HomeMy WebLinkAboutLochinvar cut sheet.pdf~ CON >~US®
REMOTE CONNECT
801 LER CONTROL,
FROM ANYWHERE.
From wherever you are, the CON·X·US option lets you use any Internet-capable device
to link up with the SMART SYSTEM on an unlimited number of KNIGHT boilers.
> Do regular CON·X·US
checks for all your KNIGHT
customers, and let them
know you're monitoring
their boiler's performance.
> Adjust setpoints, domestic
hot water, reset curves,
pump delays and more,
using the CON·X·US
interactive display.
> Status alerts via text or
e-mail let you know when
a KNIGHT boiler needs
attention.
With CON ·X·US, you're always in touch and in control.
Optional CON·X·US control board is sold separately.
l\NOROID APP ON
~ Cno~~lc olJy
l#th'4f41a@svsTE Mf
THE ULTIMATE IN BOILER CONTROL & MONITORING
The industry's most advanced boiler control system now includes the CON·X·US Remote Connect
option and LOCH-N-LINK USB Programming feature. See back cover for a complete list of
SMART SYSTEM functions and features.
Blue Screen Normal system operation
Yellow Screen Maintenance due shows
installer name & number
Red Screen Lockout mode
KNIGHT BOILER DIMENSIONS AND SPECIFICATIONS r;;o
r A
22
31
4{)
57
LOW VOLTAGE
ELECTRICAL
HIGH VOLTAGE
ELECTRICAL
CONNECTIONS
BOTTOM
399 80 94.4 377 328 35-1/l' 25' 21-3/4' 17-1/l' 12-1/l' 't-1/4' ')-1/l' 2-1/4' 13-1/4' 21-1/l' 9' 4-3/4' 4• 22-1/l' 3-3/4' 3/4' 1-1/l' 4• 4' 213
**10:1 Turndown ratio and top and bottom water connections are not included on WHN400. See dimensional chart for specific product information. WHN400 is rated in
Thermal Efficiency.
Information subject to change without notice. Change "N" to .. L .. for LP gas models. The Net AHRI Water Ratings shown are based on a piping and pickup allowance of 1.15. lochinvar should be consulted
before selecting a boiler for installations having unusual piping and pickup requirements. such as intermittent system operation, extensive piping systems, etc. The ratings have been determined
under the provisions governing forced draft burners.
SMART SYSTEM FEATURES
> Smart System Digital Operating Control
Multi-Color Graphic LCD Display w/Navigation Dial,
Soft Keys and Loch-N-Link USB programming
>Three Boller Setpolnt Temperature Inputs
Plus Domestic Hot Water Prioritization
> Built-In Cascading Sequencer for up to 8 Boilers,
with Cascade Redundancy
Multiple Size Boiler Cascade
Lead Lag
Efficiency Optimization
Front End Loading Capability
> Outdoor Reset Control with Outdoor Air Sensor
Programmable for Three Reset Temperature Inputs
> Programmable System Efficiency Optimizers
SH Night Setback
DHW Night Setback
Anti-Cycling
Outdoor Air Reset Curve
Ramp Delay
Modulation Factor Control
Boost Temperature & Time
> Four Pump Control
System Pump with Parameter for Continuous Operation
Boiler Pump with Variable Speed Control
Domestic Hot Water Pump
Domestic Hot Water Recirculation
> Domestic Hot Water Prioritization
DHW tank piped with priority in the boiler loop
DHW tank piped as a zone in the system with the pumps
controlled by the SMART SYSTEM
DHW Modulation Limiting
Separately Adjustable Space Heat/DHW Switching Times
> Building Management System Integration
0·10 VDC Input to Control Modulation or Setpoint
0·10 VDC Modulation Rate Output
0-10 VDC Input to Enable/Disable Call for Heat
> Access to BMS Settings through Graphic LCD Display
> High-Voltage Terminal Strip
120 VACI 60 Hertz/ I Phase Power Supply
Three Sets of Pump Contacts
> Low-Voltage Terminal Strip
DHW Recirculation Pump Start/Stop
24 VAC Device Relay
Proving Switch Contacts
Flow Switch Contacts
Alarm on Any Failure Contacts
Runtime Contacts
DHW Thermostat Contacts
3 Space Heat Thermostat Contacts
System Sensor Contacts
DHW Tank Sensor Contacts
Outdoor Air Sensor Contacts
Cascade Contacts
0-10 VDC BMS External Control Contact
0-10 VDC Boiler Rate Output Contacts
0-10 VDC Variable Speed System Pump Signal Input
0-10 VDC Signal to Control Variable Speed Boiler Pump
Modbus Contacts
>lime Clock
> Data Logging
Hours Running, Space Heating
Hours Running, Domestic Hot Water
Ignition Attempts
Last IO Lockouts
> Maintenance Reminder
Custom Maintenance Reminder with
Contractor Contact Information
Installer Ability to De-activate Service Reminder
> Low-Water Flow Safety Control & Indication
> Password Security
> Customizable Freeze Protection Parameters
Lochinvar, LLC
300 Maddox Simpson Parkway
Lebanon, Tennessee 37090
p, 61S.889.8900 I Fo 615.547.tooo
11 Cl Ill! C Lochinvar.com
STANDARD FEATURES
> 95% DOE AFUE Efficiency (56-286)
> Modulating Burner with up to 10:1 Tumdown**
Direct Spark Ignition
Low NOx Operation
> ASME Stainless Steel Heat Exchanger
30 PSI ASME Relief Valve
>Top and bottom water connections (MNPl)**
>Vertical & Horizontal Direct Vent
PVC, CPVC, Polypropylene or SS Venting up to 100 feet
> SMART SYSTEM Control
> Condensate Trap
> Other Features
Automatic Reset High Limit
Adjustable High Limit w/Manual Reset
Boiler Circulating Pump
Zero Clearances to Combustible Materials
15-Year Limited Warranty (See Warranty for Details)
5-Year Limited Parts Warranty
OPTIONAL EQUIPMENT
CON·X·US Remote Connectivity
Mod bus Communication
BACnet MSTP
Flow Switch
Low-WaterCutoffw/Manual Reset & Test
Alarm Bell
Concentric Vent Kit
Condensate Neutralization Kit
BMS Gateway to LON or BACnet IP
Multi-Temperature Loop Control
Sidewall Vent Termination
Wireless Outdoor Sensor
LP Gas Conversion Kit
>Firing Codes
M9 Standard Construction
M7 California Code
**Not included on WHN400