HomeMy WebLinkAbout1853 LIONSRIDGE LOOP TAB.pdf TEST, ADJUST AND BALANCE REPORT
PROJECT
1853 LIONSRIDGE LOOP
#1375
PREPARED FOR
SKYLINE MECHANICAL
REPORT ISSUE DATE
10/11/2018
PREPARED BY
HVAC TAB IIc
P.O. BOX 1926
VAIL, CO 81658
PHONE: 970-376-5198
E-MAIL: mrichardson@hvactab.co
HVAC TAB Ilc
TEST, ADJUST AND BALANCE REPORT
THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF
SYSTEM PERFORMANCE AND WAS OBTAINED IN COMPLIANCE WITH
NBC PROCEDURAL STANDARDS. ANY VARIANCES FROM THE DESIGN
REQUIREMENTS ARE NOTED THROUGHOUT THIS REPORT.
THE RESULTS SHOWN AND INFORMATION PRESENTED IN THIS
REPORT IS CERTIFIED TO BE ACCURATE AND COMPLETE, TO THE
EXTENT POSSIBLE BY EQUIPMENT AND PROCEDURES USED THROUGH-
OUT THIS SURVEY.
THE FINAL AIR DISTRIBUTION SYSTEM MEASUREMENTS ARE IN
COMPLIANCE WITH NBC PROCEDURAL STANDARDS FOR TESTING,
ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS AND THE
PROJECT SPECIFICATIONS.
CERTIFIED By„, 417 DATE: /Cf /r'/ /
THE FINAL HYDRONIC DISTRIBUTION SYSTEM MEASUREMENTS
ARE IN COMPLIANCE WITH NBC PROCEDURAL STANDARDS FOR
TESTING,ADUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS
AND THE PROJECT SPECIFICATIONS.
i
CERTIFIED BY: DATE:
HVAC TAB Ilc WARRANTS THAT THE AIR AND HYDRONIC SYSTEM
EVALUATED DURING THIS SURVEY IS OPERATING AT THE SPECIFIED LEVELS
AS SHOWN WITHIN THIS REPORT,AT AND ONLY AT THIS TIME. HVAC TAB lic
MAKES NO OTHER WARRANTIES, STATED OR IMPLIED, CONCERNING THE
CONTINUED PERFORMANCE, OPERATION OR SAFETY IN THE USE OF THIS
EQUIPMENT PASS THIS TIME.
CERTIFIED
Michael T.Richa son Page: 1
HVAC TAH.LLC
i 13-084-033 Expires 2/23/2019
NATIONAL BALANCING COUNCIL
HVAC TAB I l c INSTRUMENT
CALIBRATION REPORT
DATE: 10/10/2018
PROJECT : 1853 LIONSRIDGE LOOP
PROJECT ALTITUDE: "HG
INSTRUMENT/SERIAL# APPLICATION DATE OF USE CALIBRATION CALIBRATION
DATE DUE DATE
SHORTRIDGE ADM-870C/#M09211 AIR FLOW READINGS 10/10/2018 6/20/2018 6/20/2019
ANEMOMETER #T57251515001 AIR FLOW READINGS 10/10/2018 6/13/2018 6/13/2019
SHORTRIDGE FLOW HOOD AIF FLOW READINGS NOT USED * *
TH-720 HYGROMETER/#TH7200950003 AIR TEMP/HUMIDITY NOT USED 6/9/2018 6/9/2019
PITOT TUBE 18" PRES.READINGS 10/10/2018 N/A N/A
PITOT TUBE 24" PRES.READINGS NOT USED N/A N/A
PITOT TUBE 36" PRES.READINGS NOT USED N/A N/A
PITOT TUBE 48" PRES.READINGS NOT USED NA NA
SHIMPO TACHOMETER /#C105B0010 RPM READINGS NOT USED 6/9/2018 6/9/2019
FLUKE 375/#21290229 VOLT/AMP NOT USED 06/14/2018 6/14/2019
SHORTRIDGE HDM-250/#W11037 WATER PRES.READINGS NOT USED 6/20/2018 6/20/2019
ASCROFT/0-100 PSI/#D068332-06 WATER PRES.READINGS NOT USED * *
FLUKE 52 II THERMOMETER/99780167 TEMP.READINGS NOT USED 6/21/2018 6/21/2019
REFRACTOMETER RHA-100 /#RHA- GLYCOL%READINGS NOT USED N/A N/A
100
*CHECKED TO CALIBRATED METER
REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR
TEMPERATURE AND ALTITUDE. PAGE:
1853 LIONSRIDGE LOOP 10/10/2018
MUA
MANUFACTURER ELECTRO MAKEUP AIR
MODEL EM-MA05-240-1-08
SERIAL# 2819,
CFM 329 CFM
KEF
MANUFACTURER BEST
MODEL CC34E6SB
SERIAL# 1418 00011,
CFM 332 CFM