HomeMy WebLinkAboutA18-0060_approved plans_1538681619.pdfCHECKED BY:DESCRIPTION CAD DATE MARK SYSTEM:CHKISSUE DATE: SHEET: DRAWN BY: JOB #: PROJECT #:24" x 36" - Arch D Size ISSUE LOG:Revisions shown with # symbolDRAWING INDEX LEGENDS PROJECT DIRECTORY JOHNSON CONTROLS CONTACTS SCOPE OF WORK APPLICABLE CODES & STANDARDS DEVICE TAG LEGEND SYSTEM SEQUENCE OF OPERATIONSGENERAL NOTES MODIFICATIONS TO FIRE ALARM SYSTEM EAST ELEVATOR UPGRADE LODGE TOWER - BUILDING F 1. THESE DRAWINGS DEPICT GENERAL LOCATIONS OF LIFE SAFETY EQUIPMENT & FIELD DEVICES. EXACT ROUTING OF CONDUITS IS TO BE DETERMINED IN THE FIELD BY THE INSTALLING CONTRACTOR TO SUIT CONDITIONS. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS. 2. SHOULD ANY CONDITIONS EXIST THAT DIFFER FROM WHAT IS INDICATED ON THESE DRAWINGS WHICH CAUSE MAJOR DEVIATIONS IN THE WORK SHOWN, THE CONTRACTOR SHALL CONTACT JOHNSON CONTROLS IN A TIMELY MANNER SO AS NOT TO IMPAIR THE CONSTRUCTION SCHEDULE. 3. CONTRACTOR IS RESPONSIBLE FOR MAKING AND OBTAINING APPROVAL FOR ALL NECESSARY ADJUSTMENTS IN CIRCUITING AS REQUIRED TO ACCOMMODATE THE RELOCATION OF EQUIPMENT AND/OR DEVICES WHICH ARE AFFECTED BY ANY AUTHORIZED CHANGE. ALL CHANGES SHALL BE CLEARLY INDICATED ON THE RECORD DRAWINGS. 4. A STAMPED SET OF APPROVED FIRE ALARM DRAWINGS SHALL BE AT THE JOB SITE AND SHALL BE USED FOR INSTALLATION. 5. THE POWER CIRCUIT TO THE FACP AND TO THE FIRE ALARM POWER SUPPLIES SHALL BE ON A DEDICATED 120V, 20A BRANCH CIRCUIT BREAKER, AND SHALL HAVE A RED MARKING, LOCK-ON PROVISION AND SHALL BE IDENTIFIED AS "FIRE ALARM CIRCUIT CONTROL." THE LOCATION OF THE CIRCUIT DISCONNECT MEANS (CIRCUIT BREAKER) SHALL BE PERMANENTLY IDENTIFIED AT THE FIRE ALARM CONTROL UNIT. 6. UPDATE THE AS-BUILT DRAWING SET DAILY WITH JOB PROGRESS. RETURN THE AS-BUILT DRAWING SET TO JOHNSON CONTROLS NO LATER THAN 7 DAYS AFTER FINAL TEST. 7. THE CONTRACTOR WILL MAINTAIN ALL AREAS OF THE BUILDING IN A NEAT AND WORKMANLIKE MANNER. 8. DO NOT APPLY POWER EXCEPT IN THE PRESENCE OF A FACTORY TRAINED JOHNSON CONTROLS TECHNICAL REPRESENTATIVE. 9. ANY SMOKE DETECTOR HEAD INSTALLED BEFORE THE BUILDING IS CLEANED AND ACCEPTED SHALL BE COVERED TO PROTECT FROM DUST. ANY FALSE ALARMS DUE TO DIRT CONTAMINATED HEADS SHALL BE THE RESPONSIBILITY OF THE FIRE ALARM INSTALLER. 10. THE FIRE ALARM INSTALLER WILL MAINTAIN THE FIRE RESISTANCE INTEGRITY OF ALL WALL, CEILING, AND ROOF ASSEMBLIES ANY TIME THAT WORK IS NOT ACTIVELY BEING PERFORMED. 11. INSTALLATION OF DEVICES SHALL BE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS. POWER LIMITED AND NON-POWER LIMITED FIELD WIRING MUST BE INSTALLED WITHIN THE FACP ENCLOSURE IN ACCORDANCE WITH MANUFACTURER'S INSTRUCTIONS AND APPLICABLE ELECTRICAL CODES. REFER TO 'APPLICABLE CODES & STANDARDS' FOR SPECIFIC CODE REFERENCES. 12. ALL WIRING SHALL BE INSTALLED ACCORDING TO APPLICABLE ELECTRICAL CODES. 13. FIRE ALARM CIRCUITS SHALL BE IDENTIFIED IN ACCORDANCE WITH APPLICABLE ELECTRICAL CODES. MARK ALL FIRE ALARM WIRES IN ACCORDANCE WITH APPLICABLE ELECTRICAL CODE SECTIONS FOR POWER LIMITED AND NON-POWER LIMITED WIRE. 14 FIRE ALARM CABLE INSTALLED IN DUCTS, PLENUM, AND OTHER SPACES USED FOR ENVIRONMENTAL AIR SHALL BE TYPE FPLP. 15. FIRE ALARM CABLE INSTALLED IN THE VERTICAL RUNS AND PENETRATING MORE THAN ONE FLOOR OR CABLES INSTALLED IN VERTICAL RUNS IN SHAFTS SHALL BE TYPE FPLR. 16. FIRE ALARM CABLE INSTALLED IN UNDERGROUND CONDUIT OR OTHER WET LOCATIONS SHALL BE UL LISTED FOR WET LOCATIONS. 17. FIRE ALARM CIRCUITS EXTENDING BEYOND ONE BUILDING AND RUN OUTDOORS SHALL BE INSTALLED IN ACCORDANCE APPLICABLE ELECTRICAL CODES, WHERE APPLICABLE. 18. ALL WIRING, INCLUDING SHIELDS MUST BE DRY AND FREE OF SHORTS AND GROUNDS. 19. ALL SHIELDED WIRE MUST HAVE SHIELD CONTINUITY AT FULL LENGTH OF THE WIRE. 20. ONLY SYSTEM WIRING CAN BE RUN IN THE SAME CONDUIT. 21. 120VAC IS NOT PERMITTED IN THE SAME CONDUIT WITH LOW VOLTAGE WIRING. 22. MAINTAIN MAXIMUM CONDUIT FILL RATIO AS PER APPLICABLE ELECTRICAL CODES REQUIREMENTS. 23. EXISTING CONDUITS MAY BE USED BY THE INSTALLATION CONTRACTOR AS DEEMED NECESSARY; HOWEVER, ANY EXISTING CONDUIT WILL BE USED ONLY IF CONDUITS MEET CURRENT STANDARDS AND CODES. JOHNSON CONTROLS MAKES NO STATEMENTS WRITTEN OR VERBAL AS TO THE CONDITION OF EXISTING CONDUITS. Site LODGE TOWER 200 VAIL ROAD VAIL, CO 81657 General Contractor E.M.C.C PO BOX 4555 EAGLE, CO 81631 Owner LODGE TOWER 200 VAIL ROAD VAIL, CO 81657 Johnson Controls District - 419 14200 E. EXPOSITION AVE AURORA, CO 80012 PHONE: 303-355-0500 FAX: 303-355-0615 SERVICE: 303-355-0500 PHONE: Sales Representative TODD STEWART TODD.STEWART@JCI.COM 303-961-2749 PHONE: Project Manager GREG MIKEVICH GREG.MIKEVICH@OSLOCORP.COM 303-888-5535 PHONE: Drawings Prepared By DEANNA JOHNSON DEANNA.JOHNSON@JCI.COM 303-283-4406 PHONE: Drawings Reviewed By JASON EVANS JASON.1.EVANS@JCI.COM 303-349-4919 OCCUPANCY TYPE(S): SPRINKLER PROTECTION: R-2 Residential Group BUILDING IS FULLY SPRINKLED MFG4100ES FIRE ALARM CONTROL PANEL, 120 VAC EXISTING EX. SIMPLEX PANELS & ANNUNCIATORS FACP 4" SQ. BOX 1 1/2" DEEP 4A SINGLE GANG BOX 2" DEEP 1B SINGLE GANG BOX 2 1/8" DEEP W/COVER 1D CODE BOX SPECIFICATIONS CODE BOX SPECIFICATIONS 4" SQ. BOX 2 1/8" DEEP W/ TWO GANG COVER4H 4" OCT. BOX 1 1/2" DEEP4K QTY SYMBOL DESCRIPTION MODEL BOX CODE WIRE TYPEBRAND FIRE ALARM SYMBOL LEGEND 4H RELAY IAM 4090-9002 3 M RSIMPLEX 4" SQ. BOX 1 1/2" DEEP W/RACO 787 OR EQUIV.4R 4KADDRESSABLE PHOTOELECTRIC SMOKE SENSOR WITH STANDARD BASE 4098-9792 BASE 4098-9714 HEAD 1 M 4RSIMPLEX 4AHEAT SENSOR WITH STANDARD BASE 4098-9792 BASE 4098-9733 HEAD 5 M 1BSIMPLEX INITIATING DEVICES MODULES & RELAYS BACKBOX CODES S AOM 1D ENCAPSULATED RELAY PAM-1, SPDT W/ LED, APOLLO AMERICA INC PAM-1 2088-9021 2 RSIMPLEXR 4HRELAY IDNET 2 IAM W/T SENSE 4090-91181 M RSIMPLEXAIO 2 MAX CONDUCTOR AREA CONDUIT SIZE 1/2" 3/4" 1" 0.12 SQ INCH * 0.21 SQ INCH * 0.34 SQ INCH * 1-1/4" 1-1/2" 2" 0.60 SQ INCH * 0.82 SQ INCH * 1.34 SQ INCH * NOTES *40% FILL PER N.E.C. SUBSCRIPT "u": UNSHIELDED CABLES MIXED WITH SHIELDED CABLES OF SAME CIRCUIT DESIGNATION. MAX CONDUCTOR AREA CONDUIT SIZE FPLPTFFNCIRCUIT DESCRIPTION ACCEPTABLE CABLE TYPES CONSTRUCTION GAUGE CIRCUIT PROPERTIES OUTDOORFPLRC.I.THHNFIRE ALARM WIRE LIST 18 AWG X M IDNET UTP SOLID X 14 AWG X XP POWER 2 COND. SOLID X 14 AWG X XR RELAY 2 COND. SOLID X IMPORTANT NOTICE TO USER: This information may not be sold or transferred to any third party, used on other projects or additions to the project for which it was prepared, or used for completion of this project by any third party. Johnson Controls disclaims all liability for the use or reuse of altered files by the user or any third party and such use will be a user's sole risk. User shall, to the fullest extent permitted by law, defend, indemnify, and hold Johnson Controls harmless from any and all claims for loss, damage or injury arising directly or indirectly from any such unauthorized use.LAST PRINTED:LAST SAVED BY:FILE PATH: G:\Lodge at Vail - 174 E Gore Creek-Vail\Building F - Lodge Tower - 200 Vail Rd\12 - Lodge Tower East Elev. #1 Upgrade - 2018 - 608831101\Fire\FA-001.dwg9/28/2018 9:56:35 AMJ JODEA3 419:608831101 J. EVANS D. JOHNSON 9/24/18 FIRE ALARM SYSTEMLODGE TOWER200 VAIL ROADVAIL, CO 8165714200 E. EXPOSITION AVEAURORA, CO 80012PHONE: 303-355-0500 SERVICE: 303-355-0500FAX: 303-355-0615DISTRICT - 419FA-001 COVER SHEET JOHNSON CONTROLS © 2018LODGE TOWER - BUILDING FEAST ELEVATOR UPGRADE© Johnson Controls 2018. All rights reserved. Reuse, copying, modification or alteration of the drawings and other information contained herein is strictly prohibited. INTERNATIONAL FIRE CODE (IFC), 2015 EDITION INTERNATIONAL BUILDING CODE (IBC), 2015 EDITION INTERNATIONAL MECHANICAL CODE (IMC), 2015 EDITION INTERNATIONAL FIRE SAFETY CODE (NFPA 101), 2012 EDITION NATIONAL ELECTRIC CODE (NFPA 70), 2011 EDITION NATIONAL FIRE ALARM AND SIGNALING CODE (NFPA 72), 2017 EDITION ELEVATOR CODE 2007 EDITION A17.1 STORIES: 7 FLOOR + BASEMENT + GROUND FLOOR + ATTIC 7TH FLOOR - ELEVATOR #1 AND ELEVATOR MACHINE ROOM (SCOPE OF WORK) Vail Lodge Tower - Sequence of Operations SYSTEM OUTPUTS FACP Annunciation Notification Required Supplementary Controls SYSTEM INPUTS Actuate Common Alarm Signal Indicator Actuate Audible Alarm SignalActuate Common Supervisory Signal Indicator Actuate Audible Supervisory SignalActuate Common Trouble Signal Indicator Actuate Audible Common Trouble SignalActuate Alarm Indicator Actuate Evacuation Signals (Horn/Strobes)Display Change of StatusTransmit Fire Alarm Signal to Supervising StationTransmit Supervisory Signal to Supervising StationTransmit Trouble Signal to Supervising StationRelease Magnetically Held DoorsRecall Elevators to Primary Recall FloorRecall Elevators to Alternate Recall FloorActivate Elevator Cab LightShunt power to Elevator Controller *Close Relay That Will Cut Power to Fire/SmokeDampers Serving H&V Unit - M1-122Close Relay That Will Cut Power to the H&V Unit - M1-123Close the Dry Contacts at the VFD'sFireman's Overide Input - M1-124Light Fault Light for SEF-1 onSmoke Management Control PanelShutdown AHUSilence Audible Signal (Horns)Actuate Outside Horn/StrobeA B C D E F G H I J K L M N O P Q T U V W X Y Z 1 Manual Pull Station - All Locations X X X X X X X 1 2 Smoke Sensors - All Locations X X X X X X X X X X 2 3 Smoke Sensor - Elevator Machine Room X X X X X X X X X X X 3 4 Smoke Sensor - Elevator Shaft X X X X X X X X X X X X 4 5 Smoke Sensor - Elevator Lobby Ground Flr X X X X X X X X X X X 5 6 Smoke Sensor - Elevator Lobby Flr 1 - 7 X X X X X X X X X X X 6 7 Duct Smoke Sensor X X X X X 7 8 Thermal Sensors - All Locations X X X X X X X X X X 8 9 Thermal Sensor - Elevator Machine Room X X X X X X X X X X X X 9 10 Thermal Sensors - Elevator Shaft X X X X X X X X X X X X 10 11 Thermal Sensors - Storage Lockers X X X X X X X X X X 11 12 Waterflow - Main X X X X X X X X X X X 12 13 Sprinkler Control Valve - X X X X 13 14 VFD Fault Status Module - M1-125 X 14 15 Internal Current Sensor (Fan Belt Broke) - M1-126 X 15 16 FACP AC Power Failure X X X X 16 17 FACP Low Battery X X X X 17 18 Open Circuit X X X X 18 19 Ground Fault X X X X 19 20 Notification Appliance Circuit Short X X X X 20 21 Alarm Signal Silence X X 21 A B C D E F G H I J K L M N O P Q T U V W X Y Z NOTE: Audible Evacuation Signal shall be Temporal Pattern per NFPA 72-2010. * Disconnect power after a time delay equal to the time it takes for the car to travel from the highest to the lowest level plus 10 seconds. FIRE DEPT./BLDG DEPT. PLAN REVIEW #: Sheet List Table Sheet Number Sheet Title FA-001 COVER SHEET FA-101 DEVICE PLACEMENT PLAN & PARTIAL RISER DIAGRAM FA-601 CALCULATIONS FA-701 WIRING TYPICALS NICET CERTIFICATION 9/28/2018 THIS IS A MODIFICATION TO THE EXISTING FIRE ALARM SYSTEM AT LODGE TOWER, PART OF LODGE AT VAIL, 200 VAIL ROAD VAIL, CO 81657. SCOPE OF WORK TO TAKE PLACE ON THE SEVENTH FLOOR, EAST ELEVATOR #1. UPGRADE ELEVATOR CONTROLS TO SUPPORT ELEVATOR MODERNIZATION. ADDITION OF ADDRESSABLE INITIATION DEVICES TO THE ELEVATOR MACHINE ROOM AND TOP OF SHAFT. CONTROL MODULES WILL BE ADDED TO CONTROL POWER SHUNT, FF HAT, PRIMARY AND ALTERNATE RECALL. MONITOR FUNCTION IS PROVIDED TO MONITOR SHUNT TRIP. ALL OTHER DEVICES IN AREA TO REMAIN UNCHANGED. BATTERY CALCULATIONS HAVE BEEN UPDATED. VOLTAGE DROP CALCULATIONS WILL REMAIN UNCHANGED. THE SEQUENCE OF OPERATION WILL REMAIN AS-IS AND WILL NOT BE MODIFIED. ALL NEW WIRING TO BE CLASS B. THE EXISTING FIRE ALARM SYSTEM SHALL NOT BE DISCONNECTED OR TAKEN OUT OF SERVICE WITHOUT WRITTEN PERMISSION FROM THE OWNER. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE WITH THE OWNER THE TIMING OF ANY EXISTING FIRE ALARM SYSTEM DEMOLITION WORK. Approved for changes Stop using this address. Vail Fire & Emergency Services 10/04/18 M2-140 M2-147 PRIM ALTERN FF HAT M2-148 M2-149 AIO2 M2-146ELEV POWER M2-141 M M2-143 M2-142 M2-145M2-144 FLOOR AIO 2M2-121R R ELEV 2 BREAKER AOM M2-124PRIMALTERNFF HATM2-154M2-125ELEVATOR 2 CONTROLLER AOMM2-123AOMM2-122M2-156IDNET - M2M2-140M2-141M2-142M2-143M2-144M2-145AIO 2 M2-146R R ELEV 1 BREAKER AOM M2-147PRIM ALTERN FF HAT ELEVATOR 1 CONTROLLER AOM M2-148AOM M2-149 M2-66POWER CHECKED BY:DESCRIPTION CAD DATE MARK SYSTEM:CHKISSUE DATE: SHEET: DRAWN BY: JOB #: PROJECT #:24" x 36" - Arch D Size ISSUE LOG:Revisions shown with # symbolMFG4100ES FIRE ALARM CONTROL PANEL, 120 VAC EXISTINGSIMPLEX PANELS & ANNUNCIATORS FACP 4" SQ. BOX 1 1/2" DEEP 4A SINGLE GANG BOX 2" DEEP 1B SINGLE GANG BOX 2 1/8" DEEP W/COVER 1D CODE BOX SPECIFICATIONS CODE BOX SPECIFICATIONS 4" SQ. BOX 2 1/8" DEEP W/ TWO GANG COVER4H 4" OCT. BOX 1 1/2" DEEP4K SYMBOL DESCRIPTION MODEL BOX CODE WIRE TYPEBRAND FIRE ALARM SYMBOL LEGEND 4HRELAY IAM 4090-9002 M RSIMPLEX 4" SQ. BOX 1 1/2" DEEP W/RACO 787 OR EQUIV.4R 4K ADDRESSABLE PHOTOELECTRIC SMOKE SENSOR WITH STANDARD BASE 4098-9792 BASE 4098-9714 HEAD M 4RSIMPLEX 4AHEAT SENSOR WITH STANDARD BASE 4098-9792 BASE 4098-9733 HEAD M 1BSIMPLEX INITIATING DEVICES MODULES & RELAYS BACKBOX CODES S AOM 1DENCAPSULATED RELAY PAM-1, SPDT W/ LED, APOLLO AMERICA INC PAM-1 2088-9021 RSIMPLEXR 4H RELAY IDNET 2 IAM W/T SENSE 4090-9118 M RSIMPLEXAIO 2 MAX CONDUCTOR AREA CONDUIT SIZE 1/2" 3/4" 1" 0.12 SQ INCH * 0.21 SQ INCH * 0.34 SQ INCH * 1-1/4" 1-1/2" 2" 0.60 SQ INCH * 0.82 SQ INCH * 1.34 SQ INCH * NOTES *40% FILL PER N.E.C. SUBSCRIPT "u": UNSHIELDED CABLES MIXED WITH SHIELDED CABLES OF SAME CIRCUIT DESIGNATION. MAX CONDUCTOR AREA CONDUIT SIZE FPLPTFFNCIRCUIT DESCRIPTION ACCEPTABLE CABLE TYPES CONSTRUCTION GAUGE CIRCUIT PROPERTIES OUTDOORFPLRC.I.THHNFIRE ALARM WIRE LIST 18 AWG X M IDNET UTP SOLID X 14 AWG X XP POWER 2 COND. SOLID X 14 AWG X XR RELAY 2 COND. SOLID X 0 4' 8' 16' SCALE:IN FEET1/8" = 1'-0" N SCALE: 1/8" = 1'-0" 7TH FLOOR - PARTIAL FLOOR PLAN DEVICE PLACEMENT GENERAL NOTES: 1. INFORMATION AND SYMBOLS SHOWN AS BOLD LINETYPE ARE NEW. 2. INFORMATION AND SYMBOLS SHOWN AS LIGHT LINETYPE ARE EXISTING. 3. (RR) = APPLIANCE TO BE REMOVED AND REPLACED WITH NEW. 4. HATCHED INFORMATION IS NOT WITHIN SCOPE OF CONTRACT. KEYNOTES: REMOVE EXISTING SMOKE AND HEAT DETECTOR ON TOP OF SHAFT AND REPLACE WITH NEW ADDRESSABLE SMOKE AND HEAT DETECTOR. TIE INTO IDNET "M2" CIRCUIT.1 LAST PRINTED:LAST SAVED BY:FILE PATH: G:\Lodge at Vail - 174 E Gore Creek-Vail\Building F - Lodge Tower - 200 Vail Rd\12 - Lodge Tower East Elev. #1 Upgrade - 2018 - 608831101\Fire\FA-101.dwg9/28/2018 9:59:27 AMJ JODEA3 419:608831101 J. EVANS D. JOHNSON 9/24/18 FIRE ALARM SYSTEMLODGE TOWER200 VAIL ROADVAIL, CO 8165714200 E. EXPOSITION AVEAURORA, CO 80012PHONE: 303-355-0500 SERVICE: 303-355-0500FAX: 303-355-0615DISTRICT - 419FA-101 DEVICE PLACEMENT PLAN & PARTIAL RISER DIAGRAM JOHNSON CONTROLS © 2018LODGE TOWER - BUILDING FEAST ELEVATOR UPGRADE© Johnson Controls 2018. All rights reserved. Reuse, copying, modification or alteration of the drawings and other information contained herein is strictly prohibited. 1 SCALE: N.T.S KEY PLAN - 7TH FLOORN NOT IN SCOPE OF WORK SCOPE OF WORK SCALE: N.T.S 7TH FLOOR - PARTIAL RISER DIAGRAM NICET CERTIFICATION 9/24/2018 NOT IN SCOPE OF WORK Vail Fire & Emergency Services 10/04/18 CHECKED BY:DESCRIPTION CAD DATE MARK SYSTEM:CHKISSUE DATE: SHEET: DRAWN BY: JOB #: PROJECT #:24" x 36" - Arch D Size ISSUE LOG:Revisions shown with # symbolLAST PRINTED:LAST SAVED BY:FILE PATH: G:\Lodge at Vail - 174 E Gore Creek-Vail\Building F - Lodge Tower - 200 Vail Rd\12 - Lodge Tower East Elev. #1 Upgrade - 2018 - 608831101\Fire\FA-601.dwg9/28/2018 10:07:22 AMJ JODEA3 419:608831101 J. EVANS D. JOHNSON 9/24/18 FIRE ALARM SYSTEMLODGE TOWER200 VAIL ROADVAIL, CO 8165714200 E. EXPOSITION AVEAURORA, CO 80012PHONE: 303-355-0500 SERVICE: 303-355-0500FAX: 303-355-0615DISTRICT - 419FA-601 CALCULATIONS JOHNSON CONTROLS © 2018LODGE TOWER - BUILDING FEAST ELEVATOR UPGRADE© Johnson Controls 2018. All rights reserved. Reuse, copying, modification or alteration of the drawings and other information contained herein is strictly prohibited. SCALE: ############ CALCULATIONS NICET CERTIFICATION 9/24/2018 SCALE: N.T.S IDNET DESCRIPTIONS LODGE TOWER UPGRADE 4100es FACP Standby Total Alarm Total Module Qty Description Current Standby Current Alarm Panel Equipment 4100-7153 1 INFOALARM 4100U UPGRADE 0.0820 0.0820 0.1270 0.1270 4100-0110 2 MAPNET II ADDRESSABLE MODULE * 0.2700 0.5400 0.2900 0.5800 4100-3107 1 IDNET+ MODULE, UP TO 250 POINTS * 0.0750 0.0750 0.1150 0.1150 4100-4321 3 6 CIRCUIT CLASS B (STYLE Y) 0.0250 0.0750 0.0700 0.2100 4100-7401 1 24 POINT I/O INTERFACE MODULE 0.0780 0.0780 0.0780 0.0780 4100-5125 1 REMOTE POWER SUPPLY W/CHARGER - 120VAC 0.1500 0.1500 0.1850 0.1850 4100-9620 1 BASIC AUDIO WITH MICROPHONE - ANALOG 0.2250 0.2250 0.2250 0.2250 4100-6052 1 EVENT REPORTING DACT 0.0300 0.0300 0.0400 0.0400 4100-6038 1 DUAL RS-232 IF CARD 0.1320 0.1320 0.1320 0.1320 4100-1326 1 DIGITAL FLEX 50W AMP W/3 NACS - 25V 0.0850 0.0850 2.2700 2.2700 4100-1294 1 LED/SWITCH SLIDE-IN LABEL KIT 0.0000 0.0000 0.0000 0.0000 4100-6079 1 SAFELINC INTERNET INTRFACE 0.1450 0.1450 0.1450 0.1450 4100-1293 1 PANEL MOUNTED PRINTER 0.1250 0.1250 0.8000 0.8000 4100-1288 1 64/64 LED/SWITCH CONTROLLER 0.0200 0.0200 0.0200 0.0200 4100-1252 1 1 CHANNEL AUDIO OPERATOR INTERFACE 0.0000 0.0000 0.0240 0.0240 4100-1241 1 MESSAGE EXPANSION BOARD - 8 MINUTES 0.0020 0.0020 0.0170 0.0170 Panel Totals 1.7640 4.9680 IDNet Addressable Devices (SLC) 4099-9004 14 ADDRESSABLE SINGLE ACTION MANUAL STATION * Constant current draw of .8mA standby and 1mA alarm per address used. Devices requiring additional current are accounted for in the section labeled "Miscellaneous Peripheral Devices Requiring Additional System Power". 4090-9001 29 IDNET SUPERVISED IAM * 4090-9002 6 IDNET RELAY IAM * 4090-9118 2 RELAY IDNET 2 IAM W/T SENSE * 4098-9714 81 TRUEALARM PHOTO SMOKE SENSOR 4098-9733 6 TRUEALARM HEAT SENSOR 4009-9201 1 4009 IDNET NAC EXTENDER, 120 VAC * 4098-9792 65 TRUEALARM SENSOR BASE * 4098-9794 11 TRUEALARM SENSOR SOUNDER BASE * 4098-9773 10 TRUEALARM 520HZ SOUNDER BASE W/ CO MOD, REM LED * 4098-9771 1 TRUEALARM SOUNDER BASE W/ CO MODULE * Mapnet Addressable Devices (SLC) 2190-9163 13 MAPNET UNSUPERVISED CONTROL ZAM * 2190-9172 83 MAPNET SUPERVISED IAM * 2099-9795 10 MAPNET SINGLE ACTION PULL STATION * 4098-9714 40 TRUEALARM PHOTO SMOKE SENSOR 4098-9733 13 TRUEALARM HEAT SENSOR 4098-9756 1 TRUEALARM DUCT SMOKE SENSOR W/ RELAY OUTPUT * 4098-9792 53 TRUEALARM SENSOR BASE * Miscellaneous Peripheral Devices That Require (Additional) System Power 4098-9843 1 ENCAPSULATED RELAY PAM-SD 0.0000 0.0000 0.0150 0.0150 4098-9756 1 TRUEALARM DUCT SMOKE SENSOR W/ RELAY OUTPUT 0.0030 0.0030 0.0150 0.0150 4098-9794 11 TRUEALARM SENSOR SOUNDER BASE 0.0000 0.0000 0.0200 0.2200 4098-9771 1 TRUEALARM SOUNDER BASE W/ CO MODULE 0.0000 0.0000 0.0170 0.0170 2190-9163 13 MAPNET UNSUPERVISED CONTROL ZAM 0.0100 0.1300 0.0400 0.5200 4098-9773 10 TRUEALARM 520HZ SOUNDER BASE W/ CO MOD, REM LED 0.0000 0.0000 0.1390 1.3900 2088-9021 4 ENCAPSULATED RELAY PAM-1 0.0000 0.0000 0.0150 0.0600 Notification Appliances Setting MTWP-2475W-FR 1 MULTI TONE, BELL SETTING BELL 0.0000 0.0000 0.0530 0.0530 Peripheral Totals 0.1330 2.2900 Added Current for EPS Conversion of 24 to 29 Volt IDNac Devices 0.0000 0.0000 RUI Totals 0 0.0000 0.0000 Address Totals 340.5 Addresses 0.4538 0.4816 * Device Address current draw included below (See Additional Current Draws): System Totals*: Standby 2.3508 Alarm 7.7396 2. Backup Amplifier assumes Main Amplifier alarm current on failure. Standby Standby Alarm Alarm Battery Set #1 (Cabinet/Charger #1) Current Total Current Total Select ALL Power Supplies on this battery set: RPS-1 1.8970 7.2580 Sub Total 1.8970 7.2580 Additional Current Draws: MAPNET/IDNet Device Address Communication Current 341 x 0.001333 = 0.4538 x 0.001414 = 0.4816 Sub Total 2.3508 7.7396 Spare addressable point capacity 20% 69 x 0.001333 = 0.0919 x 0.001414 = 0.0976 Total 2.4427 7.8372 Standby Time = 24 Hrs x 2.4427 = 58.6248 Standby Ah Alarm Time = 15 Min 0.25 x 7.8372 = 1.9593 Alarm Ah 60.5841 Additional Spare Battery Capacity = 20% + 12.1168 72.7009 Battery Discharge Factor = 20% + 14.5402 Minimum Battery Required 2081-9279 110AH (2x) 87.2411 Battery Supplied 2081-9279 110AH (2x) * System Totals represent total system current requirements. Those currents may be distributed between multiple battery sets or power supplies as shown above. SCALE: N.T.S FACP BATTERY CALCULATIONS IDNET CHANNEL M2 ADDRESSES IN USE: 159 (63.6%) | SPARE ADDRESSES: 91 (36.4%) SWITCH SETTINGS Address Device Type Point Type Location Description 1 9 M2-1 PHOTO VSMOKE M2-1 1ST FLR W RESIDENTIAL CORRIDOR X ON M2-2 PHOTO VSMOKE M2-2 1ST FLR MID W RESIDENTIAL CORRIDOR X ON M2-3 PHOTO VSMOKE M2-3 1ST FLR MID W RESIDENTIAL CORRIDOR X X ON M2-4 PHOTO VSMOKE M2-4 1ST FLR MID RESIDENTIAL CORRIDOR X ON M2-5 PHOTO VSMOKE M2-5 1ST FLR MID ELEVATOR LOBBY X X ON M2-6 PHOTO VSMOKE M2-6 1ST FLR MID RESIDENTIAL CORRIDOR X X ON M2-7 PHOTO VSMOKE M2-7 1ST FLR EAST RESIDENTIAL CORRIDOR X X X ON M2-8 PHOTO VSMOKE M2-8 1ST FLR E ELEVATOR LOBBY X ON M2-9 ADRPUL PULL M2-9 1ST FLR WEST X X ON M2-10 PHOTO VSMOKE M2-10 2ND FLR W RESIDENTIAL CORRIDOR X X ON M2-11 PHOTO VSMOKE M2-11 2ND FLR MID W RESIDENTIAL CORRIDOR X X X ON M2-12 PHOTO VSMOKE M2-12 2ND FLR MID W RESIDENTIAL CORRIDOR X X ON M2-13 PHOTO VSMOKE M2-13 2ND FLR MID RESIDENTIAL CORRIDOR X X X ON M2-14 PHOTO VSMOKE M2-14 2ND FLR MID ELEVATOR LOBBY X X X ON M2-15 PHOTO VSMOKE M2-15 2ND FLR MID RESIDENTIAL CORRIDOR X X X X ON M2-16 PHOTO VSMOKE M2-16 2ND FLR EAST RESIDENTIAL CORRIDOR X ON M2-17 PHOTO VSMOKE M2-17 2ND FLR E ELEVATOR LOBBY X X ON M2-18 ADRPUL PULL M2-18 2ND FLR WEST X X ON M2-19 SPARE X X X ON M2-20 PHOTO VSMOKE M2-20 3RD FLR W RESIDENTIAL CORRIDOR X X ON M2-21 PHOTO VSMOKE M2-21 3RD FLR MID W RESIDENTIAL CORRIDOR X X X ON M2-22 PHOTO VSMOKE M2-22 3RD FLR MID W RESIDENTIAL CORRIDOR X X X ON M2-23 PHOTO VSMOKE M2-23 3RD FLR MID RESIDENTIAL CORRIDOR X X X X ON M2-24 PHOTO VSMOKE M2-24 3RD FLR MID ELEVATOR LOBBY X X ON M2-25 PHOTO VSMOKE M2-25 3RD FLR MID RESIDENTIAL CORRIDOR X X X ON M2-26 PHOTO VSMOKE M2-26 3RD FLR EAST RESIDENTIAL CORRIDOR X X X ON M2-27 PHOTO VSMOKE M2-27 3RD FLR E ELEVATOR LOBBY X X X X ON M2-28 ADRPUL PULL M2-28 3RD FLR WEST X X X ON M2-29 SPARE X X X X ON M2-30 PHOTO VSMOKE M2-30 4TH FLR W RESIDENTIAL CORRIDOR X X X X ON M2-31 PHOTO VSMOKE M2-31 4TH FLR MID W RESIDENTIAL CORRIDOR X X X X X ON M2-32 PHOTO VSMOKE M2-32 4TH FLR MID W RESIDENTIAL CORRIDOR X ON M2-33 PHOTO VSMOKE M2-33 4TH FLR MID RESIDENTIAL CORRIDOR X X ON M2-34 PHOTO VSMOKE M2-34 4TH FLR MID ELEVATOR LOBBY X X ON M2-35 PHOTO VSMOKE M2-35 4TH FLR MID RESIDENTIAL CORRIDOR X X X ON M2-36 PHOTO VSMOKE M2-36 4TH FLR EAST RESIDENTIAL CORRIDOR X X ON M2-37 PHOTO VSMOKE M2-37 4TH FLR E ELEVATOR LOBBY X X X ON M2-38 ADRPUL PULL M2-38 4TH FLR WEST X X X ON M2-39 SPARE X X X X ON M2-40 PHOTO VSMOKE M2-40 5TH FLR W RESIDENTIAL CORRIDOR X X ON M2-41 PHOTO VSMOKE M2-41 5TH FLR MID W RESIDENTIAL CORRIDOR X X X ON M2-42 PHOTO VSMOKE M2-42 5TH FLR MID W RESIDENTIAL CORRIDOR X X X ON M2-43 PHOTO VSMOKE M2-43 5TH FLR MID RESIDENTIAL CORRIDOR X X X X ON M2-44 PHOTO VSMOKE M2-44 5TH FLR MID ELEVATOR LOBBY X X X ON M2-45 PHOTO VSMOKE M2-45 5TH FLR MID RESIDENTIAL CORRIDOR X X X X ON M2-46 PHOTO VSMOKE M2-46 5TH FLR EAST RESIDENTIAL CORRIDOR X X X X ON M2-47 PHOTO VSMOKE M2-47 5TH FLR E ELEVATOR LOBBY X X X X X ON M2-48 ADRPUL PULL M2-48 5TH FLR WEST X X ON M2-49 SPARE X X X ON M2-50 PHOTO VSMOKE M2-50 6TH FLR W RESIDENTIAL CORRIDOR X X X ON M2-51 PHOTO VSMOKE M2-51 6TH FLR MID W RESIDENTIAL CORRIDOR X X X X ON M2-52 PHOTO VSMOKE M2-52 6TH FLR MID W RESIDENTIAL CORRIDOR X X X ON M2-53 PHOTO VSMOKE M2-53 6TH FLR MID RESIDENTIAL CORRIDOR X X X X ON M2-54 PHOTO VSMOKE M2-54 6TH FLR MID ELEVATOR LOBBY X X X X ON M2-55 PHOTO VSMOKE M2-55 6TH FLR MID RESIDENTIAL CORRIDOR X X X X X ON M2-56 PHOTO VSMOKE M2-56 6TH FLR EAST RESIDENTIAL CORRIDOR X X X ON M2-57 PHOTO VSMOKE M2-57 6TH FLR E ELEVATOR LOBBY X X X X ON M2-58 ADRPUL PULL M2-58 6TH FLR WEST X X X X ON M2-59 SPARE X X X X X ON M2-60 PHOTO VSMOKE M2-60 7TH FLR W RESIDENTIAL CORRIDOR X X X X ON M2-61 PHOTO VSMOKE M2-61 7TH FLR MID W RESIDENTIAL CORRIDOR X X X X X ON M2-62 PHOTO VSMOKE M2-62 7TH FLR MID W RESIDENTIAL CORRIDOR X X X X X ON M2-63 PHOTO VSMOKE M2-63 7TH FLR MID RESIDENTIAL CORRIDOR X X X X X X ON M2-64 PHOTO VSMOKE M2-64 7TH FLR MID ELEVATOR LOBBY X ON M2-65 PHOTO VSMOKE M2-65 7TH FLR MID RESIDENTIAL CORRIDOR X X ON M2-66 PHOTO VSMOKE M2-66 7TH FLR EAST RESIDENTIAL CORRIDOR X X ON M2-67 SPARE X X X ON M2-68 ADRPUL PULL M2-68 7TH FLR WEST X X ON M2-69 SPARE X X X ON M2-70 ADRPUL PULL M2-70 1ST FLR EAST X X X ON M2-71 ADRPUL PULL M2-71 2ND FLR EAST X X X X ON M2-72 ADRPUL PULL M2-72 3RD FLR EAST X X ON M2-73 ADRPUL PULL M2-73 4TH FLR EAST X X X ON M2-74 ADRPUL PULL M2-74 5TH FLR EAST X X X ON M2-75 ADRPUL PULL M2-75 6TH FLR EAST X X X X ON M2-76 ADRPUL PULL M2-76 7TH FLR EAST X X X ON M2-77 SPARE X X X X ON M2-78 SPARE X X X X ON M2-79 NAC8PT SIGNAL M2-81 GARAGE NAC PANEL #1 X X X X X ON M2-80 IAM HEAT M2-80 GARAGE X X ON M2-81 IAM HEAT M2-81 GARAGE X X X ON M2-82 IAM HEAT M2-82 GARAGE X X X ON M2-83 IAM HEAT M2-83 GARAGE X X X X ON M2-84 IAM HEAT M2-84 GARAGE X X X ON M2-85 IAM HEAT M2-85 GARAGE X X X X ON M2-86 IAM HEAT M2-86 GARAGE X X X X ON M2-87 IAM HEAT M2-87 GARAGE X X X X X ON M2-88 IAM HEAT M2-88 GARAGE X X X ON M2-89 IAM HEAT M2-89 GARAGE X X X X ON M2-90 IAM HEAT M2-90 GARAGE X X X X ON M2-91 IAM HEAT M2-91 GARAGE X X X X X ON M2-92 IAM HEAT M2-92 GARAGE X X X X ON M2-93 IAM HEAT M2-93 GARAGE X X X X X ON M2-94 IAM HEAT M2-94 GARAGE X X X X X ON M2-95 IAM HEAT M2-95 GARAGE X X X X X X ON M2-96 IAM HEAT M2-96 GARAGE X X ON M2-97 IAM HEAT M2-97 SOUTH GARAGE STORAGE CLOSET #507 X X X ON M2-98 IAM HEAT M2-98 SOUTH GARAGE STORAGE CLOSET #537 X X X ON M2-99 IAM HEAT M2-99 SOUTH GARAGE STORAGE CLOSET #538 X X X X ON M2-100 IAM HEAT M2-100 SOUTH GARAGE STORAGE CLOSET #539 X X X ON M2-101 SPARE X X X X ON M2-102 IAM HEAT M2-102 GARAGE X X X X ON M2-103 IAM HEAT M2-103 GARAGE X X X X X ON M2-104 IAM HEAT M2-104 GARAGE X X X ON M2-105 IAM HEAT M2-105 GARAGE X X X X ON M2-106 IAM HEAT M2-106 GARAGE X X X X ON M2-107 PHOTO VSMOKE M2-107 EAST ELEVATOR LOBBY X X X X X ON M2-108 IAM HEAT M2-108 SOUTH PARKING GARAGE X X X X ON M2-109 IAM HEAT M2-109 SOUTH GARAGE STORAGE CLOSET #506 X X X X X ON M2-110 IAM HEAT M2-110 SOUTH GARAGE STORAGE CLOSET #207 X X X X X ON M2-111 SPHOTO LATSUPV M2-111 UNIT 777 HALLWAY X X X X X X ON ON M2-112 SPHOTO LATSUPV M2-112 UNIT 777 LIVING ROOM X X X ON ON M2-113 SPHOTO LATSUPV M2-113 UNIT 777 BED ROOM 1 X X X X ON ON M2-114 SPHOTO LATSUPV M2-114 UNIT 777 BED ROOM 2 X X X X ON ON M2-115 SPHOTO LATSUPV M2-115 UNIT 777 BED ROOM 3 X X X X X ON ON M2-116 MCOPS SUPERV M2-116 7TH FL UNIT 787 BED ROOM 3 X X X X ON ON M2-117 MCOPS SUPERV M2-117 7TH FL UNIT 787 LIVING ROOM X X X X X ON ON M2-118 MCOPS SUPERV M2-118 7TH FL UNIT 787 KITCHEN X X X X X ON ON M2-119 MCOPS SUPERV M2-119 7TH FL UNIT 787 ENTRY/HALL X X X X X X ON ON M2-120 MCOPS SUPERV M2-120 7TH FL UNIT 787 BED ROOM 2 X X X X ON ON M2-121 TRIAM UTILITY M2-121 ELEV 2 SHUNT TRIP/MONITOR X X X X X ON M2-122 RIAM PRIMARY M2-122 ELEV 2 PRIMARY RECALL X X X X X ON M2-123 RIAM ALTERN M2-123 ELEV 2 ALTERNATE RECALL X X X X X X ON M2-124 RIAM RELAY M2-124 ELEV 2 FF HAT LITE X X X X X ON M2-125 PHOTO SMOKE M2-125 7TH FL ELEV 2 TOP OF SHAFT X X X X X X ON NOTE: THE LABELS SHOWN ABOVE WILL BE USED FOR PROGRAMMING PURPOSES. ANY CHANGES TO THESE LABELS MUST BE NOTED ON THE SUBMITTAL REVIEW, PRIOR TO PROGRAMMING. POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES. IDNET CHANNEL M2 ADDRESSES IN USE: 159 (63.6%) | SPARE ADDRESSES: 91 (36.4%) SWITCH SETTINGS Address Location Description 1 9 M2-126 SPHOTO SMOKE M2-126 4TH FL UNIT 499 BUNKROOM X X X X X X ON ON M2-127 SPHOTO SMOKE M2-127 4TH FL UNIT 499 BEDROOM 2 X X X X X X X ON ON M2-128 SPHOTO SMOKE M2-128 4TH FL UNIT 499 BEDROOM 1 X ON ON M2-129 SPHOTO SMOKE M2-129 4TH FL UNIT 499 MASTER SUITE X X ON ON M2-130 SPHOTO SMOKE M2-130 4TH FL UNIT 499 CORRIDOR EAST X X ON ON M2-131 SPHOTO SMOKE M2-131 4TH FL UNIT 499 CORRIDOR WEST X X X ON ON M2-132 MCOPS FIRE M2-132 4TH FL UNIT 499 LIVING ROOM X X ON ON M2-133 MCOPS SUPERV M2-133 6TH FL UNIT 677 ENTRY/MUD 100 X X X ON ON M2-134 MCOPS SUPERV M2-134 6TH FL UNIT 677 LIVING/DINING 102 X X X ON ON M2-135 MCOPS SUPERV M2-135 6TH FL UNIT 677 MSTR 103 X X X X ON ON M2-136 MCOPS SUPERV M2-136 6TH FL UNIT 677 BEDROOM 2 X X ON ON M2-137 MCOPS SUPERV M2-137 6TH FL UNIT 677 BEDROOM 3 X X X ON ON M2-138 SPARE X X X ON M2-139 SPARE X X X X ON M2-140 PHOTO SMOKE M2-140 7TH FL ELEV 1 TOP OF SHAFT X X X ON M2-141 HEAT HEAT M2-141 7TH FL ELEV 1 TOP OF SHAFT 2-141 X X X X ON M2-142 HEAT HEAT M2-142 HEAT IN ELEC. MACHINE RM 2-142 X X X X ON M2-143 HEAT HEAT M2-143 HEAT IN ELEC. MACHINE RM 2-143 X X X X X ON M2-144 HEAT HEAT M2-144 HEAT IN ELEC. MACHINE RM 2-144 X X ON M2-145 HEAT HEAT M2-145 HEAT IN ELEC. MACHINE RM 2-145 X X X ON M2-146 TRIAM UTILITY M2-146 ELEV 1 SHUNT TRIP/MONITOR 2-146 X X X ON M2-147 RIAM PRIMARY M2-147 ELEV 2 PRIMARY RECALL 2-147 X X X X ON M2-148 RIAM ALTERN M2-148 ELEV 2 ALTERNATE RECALL 2-148 X X X ON M2-149 RIAM RELAY M2-149 ELEV 2 FF HAT LITE 2-149 X X X X ON M2-154 PHOTO SMOKE M2-150 7TH FL ELEV 2 MECH. ROOM 2-154 X X X X ON M2-155 HEAT HEAT M2-155 7TH FL ELEV 2 MECH. ROOM 2-155 X X X X X ON THRU ON M2-250 SPARE X X X X X X ON NOTE: THE LABELS SHOWN ABOVE WILL BE USED FOR PROGRAMMING PURPOSES. ANY CHANGES TO THESE LABELS MUST BE NOTED ON THE SUBMITTAL REVIEW, PRIOR TO PROGRAMMING. POINTS SHOWN IN ITALIC TEXT REFER TO EXISTING DEVICES. Vail Fire & Emergency Services 10/04/18 CHECKED BY:DESCRIPTION CAD DATE MARK SYSTEM:CHKISSUE DATE: SHEET: DRAWN BY: JOB #: PROJECT #:24" x 36" - Arch D Size ISSUE LOG:Revisions shown with # symbolLAST PRINTED:LAST SAVED BY:FILE PATH: G:\Lodge at Vail - 174 E Gore Creek-Vail\Building F - Lodge Tower - 200 Vail Rd\12 - Lodge Tower East Elev. #1 Upgrade - 2018 - 608831101\Fire\FA-701.dwg9/28/2018 10:05:01 AMJ JODEA3 419:608831101 J. EVANS D. JOHNSON 9/24/18 FIRE ALARM SYSTEMLODGE TOWER200 VAIL ROADVAIL, CO 8165714200 E. EXPOSITION AVEAURORA, CO 80012PHONE: 303-355-0500 SERVICE: 303-355-0500FAX: 303-355-0615 DISTRICT - 419FA-701 WIRING TYPICALS JOHNSON CONTROLS © 2018LODGE TOWER - BUILDING FEAST ELEVATOR UPGRADE© Johnson Controls 2018. All rights reserved. Reuse, copying, modification or alteration of the drawings and other information contained herein is strictly prohibited. CLASS B WIRING 1. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. 2. ALWAYS CUT CONDUCTORS AND SECURE UNDER TERMINALS. NEVER LOOP WIRES UNDER TERMINALS. 3. ANY WIRE SPLICES TO BE MADE BY LISTED AND AHJ APPROVED METHODS. WIRING NOTES IDNet SLC (-) (+) (-) (+) STANDARD SENSOR BASE (-) (+) OPTIONAL TAP LOCATION FOR IDNet SLC T-TAP (SPLICE) CONNECTION SERIES CONNECTION IDNet SLC TERMINATION VIEW: DEVICE REAR SENSOR BASE SMOKE SENSOR HEAT SENSOR 3' (941mm) MIN. WALL 4" (102mm) CEILING MOUNTED SENSOR HEAT SENSORS NEVER HERE 12"(305mm) MAXIMUM TO TOP OF SENSOR FINISHED WALL WALL MOUNTED SENSOR MOUNTING OPTION "B" SIMPLEX 4098-9792 1. FOR ADDITIONAL MOUNTING OPTIONS, DOWNLOAD DATA SHEET 4098-0019 FROM HTTP://WWW.SIMPLEX-FIRE.COM MOUNTING OPTIONS OPTION 1 DESCRIPTION NOTE A SINGLE GANG BOX, 2-1/8" (54mm) DEEP BY OTHERS B 4" (102mm) SQUARE BOX, 1-1/2" DEEP (MIN) W/ SINGLE GANG COVER PLATE 3/4" (19mm) EXTENSION BY OTHERS C 4" (102mm) OCTAGONAL BOX, 1-1/2" (38mm) DEEP, MINIMUM BY OTHERS D 4" (102mm) SQUARE BOX, 1-1/2" DEEP (MIN) W/ SIMPLEX 4098-9832 ADAPTER KIT BOX BY OTHER, 4098-9832 ORDERED SEPARATELY CLASS B WIRING (-) ADDRESSABLE RELAY MODULE SERIES CONNECTION IDNet SLC (+) IDNet SLC TERMINATION VIEW N.C. MOUNTING OPTION "B" 4"(102mm) SQUARE BOX 4090-9002 RELAY IAM COVER PLATE SIMPLEX 4090-9002 1. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. 2. ALWAYS CUT CONDUCTORS AND SECURE UNDER TERMINALS. NEVER LOOP WIRES UNDER TERMINALS. 3. ANY WIRE SPLICES TO BE MADE BY LISTED AND AHJ APPROVED METHODS. WIRING NOTES (-) (-) OPTIONAL 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 C N.O. 1. FOR ADDITIONAL MOUNTING OPTIONS, DOWNLOAD DATA SHEET 4090-0002 FROM HTTP://WWW.SIMPLEX-FIRE.COM (+) (+) OPTIONAL TAP LOCATION FOR IDNet SLC T-TAP (SPLICE) CONNECTION TO CONTROLLED DEVICE. SEE DATA SHEET FOR POWER RATING LIMITATIONS. MOUNTING OPTIONS OPTION 1 DESCRIPTION NOTE A 4" (102mm) SQUARE BOX, 2-1/8" MINIMUM DEPTH WITH DOUBLE GANG COVER PLATE BY OTHERS B 4" (102mm) SQUARE BOX, 2-1/8" MINIMUM DEPTH WITH SIMPLEX 4090-9801 TRIM PLATE FOR SEMI-FLUSH MOUNTED BOX BOX BY OTHERS, PLATES ORDERED SEPARATELY C 4" (102mm) SQUARE BOX, 2-1/8" MINIMUM DEPTH WITH SIMPLEX 4090-9802 TRIM PLATE FOR SURFACE MOUNTED BOX BOX BY OTHERS, PLATES ORDERED SEPARATELY COVER PLATE SUPPLIED BY ELECTRICAL CONTRACTOR BLU YEL ORG C N.C. N.O. WHT RED (+) (-) 2088-9021 PAM-1 RELAY 10.0 AMP CONTACTS RED WHT COIL VOLTAGE 1. MAINTAIN CORRECT POLARITY ON CONNECTIONS. 2. ANY WIRE SPLICES TO BE MADE BY LISTED AND AHJ APPROVED METHODS. CLASS B APPLICATIONS ONLY. WIRING NOTES FOR ADDITIONAL DETAILS SEE DATA SHEET 2088-0010 ON HTTP://WWW.SIMPLEX-FIRE.COM ANY SINGLE GANG ELECTRICAL BOX SUPPLIED BY ELECTRICAL CONTRACTOR MULTI-VOLTAGE RELAY SIMPLEX 2088-9021 / APOLLO AMERICA PAM-1 WIRING NOTES 12 34 IDNet SLC (-) (+) (-) (+) (-) 34 733-896 (4.7K 1/2W) ELECTRICAL BOX MOUNTING OPTION "B" IAM MOUNTING BRACKET CLASS B WIRING 1. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. 2. ALWAYS CUT CONDUCTORS AND SECURE UNDER TERMINALS. NEVER LOOP WIRES UNDER TERMINALS. 3. ANY WIRE SPLICES TO BE MADE BY LISTED AND AHJ APPROVED METHODS. 1. FOR ADDITIONAL MOUNTING OPTIONS, DOWNLOAD DATA SHEET 4090-0001 FROM HTTP://WWW.SIMPLEX-FIRE.COM ADDRESSABLE INPUT MODULE (+) OPTIONAL TAP LOCATION FOR IDNet SLC 12 T-TAP (SPLICE) CONNECTION SERIES CONNECTION IDNet SLC TERMINATION VIEW: DEVICE REAR 733-886 (6.8K 1/2W) 733-984 (1.8K 1/2W) 4090-9001 IAM TRIM PLATE SIMPLEX 4090-9001 (IAM) MOUNTING OPTIONS OPTION 1 DESCRIPTION NOTE A SINGLE GANG BOX, 2-1/2" (64mm) DEEP WITH SINGLE GANG COVER PLATE BY OTHERS B SINGLE GANG BOX, 2-1/2" (64mm) DEEP WITH SIMPLEX 4090-9810 IAM MOUNTING BRACKET AND SIMPLEX 4090-9806 TRIM PLATE FOR SEMI-FLUSH MOUNTED BOX BOX BY OTHERS, PLATES ORDERED SEPARATELY C SINGLE GANG BOX, 2-1/2" (64mm) DEEP WITH SIMPLEX 4090-9810 IAM MOUNTING BRACKET AND SIMPLEX 4090-9807 TRIM PLATE FOR SURFACE MOUNTED BOX BOX BY OTHERS, PLATES ORDERED SEPARATELY SCALE: N.T.S WIRING TYPICALS 1. MAINTAIN CORRECT POLARITY ON TERMINAL CONNECTIONS. 2. ALWAYS CUT CONDUCTORS AND SECURE UNDER TERMINALS. NEVER LOOP WIRES UNDER TERMINALS. 3. ANY WIRE SPLICES TO BE MADE BY LISTED AND AHJ APPROVED METHODS. 4. T-SENSE INPUT CIRCUITS ARE NOT TO EXCEED 500 FEET. ONLY NORMALLY OPEN (N/O) DRY CONTACTS ARE ALLOWED ON THE INPUT CIRCUITS. IDNet SLC (-) (+) (+) (-) OPTIONAL TAP LOCATION FOR IDNet SLC SERIES CONNECTION IDNet SLC N.C. 1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8 TO CONTROLLED DEVICE. SEE DATA SHEET FOR POWER RATING LIMITATIONS. ELECTRICAL BOX 4090-9118 RELAY IAM COVER PLATE SIMPLEX 4090-9118 WITH T-SENSE CLASS B WIRING WIRING NOTES 1. FOR ADDITIONAL MOUNTING OPTIONS, DOWNLOAD DATA SHEET 4090-0007 FROM HTTP://WWW.SIMPLEX-FIRE.COM (-) (+) ADDRESSABLE RELAY MODULE T-TAP (SPLICE) CONNECTION TERMINATION VIEW C N.O. MOUNTING OPTION "B" 4.7K 1/2W (733-886) 1.8K 1/2W (733-984) SEE NOTE 4 MOUNTING OPTIONS OPTION 1 DESCRIPTION NOTE A 4" (102mm) SQUARE BOX, 2-1/8" MINIMUM DEPTH WITH DOUBLE GANG COVER PLATE. BY OTHERS B 4" (102mm) SQUARE BOX, 2-1/8" MINIMUM DEPTH WITH SIMPLEX 4090-9801 TRIM PLATE FOR SEMI-FLUSH MOUNTED BOX BOX BY OTHERS, PLATES ORDERED SEPARATELY C 4" (102mm) SQUARE BOX, 2-1/8" MINIMUM DEPTH WITH SIMPLEX 4090-9802 TRIM PLATE FOR SURFACE MOUNTED BOX BOX BY OTHERS, PLATES ORDERED SEPARATELY NICET CERTIFICATION 9/24/2018 Vail Fire & Emergency Services 10/04/18