1 I -1 • 1 , 1 , I : I . I : • • , 1 t , I , , , •i i 1 , I i I- 1 • 1. .4 , 1--• •••••!. 4 ---: 1.• , , ;-.4. —. ,'• i•-•'' ..! • --1-- i r 1 . . • ; ; ,, , 11 • t I s s .... , 1 ; : 1 1,00,,c17,14 eir. '; 0'11(' .. .D ILCOV Wt.,. 1 .. 1 ! t . . . , ; ! 4- 1 ; • ; 3 -3•• 4 • ! I ; ; 1 3• -; -; - • ; 1 ; : • 1 ; i I • 1 1 I ; 1. i • I • ! j t i ' j • . i I I , I : j 1 I • 2 z I ;.- . -.1-.. 4. l• 4 ,- - --- 1 -I -1 I 1 1 3 , ; ; 3 1 ; I : i 3 1 i 1 3 ; . 1 1 1 I 1 • 2 ; 2 i F- ; •-j— If "Ik 1 -1- 1 ; .,.. -1 I. , • I ....... .1 1...... 4. ,...... i.. _I._ ! --1- ..41.1.- 1 ; 1 • I : ! i 1 r 1 I i i . i I , , , • 1 , . I • ; t . I 1 I i i j 1 1.•- RA • . 4 •-•!-• 1 i• •L'•-•"'' -I--—1--- t• --r— --t I --I 1 ! . . . I . I . , . . . :• • . i ! ..1 : . . ; ..,.. ..... , I •I ! •4 I . .1•••• .. .1.. i : . 1!: I 1 1 1 !',I I , P • . ! ; i I . . I i• s , <---1-71 ' sel-ui ClUor Nttakb W6 I • . I i• :r . : : I • I . ' i ,: 1 j1 i I : i : . ,-.I I 0 I i I I ' I i , • . .I I i 1 K1 I —; 1 ' ; ..,,.. ' - . . . . s it is - I •= i I I i ; - I ! I .: i. 1--- ; i : 1 ; r i i ! I ; . t 1 Ciar--Namit.... Natatt2,-c : 3 ' I • 1. i : I • f-• ; ' 1 I ; ; ; , it, 1 1 , i • • , 1 1 1 0. , , Fti ' : wit:. in) ispho- c.4.4rro&- , , , 1 , , , ,...,,- , , 1 1 • .1 , . 1 . . 1 ! : 1 I i I 1 • I . i I ; I I ! I i I I I I I ; I I • . . • 1 I Noso 166„.4.106--• ._18 1..f" ocr- 1._ ; i I ; I ; ....i........ 1_0 r.. .4_ ..!...L. I...±. 1...... ..._ _ . ; - •• ,1 4 4_ . i. .4.. H.. .... i I I ; 1 I i i ! '7C1! tX I 601.414(17 0 WHAT-1 ! i . ! , 2 i t— • -----.1• * r. : : - ' *:, .- • . 1 . . . I I i : I I . ! S I ; I . , I . i. I j NIPeiC4- • : ; •- 1 ! . ..1... ,•• 1 ; . i .• ; . 1 i 1-a\AV14,--•I t'errsTlil ,. 1 ; : 1 , ; 4 ; s i s : ;- • i . . . : I ; : ! • . I : .4.; ! ...1 , ....i..._- .i.. .....r....1 ......f...._.i....-• • I. __.1... ......1___1.. I . 1..„,..... ; ...3.. ..4..... .......1( ...1. .....1.... I 1... .....1.... T._ ..I i 1 1 4 ! II - . . . i I : . .. . I I - I I . i i I . • - . . I . . - . . 1 I E i ! .4. i• , i• I ! i i . • I ; , r ,I i 1 • . 1 i , ! i I 1 I • 1 i i I I ! i [ I • 1 - , i • ! I -1-- ; : -.4 1- ,' , • Loiv WI_ Gee 604._ ilk.i, 1 , . . ! . 1 . : . , ___ i 1 _I 1 . I 1 LMLIV-L•61 el-) V .4 1240114 I : . t , . . I . q - !; 1 ; e •• 1 4 ,t 1 1.. II.. i 1 . 1 • H I ! • I— ..i. . ! ! 1 i ! r ; ! ! i 1 : . 1 ! 1 It • . . ! i I i 1 I f I I 1 1 .1 I • [ 1 i 1 • i I I 1 I 1 ! 2 i s : I 1 z z 1 i • 2 1 , • - 2 I ' _i_ 4 ; . ; •,. 2 ! 1 I I 1 2 i I 1 i 1 1 i - ! i 2 I I i i • I , i i ..... ....,.... __, 4 • -1--• ; i . -1-•- t 1 1 - -I I ; 1 . j s j I i i I ! . I ! I .••' nnnnein•mI I I t•:..0.01.....%riAL 4 111.1.1.11 % I ''V 4r4"* . II Monroe & Newell J°B �- Engineers, Inc. SHEET NO. OF �� CALCULATED BY ' DATE 1 /" I 1 CHECKED BY DATE SCALE • • • • • • • • 0 ''.;//::: 1 • , ..0e..., :.-- ,1,14 1 ., :, ., J. i. . . . . , , , . 1 Lc € � ►•: — `It 7 • f . .......... t .. �. ._. >.. .....::. .......... _.. .. .. ......... .. ... ... .a. .... ...... .. ............. .... • • Ga I_4 -.12_,* pal oR- • • to:2_4... , : ., :• . , _ • • R : ,................. , G . : . .. . I : : , : .• u . , PRODUCT „ , : .. .: : • i te2p. 514. 1 ., , , ,I , . .