Loading...
HomeMy WebLinkAbout1853 LIONSRIDGE LOOP TAB.pdf TEST, ADJUST AND BALANCE REPORT PROJECT 1853 LIONSRIDGE LOOP #1375 PREPARED FOR SKYLINE MECHANICAL REPORT ISSUE DATE 10/11/2018 PREPARED BY HVAC TAB IIc P.O. BOX 1926 VAIL, CO 81658 PHONE: 970-376-5198 E-MAIL: mrichardson@hvactab.co HVAC TAB Ilc TEST, ADJUST AND BALANCE REPORT THE DATA PRESENTED IN THIS REPORT IS AN EXACT RECORD OF SYSTEM PERFORMANCE AND WAS OBTAINED IN COMPLIANCE WITH NBC PROCEDURAL STANDARDS. ANY VARIANCES FROM THE DESIGN REQUIREMENTS ARE NOTED THROUGHOUT THIS REPORT. THE RESULTS SHOWN AND INFORMATION PRESENTED IN THIS REPORT IS CERTIFIED TO BE ACCURATE AND COMPLETE, TO THE EXTENT POSSIBLE BY EQUIPMENT AND PROCEDURES USED THROUGH- OUT THIS SURVEY. THE FINAL AIR DISTRIBUTION SYSTEM MEASUREMENTS ARE IN COMPLIANCE WITH NBC PROCEDURAL STANDARDS FOR TESTING, ADJUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS AND THE PROJECT SPECIFICATIONS. CERTIFIED By„, 417 DATE: /Cf /r'/ / THE FINAL HYDRONIC DISTRIBUTION SYSTEM MEASUREMENTS ARE IN COMPLIANCE WITH NBC PROCEDURAL STANDARDS FOR TESTING,ADUSTING AND BALANCING OF ENVIRONMENTAL SYSTEMS AND THE PROJECT SPECIFICATIONS. i CERTIFIED BY: DATE: HVAC TAB Ilc WARRANTS THAT THE AIR AND HYDRONIC SYSTEM EVALUATED DURING THIS SURVEY IS OPERATING AT THE SPECIFIED LEVELS AS SHOWN WITHIN THIS REPORT,AT AND ONLY AT THIS TIME. HVAC TAB lic MAKES NO OTHER WARRANTIES, STATED OR IMPLIED, CONCERNING THE CONTINUED PERFORMANCE, OPERATION OR SAFETY IN THE USE OF THIS EQUIPMENT PASS THIS TIME. CERTIFIED Michael T.Richa son Page: 1 HVAC TAH.LLC i 13-084-033 Expires 2/23/2019 NATIONAL BALANCING COUNCIL HVAC TAB I l c INSTRUMENT CALIBRATION REPORT DATE: 10/10/2018 PROJECT : 1853 LIONSRIDGE LOOP PROJECT ALTITUDE: "HG INSTRUMENT/SERIAL# APPLICATION DATE OF USE CALIBRATION CALIBRATION DATE DUE DATE SHORTRIDGE ADM-870C/#M09211 AIR FLOW READINGS 10/10/2018 6/20/2018 6/20/2019 ANEMOMETER #T57251515001 AIR FLOW READINGS 10/10/2018 6/13/2018 6/13/2019 SHORTRIDGE FLOW HOOD AIF FLOW READINGS NOT USED * * TH-720 HYGROMETER/#TH7200950003 AIR TEMP/HUMIDITY NOT USED 6/9/2018 6/9/2019 PITOT TUBE 18" PRES.READINGS 10/10/2018 N/A N/A PITOT TUBE 24" PRES.READINGS NOT USED N/A N/A PITOT TUBE 36" PRES.READINGS NOT USED N/A N/A PITOT TUBE 48" PRES.READINGS NOT USED NA NA SHIMPO TACHOMETER /#C105B0010 RPM READINGS NOT USED 6/9/2018 6/9/2019 FLUKE 375/#21290229 VOLT/AMP NOT USED 06/14/2018 6/14/2019 SHORTRIDGE HDM-250/#W11037 WATER PRES.READINGS NOT USED 6/20/2018 6/20/2019 ASCROFT/0-100 PSI/#D068332-06 WATER PRES.READINGS NOT USED * * FLUKE 52 II THERMOMETER/99780167 TEMP.READINGS NOT USED 6/21/2018 6/21/2019 REFRACTOMETER RHA-100 /#RHA- GLYCOL%READINGS NOT USED N/A N/A 100 *CHECKED TO CALIBRATED METER REMARKS: ALL READINGS WITH SHORTRIDGE INSTRUMENTS ARE CORRECTED FOR TEMPERATURE AND ALTITUDE. PAGE: 1853 LIONSRIDGE LOOP 10/10/2018 MUA MANUFACTURER ELECTRO MAKEUP AIR MODEL EM-MA05-240-1-08 SERIAL# 2819, CFM 329 CFM KEF MANUFACTURER BEST MODEL CC34E6SB SERIAL# 1418 00011, CFM 332 CFM