HomeMy WebLinkAboutB18-0283_Approved Plans_1534542461.pdfA0.1
GRFA
CALCS
EXISTING PLANS
1
8" = 1'-0"2
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-92PROPOSED PLANS
18" = 1'-0"1
1,928.4 sf
1,555.6 sf
537.0 sf
TOTAL
3,484.0 sf
2,009.7 sf
1,719.5 sf
563.7 sf
TOTAL
3,729.2 sf
08/17/18
A1.1
MAIN LEVEL
PLANMAIN LEVEL
1
4" =1'-0"1
C 2018 GPS Designs LLCISSUE3 August 2018RELEASE
Permit - Rev AShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-92GARAGE
101
FAMILY RM
111
KITCHEN
109
DINING
108
HEARTH
107
LIVING
106
ENTRY
105
PANTRY
110
POWDER
104
3
4 BATH
103
MUD RM
102
CLO
EXTEND DECK 4'-6" OUT.
OPEN HOLE INSPECTION AT
EXCAVATION FOR NEW
FOOTER/FDN
REMOVE SMALL CORNER
GAS FIREPLACE
DASHED WALLS REPRESENT
EXISTING WALLS TO BE
REMOVED, COORDINATE WITH
STRUCTURAL POSTS TO REMAIN
UPON REMOVAL OF DRYWALL.
NEW STAIR AND MUD ROOM CONFIGURATION,
UPPER TWO RUNS OF STAIRS TO REMAIN. NEW
LOWER FLIGHT TO TIE INTO EXISTING LANDING.
NEW TREADS TO BE 101
2" DEEP (RISER TO RISER)
1(: 5,6(56 72 0$7&+ (;,67,1* 58"
+$1'5$,/ $%29( 126,1* ,) 2:1(5
ELECTS TO CHANGE BALUSTERSAND NEWELS,
SPACING SHALL NOT EXCEED 37
8" CLEAR.
NEW DIRECT VENT GAS
FIREPLACE.
42" MAJESTIC MARQUIS II
WOOD BURNING FIREPLACE
TO BE REMOVED
DECK
A3.1
1
A3.1
2
A3.0
1
A3.0
2
A3.3
2
A3.3
1
A3.2
2
A3.2
1
A3.1
1
A3.1
2
A3.0
1
A3.0
2
A3.3
2
A3.3
1
A3.2
2
A3.2
1
MECHANICAL
112
EXISTING MECHANICAL SYSTEMS TO
REMAIN, EXTEND CURRENT ZONES
TO INCLUDE ADDED SPACES
REMOVE OVERFRAMED STEP AND
TIE BACK TO OPENING AT ENTRY
NEW FLUSH BEAM TO BE PLACED
AT BEARING WALL BEING REMOVED
NEW WINDOWS TO MATCH WIDTH OF
EXISTING, RAISE SILL TO PROVIDE ADDITIONAL
PRIVACY FOR EXISTING HOT TUB.
DASHED WALS ARE EXISTING TO BE REMOVED
TMPRD
NEW DIRECT VENT GAS
FIREPLACE.
36" MAJESTIC MARQUIS II NEW WALLS AND CEILING AT
GARAGE TO LIVING SPACE MUST
BE PROVIDED WITH 5
8" TYPE X
DRYWALL
UP
NON-BEARING INTERIOR PARTITION WITH
POCKETING PRIVACY DOORS
TIED TO CEILING AT EITHER END RE: DTLS
TMPRD TMPRD TMPRD
A
08/17/18
A1.2
UPPER
LEVEL PLANMAIN LEVEL
1
4" =1'-0"1
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-92A3.1
1
A3.1
2
A3.0
1
A3.0
2
A3.3
2
A3.3
1
A3.2
2
A3.2
1
A3.1
1
A3.1
2
A3.0
1
A3.0
2
A3.3
2
A3.3
1
A3.2
2
A3.2
1
LANDING
201
MASTER BED
202
M BATH
203
BED 2
204
BATH
205
LAUNDRY
206
BATH
207
BATH
210
BED 4
209 BED 3
208
CLO
CLO
CLO
CLO
AREA OF ADDITION
MASTER SUITE EXPANDS AND
RECEIVES NEW ROOF AREA OVER
SNOW DAMMING AREA
AREA OF DORMER TO MATCH
EXISTING CONDITION TOWARD
FRONT OF HOUSE
RECONFIGURE ARCH TOP
WINDOWS
AREA OF DORMER TO MATCH
EXISTING CONDITION TOWARD
FRONT OF HOUSE
TMPRD
TMPRD
TMPRD
TMPRD
OPERABLE VELUX SKYLIGHT,
CURB MOUNTED
OPERABLE VELUX SKYLIGHT,
CURB MOUNTED
TUB LOCATION TO REMAIN, SINKS
AND VANITY TO SWITCH WALLS
DN
EXIST
UP
2R
UP
2R
EXIST.
08/17/18
A1.3
ROOF PLANMAIN LEVEL
1
4" =1'-0"1
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-92A3.1
1
A3.1
2
A3.0
1
A3.0
2
A3.3
2
A3.3
1
A3.2
2
A3.2
1
A3.1
1
A3.1
2
A3.0
1
A3.0
2
A3.3
2
A3.3
1
A3.2
2
A3.2
1
08/17/18
ISSUE6 July 2018RELEASEPermitShapiro Addition / RenovationStan and Carol Shapiro4425 Glenn Falls LaneVail CO 81657PROJECT4425 Glenn Falls LanePROJECT NO.17_SR-0002gps designs, llc301 Boulder St, #333Minturn CO 81645EXISTING
ELEVATIONS
AREA THAT OWNERS SEE WATER
DAMAGE, TWO SLOPING ROOFS
CREATE DAMMING ISSUE.
ALL EXISTING CEDAR SHAKE ROOFING
TO BE REMOVED NAD REOLACED WITH
SYNTHETIC SHAKE, CLASS-A
EXISTING CHIMNEY TO BE REMOVED
A2.1
West Elevation
3/16" = 1'-0"1
North Elevation - river side
3/16" = 1'-0"2
East Elevation
3/16" =1'-0"4
Front Elevation - street side
3/16" = 1'-0"3
08/17/18
ISSUE3 August 2018RELEASEPermit - Rev AShapiro Addition / RenovationStan and Carol Shapiro4425 Glenn Falls LaneVail CO 81657PROJECT4425 Glenn Falls LanePROJECT NO.17_SR-0002gps designs, llc301 Boulder St, #333Minturn CO 81645PROPOSED
ELEVATIONS
G
BRIDGE VALLEY WITH SHALLOW ROOF
"DORMER". THIS ROOF IS ALMOST
IMPOSSIBLE TO ACTUALLY SEE WITH
HOME SITTING SO HIGH ON SOUTH
BANK OF CREEK
EGRESS
AREA OF ADDITION
AREA OF ADDITION
RETAIN EXISTING FENESTRATION PATTERN, REMOVE
REAR DECK AND ADD SHALLOW GUARD AT DOORS.
REDWOOD TO MATCH EXISTING DECK
NEW WINDOWS TO MATCH
EXISTING IN MATERIAL, STYLE
AND COLOR
MAINTAIN EXISTING RIDGE HEIGHT, RIDGE FALLS
UNDER MAXIMUM HEIGHT OF EXISTING ROOF.
NEW ROOF THROUGHOUT.
DAVINCI ROOF, SYNTHETIC SHAKE
BELLAFORTE "TAHOE"
RAISE SILL OF FRONT WINDOW TO
ALLOW FOR STAIR CLEARANCE BEHIND
SMALL BUMPOUTS AT WEST WALL FOR
NEW GAS FIREPLACES INSIDE,
STUCCO TO MATCH EXISTING.
CUSTOM, DECORATIVE FLUE CAPS
NEW WINDOWS, SYMMETRICALLY
FLANKING CHIMNEYS.
WINDOWS STYLE AND PAINT TO
MATCH EXISTING
NEW STUCCO SIDING
TO MATCH EXISTING,
TEXTURE AND COLOR.
NEW FASCIA AND SOFFIT TO
MATCH EXISTING, TEXTURE
AND COLOR.
EXISTING CHIMNEY TO BE REMOVED
G
X
EGRESS
XX
X
C
XX
X
X
X
XX X XFDD E
1 H H
TMPRD
EGRESS
TMPRD TMPRD
TMPRD
J
TMPRD
K
X
A A B B
TMPRD
A
A2.2
West Elevation
3/16" = 1'-0"1
North Elevation - river side
3/16" = 1'-0"2
East Elevation
3/16" =1'-0"4
Front Elevation - street side
3/16" = 1'-0"327'-4 1/4"REMAINS UNCHANGED27'-1/4"7'-0"3'-0"6'-1"7'-0"08/17/18
A3.0
BUILDING
SECTIONSMAIN LEVEL
3
16" = 1'-0"1
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-92MAIN LEVEL
3
16" = 1'-0"2
1
A3.2
2
A3.2
1
A3.3
2
A3.3
1
A3.2
2
A3.2
1
A3.3
2
A3.3
LANDING
201 BATH
207 BATH
210
MASTER BED
202
LAUNDRY
206 CLO CLO W/C BATH
205
GARAGE
101
LIVING
106 MUD RM
102
FAMILY RM
111
LIVING
106
PANTRY
110
AREAS OF HATCHING ARE
EXISTING CONSTRUCTION
AREAS OF HATCHING ARE
EXISTING CONSTRUCTION
EXISTING CHIMNEY TO BE REMOVED
LINE OF ROOF BEYOND
NEW DIRECT VENT GAS FIREPLACE,
42" MAJESTIC MARQUIS II
EXISTING CRAWL SPACE UNCHANGED
EXISTING CRAWL SPACE UNCHANGED
08/17/18
7'-118"A3.1
BUILDING
SECTIONSMAIN LEVEL
3
16" = 1'-0"1
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-92MAIN LEVEL
3
16" = 1'-0"2
1
A3.2
2
A3.2
1
A3.3
2
A3.3
1
A3.2
2
A3.2
1
A3.3
2
A3.3
MASTER BED
202
M BATH
203
BED 2
204 BATH
205
MASTER BED
202
M BATH
203
BED 2
204
BATH
205
FAMILY RM
111
KITCHEN
109
DINING
108
HEARTH
107
FAMILY RM
111
KITCHEN
109
DINING
108
HEARTH
107
AREAS OF HATCHING ARE
EXISTING CONSTRUCTION
AREAS OF HATCHING ARE
EXISTING CONSTRUCTION
NEW DORMER AT BATHROOM
NEW SHED ROOF AT
MASTER BATHROOM
NEW BEAM TO
CARRY RAFTERS
PROFILE OF ADDITION TO
MATCH EXISTING MASSING
NEW CRICKET AT WALL OF
NEW MASTER BATH
EXISTING CRAWL SPACE UNCHANGED
EXISTING CRAWL SPACE UNCHANGED
NEW CRAWL SPACE
CONNECT THROUGH TO EXISTING CRAWL
08/17/18
1114"6'-738"A3.2
BUILDING
SECTIONSMAIN LEVEL
3
16" = 1'-0"1
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-92MAIN LEVEL
3
16" = 1'-0"2
2
A3.0
1
A3.0
2
A3.1
1
A3.1
2
A3.0
1
A3.0
2
A3.1
1
A3.1
MASTER BED
202
LANDING
201
M BATH
203
DECK
DECK
HEARTH
107
LIVING
106
DINING
108
PANTRY
110
POWDER
104
ENTRY
105
AREAS OF HATCHING ARE
EXISTING CONSTRUCTION
AREAS OF HATCHING ARE
EXISTING CONSTRUCTION
EXISTING FIREPLACE ANDBUILT-IN TO BE REMOVED,
PROVIDE LOW WALL AND COLUMNS PER PLAN
EXISTING ROOF BEYOND
08/17/18
37'-0"7'-814"4'-0"MINA3.3
BUILDING
SECTIONSMAIN LEVEL
3
16" = 1'-0"1
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-92MAIN LEVEL
3
16" = 1'-0"2
A3.1
1
A3.1
2
A3.0
1
A3.0
2
A3.1
1
A3.1
2
A3.0
1
A3.0
2
M BATH
203
CLO
LANDING
201
BED 2
204
BATH
210
BED 4
209CLO
GARAGE
101
FAMILY RM
111DECK
KITCHEN
109
MUD RM
102
MECH STAIR
AREAS OF HATCHING ARE
EXISTING CONSTRUCTION
AREAS OF NEW SHED
ROOF DORMER AND
MASTER SUITE REMODEL
AREAS OF HATCHING ARE
EXISTING CONSTRUCTION
NEW STEEL BENT AT
ADDITION, RE: STRUCT
08/17/18
ISSUE6 July 2018RELEASEPermitShapiro Addition / RenovationStan and Carol Shapiro4425 Glenn Falls LaneVail CO 81657PROJECT4425 Glenn Falls LanePROJECT NO.17_SR-0002gps designs, llc301 Boulder St, #333Minturn CO 81645PerspectivesA4.1
View from front
actually a large evergreen will block this view, but shows visual impact of addition2
View from northeast
taken approx. 12' above creek 1
Bird's eye from Northwest
impossible to see this angle, but provides clear view of water issue3
08/17/18
A5.1
BUILDING
DETAILS
Dormer Wall to Roof
1 12" = 1'-0"3
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-92Skylight Head Detail
1 12" = 1'-0"2
Stair Detail
1 12" = 1'-0" 1
Partition @ Family Room
1 12" = 1'-0" 5
Dormer Fascia
1 12" = 1'-0" 4
08/17/18
A5.2
WATER
PROTECTION
DETAILS
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-9208/17/18
A5.3
AIR
INFILTRATION
DETAILS
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-9208/17/18
A B C D E
2'-6"
F G
H I J
EGRESS2'-0"2'-0" 4'-6" 3'-2"
VERIFY EXISTING
OPENING AND
GLAZING SIZE3'-0"3'-0" 4'-0"3'-0" 1'-0"6'-0"4'-0" 6'-0"3'-0" 6'-0"6'-0"4'-0"9'-0"
VERIFY EXISTING
OPENING AND
GLAZING SIZE
VERIFY EXISTING
OPENING AND
GLAZING SIZE
4'-6" 3'-2"10"2'-3" 2'-0"3'-0"2'-4"6'-0"1'-6" K 6'-8"6'-0"
VERIFY TUB
CLEARANCE
PRIOR TO ORDER
VERIFY EXISTING
OPENING AND
GLAZING SIZE
TO MATCH
1 2 3
2'-0" 2'-10" 1'-2"
4 53'-0"2'-8" NOTE:
ALL EXISTING OPENINGS SHOULD BE
MEASURED AND VERIFIED PRIOR TO
ORDER, CONFIRM OPERATION.
EASED EDGE, RECESSED
FENESTRATION
STUCCO TO MATCH EXISTING
BASE MOULDING TO
MATCH EXISTING
SINGLE PANEL SOLID
CORE DOORS
PTD PLASTER VENEER
AT DRYWALL
CASING TO
MATCH EXISTING
Stucco edge to
match existing
caulk
int trim to
match existing
stucco to match
existing on stucco wrb
58" plywd
sheathing
Doors
all exterior doors shall be weatherstripped to limit leakage while
closed. thermal transfer characteristics of insulated doors shall be
determined per IECC
Exterior Doors:
-1 3 4" Solid Wood Doors w/ wood frame
-Double Glazed at lites.
-tempered Glazing
Interior Doors:
-2 panel Masonite, or sim.
-Privacy hardware on Bedroom and Bathroom Doors.
-Unit Entry, Mechanical, and Garage man-door to be 20 minute,
self-closing.
Windows
Glazing U-values to be .30 or less with a SHGC of .30 or less. these
chall be coordinated in accordance with IECC.
windows and SGD shall be double glazed woodl type with U-values
indicated
Windows:
Painted wood windows
Color TBD
Double Glazed - Low-e
Argon filled
Simulated Divided Lites
Tempered Glazing per Elvs.
Air Leakage
exterior joints at window & door frames, openings at walls and
foundations, areas between wall and roof panels, openings and
penetrations at utility services through walls, floors and roofs, and
any other openings in the building envelope shall be sealed,
caulked, gasketed or weatherstripped to limit air leakage.
seams shall be taped.
Insulation
new exterior walls to receive R-28 value spray insulation
new roof to receive total cumulative R-49 value insulation
IRC 612.3 Window Fall Prevention Devices
Mighton Products standard bend lock,
both sides
< 4" clr w/ locks engaged to meet ASTM F 2090
LOCATED AT WINDOWS LESS THAN 2' FROM
FLOOR AND OVER 6' TO GRADE
A8.1
SCHEDULESDOOR / WDW SCHED
14" = 1'-0"1 DOOR / WDW TRIM
12" = 1'-0" 2 DOOR / WDW TRIM
11
2" =1'-0"3
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-9208/17/18
B
EXISTING
INSULATION
TO REMAIN
EXISTING
INSULATION
TO REMAIN
EXISTING
INSULATION
TO REMAIN
EXISTING
INSULATION
TO REMAIN
EXISTING
INSULATION
TO REMAIN
EXISTING
INSULATION
TO REMAIN
R-49 - ATTIC INSULATION
EXISTING ATTIC
INSULATION
EXISTING ATTIC
INSULATION
R-49 - ATTIC INSULATION
AT NEW CONSTRUCTION
R-49 - ATTIC INSULATION
AT NEW CONSTRUCTION
R-28 - SPRAY
WALL INSULATION
AT NEW WALLS
EXISTING
INSULATION
TO REMAIN
EXISTING
INSULATION
TO REMAIN
EXISTING
INSULATION
TO REMAIN
EXISTING
INSULATION
TO REMAIN
R-28 - SPRAY
WALL INSULATION
AT NEW WALLS
R-28 - SPRAY
WALL INSULATION
AT NEW WALLS
R-28 - SPRAY
WALL INSULATION
AT NEW WALLS
PER RESCHECK TABLE BUILDING AND DUCTWORK
MUST UNDERGO LEAKAGE TESTING.
THIS PROJECT IS REQUIRED TO SUBMIT AT FINAL
INSPECTION A DUCT LEAKAGE TEST SHOWING A
PASSING RATING OF <=8 CFM PER 100 SQUARE FEET OF
CONDITIONED FLOOR AREA AT A PRESSURE OF 25
PASCAL. A WRITTEN REPORT OF THE RESULTS OF THE
TEST SHALL BE SIGNED BY THE PARTY CONDUCTING
THE TEST AND PROVIDED TO THE CODE OFFICIAL UPON
REQUEST.
SHOW THAT AIR HANDLERS HAVE MANUFACTURERS
DESIGNATION FOR LEAKAGE RATE OF <=2%.
HVAC LINE-SET PIPING SHALL BE INSULATED WITH
FOAM WRAP MIN R-3
THIS PROJECT IS REQUIRED TO SUBMIT AT FINAL
INSPECTION A WHOLE-BUILDING BLOWER DOOR TEST
SHOWING A PASSING RATING OF <=5 AIR CHANGES PER
HOUR AT A PRESSURE OF 50 PASCAL. A WRITTEN
REPORT OF THE RESULTS OF THE TEST SHALL BE
SIGNED BY THE PARTY CONDUCTING THE TEST AND
PROVIDED TO THE CODE OFFICIAL UPON REQUEST.
A9.1
THERMAL &
DIAGRAMS
PLAN DIAGRAMS
3
32"=1'-0"1
1
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-9208/17/18
0 20' 40'NORTH10'
C1.0
SITE
PLAN
1
APPROXIMATE
EDGE OF STREAM
(SNOW COVERED)
C 2018 GPS Designs LLCISSUE16 August 2018RELEASE
Permit - Rev BShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-92DECK ADDITION
AT REAR
HOUSE ADDITION
AT REAR
50' STREAM SETBACK FROM
CENTER OF STREAM
EXISTING DECK
EXISTING 2-STORY STONE
AND STUCCO HOME
4425 GLEN FALLS LANE
FOUND #5 REBAR WITH
1 1
4" PLASTIC CAP
STAMPED P.L.S. 26626
GLEN FALLS LANE ( 50' R.O.W. )
LOT 2 LOT 1 LOT 3
6( 6: FOUND #5 REBAR WITH
1 1
4" PLASTIC CAP
STAMPED P.L.S. 26626
(75' WITNESS CORNER)
GORE CREEK
LOT 9
LOT 5
PUBLIC PEDESTRIAN/
FISHERMAN'S EASEMENT
FOUND #5 REBAR WITH
1 14" PLASTIC CAP
STAMPED P.L.S. 26626
(75' WITNESS CORNER) 6: 1:
30' SETBACK
EXISTING DRIVE, SIDEWALK AND SITE
LANDSCAPING TO REMAIN UNCHANGED
EXTENT OF CHANGES TO FOOTPRINT,
GRADING REMAINS UNCHANGED, NO
LANDSCAPING IMPACTS
EASEMENT/RIVER
4,610.7sf
REAR YARD @ SLOPE
1,263.4sf
YARD -FRONT/ WEST
3,178.5sf
DECK 841.8sf
HOUSE
2,705.6sf
DRIVE AND WALK
1,110.4sf
YARD -FRONT/ EAST
1,311.5sf
TREES -18 PINE
-18 ASPEN
SITE COVERAGE ALLOWED 35.0%
PROVIDED 26.2%
calc with 10,330.7sf effective lot area
LOT 2
14,941.4sf
LANDSCAPED MIN REQUIRED 40.0%
PROVIDED 63.8%
core development incl. deck at 12.8%
effective lot area used in calc.
GRADING REMAINS UNCHANGED
NEW GROUNDCOVER LANDSCAPING
TO RETURN AREAS AFFECTED BACK
TO ORIGINAL
NO TREES TO BE REMOVED
REAR SETBACK FROM BUILDING AND
DECK BOTH TO REMAIN UNCHANGED
REAR ACCESS ON EAST SIDE OF
HOME
EXISTING HOMES RESTROOM
FACILITIES WILL BE UTILIZED BY
WORKERS
DEBRIS WILL BE HAULED AWAY IN
WHEELED TRAILER. 20 YARD
DUMPSTER MAY BE USED
SHORT-TERM FOR MAJOR PORTION
OF DEMOLTION
A
LIMIT OF DISTURBANCE ORANGE
SAFETY CONSTRUCTION FENCING
SEDIMENT FENCE AT ALL AREAS OF
EXCAVATION, NO IMPACT TO CREEK
LIMIT OF DISTURBANCE
CONSTRUCTION FENCING
STAKED SEDIMENT FENCE
B
B
08/17/18
CV1
COVER
Project:
PROJECT DATA
Stan and Carol Shapiro
(305) 666-7460
OWNER
SHEET INDEX
Cover Sheet
Site Plan
GRFA Analysis
Existing Plans
Main Level Plan
Upper Level Plan
Roof Plan
Existing Elevations
Proposed Elevations
Building Sections
Building Sections
Building Sections
Building Sections
Perspectives
Details
Water Protection Details
Air Infiltration Details
Door/Window Schedule
Thermal Information
Electrical Layout
CV
C1.0
A0.1
X1.0
A1.1
A1.2
A1.3
A2.1
A2.2
A3.0
A3.1
A3.2
A3.3
A4.1
A5.1
A5.2
A5.3
A8.1
A9.1
E1.1
SHAPIRO RESIDENCE
4425 Glen Falls Lane
EAST VAIL
Permit Rev A - Submittal
August 3, 2018
Total GRFA : existing - 3,484.0 sf ( plus 537.0 sf in garage )
allowed - 3,750.0 sf ( with additional 250sf )
proposed - 3,729.2 sf ( plus 563.7 sf in garage)
Building Height: unchanged
Zoning: SDD 27
underlying LD-MF
Lot Size: .342 AC ( 14,898 sf )
effective lot area (minus easement) 10,330.7sf
Lot Coverage: per underlying zone using effective lot area
allowed .350 ( 3,615.7 sf)
existing .251 ( 2,589.1 sf)
proposed .262 ( 2,705.6 sf)
Setbacks:
side 15' ( 15' 9" - unchanged )
rear 20' ( 68' 3" - unchanged )
Site:
Parcel 2101-123-13-002
FOREST GLEN Lot 2
Address 4425 Glen Falls Lane
Vail, Colorado 81657
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-92PROJECT LOCATION
ADDITION AND INTERIOR RE-FINISH WITH
RENOVATION, ELECTRICAL AND PLUMBING.
Applicable Code
2015 IRC - Appendix J
work area
total existing area - 4,021sf
272 sf new construction
651 sf renovation - Main level
833 sf renovation - Upper level
1,756 sf total work area - 43.6%
MUNICIPAL
2015 International Existing Building Code
all associated ICC codes
local amendments per Town Code
Code Enforced:
Low Density Multi-FamilyOccupancy:
V-B, exsitingConstruction Type:
Town of Vail
Community Development
75 South Frontage Road
Vail, Colorado 81657
[p] (970) 479-2138
Planning:
existing non-sprinklered, hard wired smoke detectorsFire:
R-3, 18.6 OLOccupant Load:
GPS Designs LLC
301 Boulder St, 333
Minturn, CO 81645
(970) 470-4945
gregs@gpsdesigns.com
Contact: Gregory Sparhawk, aia
CO lic 0401016519
ARCHITECT
Structural Design Solutions
PO Box 2494
Avon, CO 81620
(970) 949-7100
sdsjeff@vail.net
Contact: Jeffrey Leonardo
STRUCTURAL ENGINEER
A
SPECIAL INSPECTIONS
STEEL WELD AND STRUCTURAL BOLTS INSPECTIONREV Ax
x
x
x
08/17/18
AF
AF
AF
AF
AFWP
WP
WP
WP
WP
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
GFCI
SURFACE MOUNTED FIXTURE
WALL SCONCE FIXTURE
SWITCH, ELEC TO DETERMINE
POLES, OWNER TO
DETERMINE DIMMING
HARD WIRED INTER-CONNECTED SMOKE
DETECTOR WITH BATTERY BACK-UP
TAMPER RESISTANT RECEPTACLE
OUTLET - 220V
6 34" RECESSED "CAN"
FIXTURE OR SIM.
TV CONNECTION
GROUND FAULT CIRCUIT
INTERUPTER OUTLET
EXHAUST FAN / LIGHT
COMBO
INTER-CONNECTED
CO DETECTOR
PHONE JACK
RECESSED CEILING SPEAKER,
TIED TO MEDIA DOCK
CAT 6
DUPLEX FLOOR OUTLET
TOE KICK LIGHTING
LOCATE TIMER IN CAB.
AF
THERMOSTAT,
PROGRAMMABLE AT MAIN
ENERGY NOTE:
A MINIMUM OF 75% OF LAMPS TO BE OF
HIGH-EFFICACY LAMPS
HOOD MIN EFFICACY - 2.8cfm/watt
EXHAUST FAN MIN EFFICACY - 1.4cfm/watt
LUTRON BLUETOOTH REC
HOUSE LIGHT NOTE:
HOUSE LIGHT WILL BE SWITCHED WITH
MOTION AT THE GARAGE DOORS. LIGHT
SENSOR AT EXTERIOR SCONCES
ARC FAULT OUTLET
NOTE:
ALL BRANCH CIRCUITS FEEDING
ALL OUTLETS IN FAMILY ROOMS, DINING
ROOMS, LIVING ROOMS, DENS,
BEDROOMS, CLOSETS, HALLWAYS, AND
SIMILAR ROOMS OR AREAS. MUST BE
INSTALLED FIRST IN LINE.
E1.1
ELECTRIC
PLANS
ELECTRIC - Plans
n.t.s. 1
GENERAL ELECTRICAL SPECIFICATIONS:
1.1 SPECIAL N0TICE
A. EACH CONTRACTOR SHALL READ ALL RELEVANT DOCUMENTS, BECOME FAMILIAR WITH THE JOB, THE SCOPE OF WORK, TYPE OF GENERAL CONSTRUCTI0N,
ARCHITECTURAL, STRUCTURAL, MECHANICAL AND ELECTRICAL DRAWINGS AND THE SPECIFLCATI0NS. EACH CONTRACTOR SHALL ALSO FAMILIARIZE HIMSELF
WITH THE PURPOSE FOR WHICH THESE DRAWINGS HAVE BEEN PREPARED AND SHALL BECOME COGNIZANT OF ALL THE DETAILS INVOLVED.
B. THE TERM "CONTRACTOR" USED IN THIS SECTI0N OF SPECIFICATIONS SHALL MEAN THE CONTRACTOR WHOSE WORK IS COVERED BY THAT SECTION.
C. WHEN THE TERM "ENGINEER" IS USED IN THIS SECTI0N OF SPECIFICATO0N IT SHALL MEAN THE CONSULTING ELECTRICAL ENGINEER.
1.2 SCOPE OF WORK
A. THE WORK UNDER THIS SECTI0N OF THE SPECIFICATIONS SHALL INCLUDE ALL LABOR AND MATERIALS NOTED, REQUIRED OR NECESSARY FOR THE COMPLETE
ELECTRICAL INSTALLATION DESCRIBED HEREIN AND/OR ON THE DRAWINGS. ALL WORK SHALL BE COMPLETED TO THE ENTIRE SATISFACTION OF THE OWNER AND
ENGINEER.
B. THIS WORK INCLUDES, BUT IS NOT LIMITED TO THE FOLLOWING:
1. ELECTRIC SERVICE AND METERING HEREINAFTER SPECIFIED INCLUDING FEES, PERMITS AND PROVISIONS FOR METERING EQUIPMENT AS AGREED TO BY
OWNER AND CONTRACTOR.
2. COMPLETE SYSTEMS OF DISTRIBUTI0N AND UTILIZATION FOR LIGHT AND POWER (WITHIN THE JOB SITE)
3. EMPTY CONDUIT SYSTEM FOR TELEPHONES. POWER, COMMUNICATION, ETC.
4. LIGHTING FIXTURES AND LAMPS.
5. ROUGH-IN AND FINAL CONNECTIONS TO MECHANICAL EQUIPMENT.
6. ROUGH-IN AND FINAL CONNECTION TO CONTRACTOR'S AND OWNER'S FURNISHED EQUIPMENT.
1.3 ELECTRICAL SERVICE
A. THIS CONTRACTOR SHALL CONTACT THE LOCAL POWER COMPANY AND MAKE ALL ARRANGEMENTS, PAY ALL FEES, AND ACQUIRE ALL PERMITS AS
REQUIRED FOR THE INSTALLATION OF THE ELECTRICAL SERVICE AND SYSTEMS AS HEREINAFTER SPECIFIED.
B. THE LOCAL POWER COMPANY WILL MAKE ALL TERMINATION'S TO THE TRANSFORMERS. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL
SECONDARY ELECTRICAL SERVICE AS REQUIRED BY LOCAL UTILITY COMPANY.
C. THE ELECTRICAL CONTRACTOR SHALL ALSO MAKE ALL PROVISIONS WHICH MAY BE REQUIRED BY THE SERVICING UTILITY COMPANIES.
1.4 FEES AND PERMITS
A. EACH CONTRACTOR SHALL OBTAIN ALL PERMITS. INSPECTI0NS, AND APPROVALS APPLICABLE TO HIS TRADE, AS REQUIRED BY REGULATORY AUTHORITIES. ALL
FEES AND COSTS OF ANY NATURE WHATSOEVER INCIDENTAL TO THESE PERMITS, INSPECTI0NS AND APPROVALS SHALL BE ASSUMED AND PAID BY THE
CONTRACTOR, EXCEPT FOR METERS. THE OWNER WILL PAY FOR METERS AS REQUIRED. THE GENERAL BUILDING PERMIT WILL BE OBTAINED UNDER OTHER
SECTI0NS OF THE WORK AND THAT PORTI0N OF THE COSTS INVOLVED IN OBTAINING THIS PERMIT WILL BE PAID BY THE CONTRACTOR FOR THE ELECTRICAL
TRADE. THE PRO-RATED COSTS. IF ANY, OR UTILITIES SERVING THIS PROPERTY WILL BE PAID FOR BY THE OWNER AND SHALL NOT BE INCLUDED AS PART OF THIS
CONTRACT.
1.5 CODES AND STANDARDS
A. ALL MATERIALS AND WORKMANSHIP SHALL COMPLY WITH ALL APPLICABLE LOCAL, COUNTY. STATE AND NATI0NAL CODES, SPECIFLCATI0NS, ORDINANCES,
UTILITY COMPANY REGULATI0NS AND SPECIFIED INDUSTRY STANDARDS.
B. IN CASE OF DIFFERENT BETWEEN BUILDING CODES, SPECIFLCATI0NS, STATE LAWS, LOCAL ORDINANCES, INDUSTRY STANDARDS AND UTILITY COMPANY
REGULATIONS AND THE CONTRACT DOCUMENTS. THE MOST STRINGENT SHALL GOVERN. THE WORK INVOLVED WITH THESE DIFFERENCES SHALL BE PERFORMED
AT NO ADDITIONAL COST TO THE OWNER.
C. IN ADDITION TO THE ABOVE, IF THE FOLLOWING INDUSTRY STANDARDS AND CODES ARE MORE STRINGENT, THEY SHALL TAKE PRECEDENCE.
IEEE - INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS
IES - ILLUMINATING ENGINEERING SOCIETY
NEC - NATIONAL ELECTRIC CODE
NEMA - NATIONAL ELECTRIC MANUFACTURER'S ASSOCLATION
NFPA - NATIONAL FIRE PROTECTI0N ASSOCLATION
UL - UNDERWRITER'S LABORATORIES
D. ALL WORK SHALL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER. ANY WORK FOUND TO BE UNSATISFACTORY, BY THE ENGINEER, LOCAL
AUTHORITIES, OR OWNER, SHALL BE REMOVED AND REINSTALLED IMMEDIATELY AT NO ADDITIONAL COST.
E. ANY AND ALL INSTALLATION OF ELECTRICAL CONDUCTORS AND APPARATUS SHALL BE PERFORMED BY SKILLED AND PROPERLY LICENSED JOURNEYMEN. ANY
UNLICENSED PERSON FOUND PERFORMING SUCH WORK SHALL BE DISMISSED AND ANY WORK PERFORMED BY THAT PERSON SHALL BE REPLACED.
1.6 MANUFACTURERS DIRECTIONS
A. THE MANUFACTURERS' PUBLISHED DIRECTI0NS SHALL BE FOLLOWED IN THE DELIVERY, STORAGE, PROTECTI0N, INSTALLATION, PIPING AND WIRING OF ALL
EQUIPMENT AND MATERIAL SHOULD THE CONTRACTOR PERFORM ANY WORK THAT DOES NOT COMPLY WITH THE MANUFACTURERS' DIRECTI0NS OR
INSTRUCTI0NS FROM THE OWNER, HE SHALL BEAR ALL COSTS ARISING IN CONNECTI0N WITH DEFICIENCIES.
1.7 SUBMITTAL DATA
A. SEE SPECIFICATIONS
1.8 EQUIPMENT IDENTIFICATION
A. ALL MAJOR EQUIPMENT SUCH AS PANEL BOARDS, DISCONNECTS, AND OTHER SIMILAR EQUIPMENT SHALL BE IDENTIFIED BY THE ATTACHMENT OF NAME
PLATES.
B. COMPLETE ALL IDENTIFICATION CARDS FOR SWITCHES, STARTERS, AND OTHER DEVICES IN ALL PANEL BOARDS. AND SIMILAR PIECES OF EQUIPMENT,
WRITTEN IN A READABLE. NEAT MANNER AND INSERT THE CARD IN THE CARD HOLDERS BEHIND A SHEET OF CLEAR PLASTIC.
1.9 RECORDS FOR THE OWNER
A. EACH CONTRACTOR SHALL OBTAIN AT HIS OWN EXPENSE A COMPLETE SET OF BLUE LINE PRINTS ON WHICH HE SHALL KEEP AN ACCURATE RECORD OF
THE INSTALLALL0N OF ALL MATERIALS AND SYSTEMS COVERED BY HIS CONTRACTUAL AGREEMENT. THE RECORD SHALL INDICATE THE LOCATION OF ALL
EQUIPMENT AND THE ROUTING OF ALL SYSTEMS, ALL CONDUIT BURIED IN CONCRETE SLABS, WALLS, AND BELOW GRADE SHALL BE LOCATED BY DIMENSION
UNLESS A SURFACE-MOUNTED DEVICE IN EACH SPACE INDICATES THE EXACT LOCATION. HE SHALL THEN OBTAIN AT HIS EXPENSE ONE COMPLETE
REPRODUCIBLE SET OF THE ORIGINAL DRAWINGS ON WHICH HE SHALL NEATLY TRANSFER HIS NOTATI0NS AND DELIVER THESE DRAWINGS TO THE ENGINEER
AT JOB COMPLETI0N BEFORE FINAL PAYMENT FOR DELIVERY TO THE OWNER.
B. IN ADDITION TO THE ABOVE, EACH CONTRACTOR SHALL ACCUMULATE DURING THE JOB PROGRESS THE FOLLOWING DATA IN DUPLICATE PREPARED IN
A NEAT BROCHURE OR PACKET FOLDER AND TURN OVER TO THE ENGINEER AND OWNER FOR CHECKING, BINDING AND SUBSEQUENT DELIVERY TO THE
OWNER. THE ELECTRICAL CONTRACTOR SHALL INCLUDE IN HIS BID THE COST OF BINDING INTO A BOOK.
1. ALL WARRANTIES AND GUARANTEE AND MANUFACTURERS' DIRECTI0NS ON EQUIPMENT AND MATERIAL COVERED BY THE CONTRACT.
2. COPIES OF APPROVED SHOP DRAWINGS.
1.10 ELECTRICAL ENERGY, WATER AND SANITARY FACILITIES
A. ELECTRICAL ENERGY, WATER AND SANITARY FACILITIES REQUIRED FOR THE CONSTRUCTION OF THIS PROJECT SHALL BE PROVIDED AS HEREIN BEFORE
SPECIFIED UNDER THE ARCHITECTURAL SECTIONS OF THE WORK
1.11 SUPERVISION
A. EACH CONTRACTOR SHALL KEEP A COMPETENT SUPERINTENDENT OR FOREMAN ON THE JOB AT ALL TIMES AND SHALL BE FULLY RESPONSIBLE FOR THE
SUPERVISION OF HIS WORK. PERIODIC VISITATIONS TO THE PROJECT BY THE ENGINEER, COMMONLY REFERRED TO AS OBSERVATIONS, ARE ONLY FOR THE
EXPRESS PURPOSE OF VERIFYING COMPLIANCE BY THE CONTRACTOR WITH THE CONTRACT DOCUMENTS. SUCH VISITATIONS BY THE ENGINEER SHALL NOT
BE CONSTRUED TO MAKE THE ENGINEER RESPONSIBLE FOR PROVIDING A SAFE PERFORMANCE OF THE WORK BY THE CONTRACTOR OF THE CONTRACTOR'S
EMPLOYEES OR THE SAFETY OF THE SUPPLIES OF THE CONTRACTOR OR HIS SUB-CONTRACTORS.
1.12 DRAWINGS AND SPECIFICATIONS
A. THE DRAWINGS SHOW DIAGRAMMATICALLY THE LOCATIONS OF THE VARIOUS LINES, DUCTS, CONDUITS, FIXTURES, AND EQUIPMENT AND THE METHOD
OF CONNECTING AND CONTROLLING THEM. IT IS NOT INTENDED TO SHOW EVERY CONNECTION IN DETAIL AND ALL FITTINGS REQUIRED FOR A COMPLETE
SYSTEM. THE SYSTEMS SHALL INCLUDE BUT ARE NOT LIMITED TO THE ITEMS SHOWN ON THE DRAWINGS. EXACT LOCATIONS OF THESE ITEMS SHALL BE
DETERMINED BY REFERENCE TO THE GENERAL PLANS AND MEASUREMENTS AT THE BUILDING AND IN COOPERATION WITH THE OTHER SUBCONTRACTORS,
AND IN ALL CASES, SHALL BE SUBJECT TO THE APPROVAL OF THE ENGINEER AND OWNER.
THE OWNER RESERVES THE RIGHT TO MAKE ANY REASONABLE CHANGE IN THE LOCATION OF ANY PART OF THIS WORK WITHOUT ADDITIONAL COST TO THE
OWNER.
B. SHOULD ANY CHANGES BE DEEMED NECESSARY BY THE CONTRACTOR IN ITEMS SHOWN ON THE CONTRACT DRAWINGS, THE SHOP DRAWINGS,
DESCRIPTIONS AND THE REASON FOR THE PROPOSED CHANGES SHALL BE SUBMITTED TO THE ENGINEER AND OWNER FOR APPROVAL
C. EXCEPTIONS AND INCONSISTENCIES IN PLANS AND SPECIFICATIONS SHALL BE BROUGHT TO THE OWNER'S ATTENTION BEFORE BIDS ARE SUBMITTED;
OTHERWISE, THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COST OF ANY AND ALL CHANGES AND ADDITIONS THAT MAY BE NECESSARY TO
ACCOMMODATE HIS PARTICULAR APPARATUS.
D. THE CONTRACTOR SHALL LAY OUT HIS WORK MAINTAINING ALL LINES, GRADES AND DIMENSIONS ACCORDING TO THESE DRAWINGS WITH DUE
CONSIDERATION FOR OTHER TRADES AND VERIFY ALL DIMENSIONS AT THE SITE PRIOR TO ANY FABRICATION OR INSTALLATION. SHOULD THE LAYOUT BE
IMPRACTICAL, THE OWNER SHALL BE NOTIFIED BEFORE ANY INSTALLATION OR FABRICATION, AND THE EXISTING CONDITIONS SHALL BE INVESTIGATED AND
PROPER CHANGES EFFECTED WITHOUT ADDITIONAL COST.
E. TITLES OF SECTIONS AND PARAGRAPHS IN THESE SPECIFICATIONS ARE INTRODUCED MERELY FOR CONVENIENCE AND ARE NOT TO BE CONSTRUED AS A
CORRECT OR COMPLETE SEGREGATION TO TABULATION OF THE VARIOUS UNITS OF MATERIALS AND/OR WORK. THE OWNER DOES NOT ASSUME ANY
RESPONSIBILITY, EITHER DIRECT OR IMPLIED, FOR OMISSIONS OR DUPLICATIONS BY THE CONTRACTOR OR ANY SUBCONTRACTOR, DUE TO REAL OR
ALLEGED ERROR IN THE ARRANGEMENT OF MATTER IN THE CONTRACT DOCUMENTS.
F. DIFFERENT ELECTRICAL OUTLETS, DEVICES, ETC. ARE INDICATED BY SYMBOLS SCHEDULED ON THE DRAWINGS. APPROXIMATE LOCATIONS ARE SHOWN;
HOWEVER, THE DESIGN TEAM RESERVES THE RIGHT TO MAKE REASONABLE CHANGES IN LOCATIONS WITHOUT ADDITIONAL COSTS.
G. LINES INDICATING BRANCH CIRCUITS DO NOT SHOW EXACT ROUTING BUT INDICATE THE ARRANGEMENT AND CONTROL OF CIRCUITS. CONCEAL
RACEWAYS (UNLESS NOTED OTHERWISE) AND RUN IN MOST DIRECT MANNER BETWEEN CABINETS, OUTLETS, ETC.
GENERAL NOTES:
A. THE ELECTRICAL INFORMATION SHOWN ON THIS PLAN IS BASED UPON THE LATEST INFORMATION AVAILABLE FROM THE RESPECTIVE UTILITY COMPANIES.
IT IS INTENDED FOR PURPOSES OF GENERAL BIDDING AND BASIC CLARITY.
SPECIFIC JOB SITE CONDITIONS SHALL BE FIELD VERIFIED PER NOTES 'B' THROUGH 'E' BELOW. THE ELECTRICAL CONTRACTOR SHALL ASSUME ALL
RESPONSIBILITY FOR SAID FIELD CONDITIONS AND ANY ASSOCIATED CHANGES REQUIRED BY THE RESPECTIVE UTILITY COMPANIES INVOLVED.
B. THE ELECTRICAL CONTRACTOR SHALL CONTACT THE ELECTRICAL UTILITY, AND VERIFY ALL REQUIREMENTS AND EQUIPMENT, AND PROVIDE ALL WIRING,
BOXES, CONDUIT, CONCRETE PADS, TRENCHING AND BACKFILL, ETC. NECESSARY FOR PROPER INSTALLATION, PAY ALL FEES AND CHARGES INCURRED,
COORDINATE WITH ELECTRICAL UTILITY.
C. THE ELECTRICAL CONTRACTOR SHALL CONTACT THE TELEPHONE UTILITY, VERIFY ALL REQUIREMENTS AND EQUIPMENT, AND FURNISH AND INSTALL ALL
WIRING, BOXES, CONDUIT, GROUNDING, CONCRETE PADS, TRENCHING AND BACKFILL, ETC., NECESSARY FOR PROPER INSTALLATION. PAY ALL FEES AND
CHARGES INCURRED. COORDINATE WITH TELEPHONE UTILITY.
D. THE ELECTRICAL CONTRACTOR SHALL FIELD VERIFY. IN THE PRESENCE OF THE RESPECTIVE UTILITY COMPANY REPRESENTATIVES, THE LOCATIONS OF ALL
EXISTING UTILITY SERVICES AND EQUIPMENT, AND THE PROPOSED LOCATIONS OF ALL NEW UTILITY SERVICES AND EQUIPMENT. THE ELECTRICAL
CONTRACTOR SHALL INCLUDE IN HIS BID SUFFICIENT FUNDS TO COVER ALL COSTS REQUIRED BY UTILITY COMPANIES TO PROVIDE NEW SERVICES AND/OR
UPGRADE EXISTING SERVICES. NO ALLOWANCES WILL BE MADE FOR THE ELECTRICAL CONTRACTOR'S UNFAMILIARITY WITH THE EXIST1NG CONDITIONS,
REQUIREMENTS OF THE NEW CONDITIONS, AND/OR FAILURE TO COORDINATE INSTALLATION WITH THE RESPECTIVE UTILITY.
E. THE ELECTRICAL CONTRACTOR SHALL CONTACT THE LOCAL ELECTRICAL CODE ENFORCEMENT AUTHORITIES AND THE LOCAL FIRE MARSHAL, VERIFY ALL
REQUIREMENTS AND EQUIPMENT. AND FURNISH AND INSTALL ALL ELECTRICAL ITEMS NECESSARY FOR PROPER INSTALLATION IN STRICT ACCORDANCE WITH
THE GUIDELINES AND INTERPRETATIONS SET FORTH BY THESE GOVERNING LOCAL AUTHORITIES, ABOVE AND BEYOND ALL THE BASIC ELECTRICAL AND FIRE
ALARM REQUIREMENTS SET FORTH IN THE NEC AND NFPA. NO ALLOWANCES WILL BE MADE FOR THE ELECTRICAL CONTRACTOR'S FAILURE TO
COORDINATE ALL SUCH REQUIREMENTS WITH SAID LOCAL AUTHORITIES.
F. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL SITE LIGHTING AS REQUIRED BY OWNER AND OWNER'S LANDSCAPE LIGHTING DESIGNER,
SITE LIGHTING SHALL BE INSTALLED TO PROVIDE A MINIMUM N.A.I.E.S. STANDARDS OF ONE-QUARTER (1/4) FOOT-CANDLE AVERAGE MAINTAINED ON
PAVED, UNENCLOSED OR UNSHELTERED DRIVING SURFACES. PROVIDE BUILDING-MOUNTED FLOOD LIGHTS. POLE LIGHTS AND OTHER SITE LUMINARIES
INDICATED ON SITE PLAN ELECTRICAL SYMBOLS LEGEND IN LOCATIONS SHOWN. HOMERUN THRU PHOTOCELL TO NEAREST OWNERS PANEL
G. THE ELECTRICAL CONTRACTOR SHALL FURNISH AND INSTALL ALL J-BOXES, POWER, CONTROL AND RELATED
COMMUNICATIONS WIRING IN CONDUIT PLUS ALL FINAL CONNECTIONS FOR ALL ID SIGNS, SECURITY GATES, CARD
PEDESTALS, ETC.
H. HOMERUN SITE LIGHTING CIRCUITS THROUGH PHOTOCELL RELAY TO 20A/1P CIRCUIT BREAKER IN NEAREST OWNER'S
PANEL OR CLUBHOUSE PANEL
I. LOCATIONS OF ALL POST LIGHTS, WALKWAY DECOR LIGHTS, AND OTHER LANDSCAPE LIGHTING SHALL BE FIELD VERIFIED
PRIOR TO INSTALLATION WITH LANDSCAPE ARCHITECT AND OWNER'S REPRESENTATIVE. LOCATIONS SHOWN ON THIS
SMALL SCALE PLAN ARE APPROXIMATE ONLY.
J. ALL ELECTRICAL WORK SHALL CONFORM TO THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE, NFPA 70, AS
ENFORCED BY THE AUTHORITIES HAVING JURISDICTION.
K. WHERE A FIRE ALARM SYSTEM OR SYSTEMS ARE REQUIRED, PROVIDE APPROPRIATE CONSTRUCTION CONFORMING TO
THE LATEST EDITION OF THE NATIONAL FIRE PROTECTION ASSOCIATION FIRE ALARM CODE, NFPA 72, AND ALL LOCAL
CODES AS ENFORCED BY THE AUTHORITIES HAVING JURISDICTION.
L THE ELECTRICAL CONTRACTOR SHALL INCREASE ONE SIZE UP TO ALL CONDUCTORS FOR EVERY 75 LFT. IN ORDER TO
PREVENT A VOLTAGE DROP EXCEEDING 3% AT THE FARTHEST OUTLET OF POWER, HEATING AND LIGHTING LOADS, OR
COMBINATION OF SUCH LOADS, AND WHERE THE MAXIMUM TOTAL VOLTAGE DROP ON BOTH THE FEEDERS AND BRANCH
CIRCUITS TO THE FARTHEST OUTLET DOES NOT EXCEED 5%, WILL PROVIDE REASONABLE EFFICIENCY OF OPERATION. IF
ELECTRICAL CONTRACTOR CAN NOT DETERMINE THE VOLTAGE DROPS OR PROPER CONDUCTOR SIZE, CONTACT THE
ELECTRICAL ENGINEER FOR ASSISTANCE.
A. ALL ELECTRICAL OUTLETS, LIGHT FIXTURES, FANS, SWITCHES, ETC.. SHALL COMPLY WITH THE 2008 NEC. & AS AMENDED
BY THE LOCAL CITY CODES.
B. OWNER TO COORD. LOC. OF GAS, WATER & ELECTRICAL METER & PANEL LOCATIONS.
C. TYP. OUTLETS TO BE INSTALLED AT +16" A.F.F. U.N.O. - VERIFY W/ OWNER. OUTLETS INDICATED AT COUNTERS ARE TO BE
INSTALLED AT +44" A.F.F. U.N.O. - OUTLETS INDICATED AT ENT. CENTERS ARE TO BE COORD. W/ MILLWORK
SUBCONTRACTOR & AUDIO VISUAL CONSULTANT.
D. OUTLETS IN FLOORS & TEL. JACKS ARE TO BE FIELD VERIFIED FOR LOC. BY OWNER.
E. COORD. OUTLETS, TEL. JACKS, ETC.. AT HOME CENTER & STUDY.
F. TWO OR MORE 20-AMPERE SM. APPLIANCE BRANCH CIRCUITS SHALL BE PROVIDED FOR ALL RECEPTACLE OUTLETS
LOCATIONS IN KITCHEN, PANTRY, NOOK, DINING RM. OR SIM. AREA. THESE CIRCUITS MUST SERVE NO MORE THAN (3)
OUTLETS EA. & HAVE NO OTHER OUTLETS CONNECTED. RE: 210-52B & 220-4B '02 NEC.
G. INSTALL ONE GFI OUTLET ADJACENT TO EACH BASIN IN ALL BATHROOMS. BATHROOM OUTLET(S) SHALL BE SUPPLIED
BY AT LEAST ONE 20-AMPERE BRANCH CIRCUIT. SUCH CIRCUITS SHALL HAVE NO OTHER OUTLETS CONNECTED. RE:
210-52D, & 210-8 '08 NEC.
H. OUTLETS IN THE FOLLOWING LOC. ARE TO HAVE GFI PROTECTION; BATHROOMS, GARAGES, OUTDOORS, UNF.
BASEMENTS, KITCHENS, LAUNDRY SINKS. RE: 210-52, & 210-8 '08 NEC.
I. GAS LOG OR FIREPLACE: SHALL REQUIRE A MANUAL SHUT-OFF VALVE LOCATED WITHIN 4' OF THE FIREBOX,
ACCESSIBLE TO THE ROOM IN WHICH THE APPLIANCE IS LOCATED. OUTSIDE COMBUSTION AIR MUST BE PROVIDED
DIRECTLY TO THE FIREBOX. RE: 2009 I.M.C.
J. A MAXIMUM OF 8 ELECTRICAL OUTLETS MAY BE CONNECTED TO A 15 AMPERE BRANCH CIRCUIT OR 10 ELECTRICAL
OUTLETS MAY BE CONNECTED TO A 20 AMPERE BRANCH CIRCUIT, PER 220-3 '08 NEC
K. LIGHT FIXTURES IN CLOTHES CLOSETS MUST COMPLY WITH 410-8 '08 NEC
L. THE GROUNDING ELECTRODE SYSTEM SHALL INCLUDE AN ELECTRODE ENCASED BY AT LEAST 2" OF CONCRETE,
LOCATED WITHIN AND NEAR THE BOTTOM OF A CONCRETE FOUNDATION OR FOOTING THAT IS IN DIRECT CONTACT
WITH THE EARTH, CONSISTING OF AT LEAST 20 FT. OF ONE OR MORE BARE OR ZINC GALVANIZED OR OTHER
ELECTRICALLY CONDUCTIVE COATED STEEL REINFORCING BARS OR RODS OF NOT LESS THAN 1/2" DIA., OR
CONSISTING OF AT LEAST 20 FT. OF BARE COPPER CONDUCTOR NOT SMALLER THAN NO.2. 250-50 (C). RE: '08 NEC
M. FIELD VERIFY ALL POWER AND CABLE REQUIREMENTS WITH OWNER AT ENTERTAINMENT AND HOME MANAGEMENT
CENTERS.
N. COORD. OPTIONAL CAT-6 OR EQUAL PRE-WIRE UPGRADE THROUGHOUT HOME WITH OWNER.
First Floor
Second Floor
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-92SWITCH FOR NEW DIRECT VENT GAS FIREPLACES
1) ELECTRIC SHOWN TO COORDINATE WITH EXISTING
SERVICES AND CIRCUITS.
2) TIE NEW CIRCUITS INTO EXISTING BREAKERS, I.E. ALL
NEW MASTER BATH CIRCUITS TO TIE INTO EXISTING
MASTER BATH BREAKER AT PANEL.
3) NOTIFY OWNER AND ARCHITECT IF EXISTING BREAKER
LOADS ARE INSUFFICIENT.
4) PROVIDE/ CONFIRM SMOKE DETECTORS AT ALL
BEDROOMS.
5) PROVIDE CO2 DETECTORS LOCATE PER
MANUFACTURERS RECOMMENDATION
6) VENT ALL BATH FANS TO EXTERIOR.
7) CABLE/POWER FOR TELEVISIONS IS ASSUMED,
CONTRACTOR TO VERIFY OWNERS SELECTED SYSTEM
AND COORDINATE PROPER WIRING.
COORDINATE LOCATION WITH INTERIORS PACKAGE
UTILIZE EXISTING EXHAUST FAN AT EXISTING POWDER ROOM
ROUGH-IN FOR PENDANT FAN WITH LIGHT
TIE INTO EXISTING STAIR AND HALL LIGHTING
TIE INTO EXISTING BEDROOM LIGHTING
TIE INTO EXISTING BEDROOM LIGHTING
08/17/18
Special inspections required for
all high strength bolting and
welds
08/17/18
08/17/18
08/17/18
08/17/18
08/17/18
X1.0
EXISTING
FLOOR
PLANSMAIN LEVEL
3
16" = 1'-0"1
UPPER LEVEL
3
16" =1'-0"2
C 2018 GPS Designs LLCISSUE6 July 2018RELEASE
PermitShapiro ResidenceStan and Carol Shapiro4425 Glen Falls LaneVail, Colorado 81657PROJECTShapiro AdditionPROJECT NO.17_SR-0002301 Boulder St, #333
Minturn CO 81645
970 470 4945
Forest Glen Lot 2BK 587 PG 376 MAP 08-19-92GARAGE
FAMILY RM
KITCHEN
DINING
FAMILY
LIVING
ENTRY
PANTRY
POWDER
34 BATH
LANDING
MASTER BED
M BATH
BED 2 BATH
LAUNDRY
BATH
BATH
BED 4
BED 3
CLO
CLO
CLO
DECK
DECK
EXISTING BATHROOM TO SHIFT OUT
TO AREA OF NEW ADDITION. NEW
BATHTUB TO BE ADDED.
EXISTING BATHROOM TO BE
RECONFIGURED. REPLACING
BATH/SHOWER WITH SHOWER ONLY.
ADDING ONE ADDITIONAL SINK.
EXISTING BATHROOM TO BE
RECONFIGURED INTO NEW AREA
NO NET INCREASE IN FIXTURES.
EXISTING POWDER ROOM TO BE
RECONFIGURED. REMOVING SHOWER
REDUCING FIXTURE COUNT.
MECHANICAL
SHIFT EXISTING RADIANT
BASEBOARD HEAT INTO NEWLY
SHIFTED BEDROOM
EXTEND EXISTING RADIANT FLOOR
HEATING AT BATHROOM
MOVE EXISTING RADIANT
BASEBOARD HEAT INTO NEWLY
SHIFTED REAR WALL AT WINDOWS.
EXISTING CHIMNEY TO BE
REMOVED
HATCH SHOWS AREAS OF MAIN
DEMOLITION, ADDITIONAL
SMALLER AREAS NEEDED FOR
WINDOWS/DOORS PER PLANS
08/17/18