Loading...
HomeMy WebLinkAboutAir Balance Report - Double Tree Hotel Vail CO - Mech Tech HVAC Inc .pdf HVAC SYSTEMS ANALYSIS 12/14/2017 AIR BALANCE REPORT PROJECT: Double Tree Hotel 2211 North Frontage Road Vail, CO 81657 CONTRACTOR: Mech Tech HVAC, Inc. 1805 Tebor Rd. Webster, NY 14580 ARCHITECT/ENGINEER: Baskerville 101 S. 15th St. Suite 200 Richmond, VA 23219 Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 1 Make: Gibson Model # 060C120C RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM RTU #1 1 8" CD Maid Market 500 515 505 2 8" CD GM Office 500 490 490 3 8" CD Work Area 525 480 490 4 8" CD Retail 75 85 80 5 255' Linear Lobby / Bar 400 390 395 Total: 2000 1960 1960 6 Pleum Return R1 1610 1570 1570 OA 390 390 390 Total 2000 1960 1960 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Final ResultsInitial Results Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 2 Make: Gibson Model # GR4G -090 RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM RTU #2 1 8" Linear Ball Room 105 95 105 2 8" Linear Ball Room 105 110 105 3 8" Linear Ball Room 105 105 95 4 8" Linear Ball Room 105 105 90 5 8" Linear Ball Room 105 115 100 6 8" Linear Ball Room 105 120 105 7 8" Linear Ball Room 105 115 110 8 8" Linear Ball Room 105 95 105 9 8" Linear Ball Room 105 75 95 10 8" Linear Ball Room 105 120 110 11 8" Linear Ball Room 105 115 115 12 8" Linear Ball Room 105 90 100 13 8" Linear Ball Room 105 125 115 14 8" Linear Ball Room 105 100 115 15 8" Linear Ball Room 105 90 100 16 8" Linear Ball Room 105 115 95 17 8" Linear Ball Room 105 120 105 18 8" Linear Ball Room 105 125 110 19 8" Linear Ball Room 105 80 85 20 8" Linear Ball Room 105 110 90 21 8" Linear Ball Room 105 65 90 22 8" Linear Ball Room 105 70 100 23 8" Linear Ball Room 105 95 115 24 8" Linear Ball Room 105 125 110 25 CD Meeting Storage 130 90 125 26 CD Pre Function 100 120 90 27 CD Pre Function 100 75 85 Total: 2850 2765 2765 28 Plenum Return R1 Ball Room 2100 2015 2015 OA 750 750 750 Total 2850 2765 2765 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 3 Make: Gibson Model # KG6RC-120C-20C RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM AHU-1 1 8" CD Ball Room 200 165 175 2 8" CD Ball Room 200 155 170 3 8" CD Ball Room 200 185 180 4 8" CD Ball Room 200 210 190 5 8" CD Ball Room 200 195 195 6 8" CD Ball Room 200 160 185 7 8" CD Ball Room 200 170 170 8 8" Linear Ball Room 100 90 95 9 8" Linear Ball Room 100 80 80 10 8" Linear Ball Room 100 100 85 11 8" Linear Ball Room 100 110 90 12 8" Linear Ball Room 100 105 100 13 8" Linear Ball Room 100 95 105 Total: 2000 1820 1820 14 20"x20" Filter Grille Lobby 900 820 820 15 20"x20" Filter Grille Lobby 900 800 800 OA 200 200 200 Total 2000 1820 1820 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 4 Make: Gibson Model # KG6RC-120C-20C RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM AHU-2 1 335" Linear Lobby / Bar 2000 1980 1980 Total: 2000 1980 1980 2 20"x20" Filter Grille Lobby 900 880 880 3 20"x20" Filter Grille Lobby 900 900 900 OA 200 200 200 Total 2000 1980 1980 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 5 Make: Trane Model # BCHC054E1A0A1B02E000000BA4EA200003DB0100 RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM AHU-3 1 8" CD Fitness Center 210 220 215 2 8" CD Fitness Center 210 210 215 3 6" CD Fitness Center 110 115 110 4 6" CD Fitness Center 110 125 115 5 6" CD Fitness Center 110 125 105 8 8" Linear Fitness Center 90 65 100 9 8" Linear Fitness Center 90 55 105 10 8" Linear Fitness Center 90 110 80 11 8" Linear Fitness Center 90 120 80 12 8" Linear Fitness Center 90 90 110 Total: 1200 1235 1235 13 22"x22" RAG Fitness Center 900 920 920 OA 300 315 315 Total 1200 1235 1235 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 6 Make: Addison Model # RCC154/HCC154 RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM AHU-5 1 VAV Boxes 3800 4170 4170 Total: 3800 4170 4170 Plenum Return R1 - - - OA 845 845 845 Total 845 845 845 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 7 Make: Price Model # SDV8 RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM VAV-1 1 10" CD Boardroom 250 275 255 2 10" CD Boardroom 250 230 250 Total: 500 505 505 Plenum Return R1 Boardroom - - - OA 100 100 100 Total 100 100 100 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 8 Make: Price Model # SDV8 RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM VAV-2 1 8" CD Meeting Room 190 175 180 2 8" CD Meeting Room 190 160 175 3 8" CD Meeting Room 185 225 200 4 8" CD Meeting Room 190 200 205 Total: 755 760 760 Plenum Return R1 Meeting Room - - - OA 150 150 150 Total 150 150 150 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 9 Make: Price Model # SDV8 RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM VAV-3 1 6" CD Office 1 65 75 75 2 6" CD Office 2 65 60 60 3 6" CD Office 3 65 60 60 4 6" CD Office 4 65 50 50 5 8" CD Reception 170 180 180 Total: 430 425 425 Plenum Return R1 - - - OA 90 90 90 Total 90 90 90 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 10 Make: Price Model # SDV8 RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM VAV-4 1 6" CD Storage 90 95 95 2 6" CD Break Room 95 90 90 3 6" CD Break Room 95 110 110 4 6" CD Break Room 95 100 100 Total: 375 395 395 Plenum Return R1 - - - OA 75 75 75 Total 75 75 75 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 11 Make: Price Model # SDV8 RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM VAV-5 1 8" CD Cooridor 170 160 160 2 8" CD Cooridor 175 180 180 3 6" CD Luggage Room 80 90 90 Total: 425 430 430 Plenum Return R1 - - - OA 85 85 85 Total 85 85 85 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name: Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 12 Make: Price Model # SDV8 RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM VAV-6 1 8" CD Men's Bathroom 210 220 220 2 8" CD M Employee Locker Room 105 100 100 3 8" CD M Employee Locker Room 105 95 95 Total: 420 415 415 Plenum Return R1 - - - OA 85 85 85 Total 85 85 85 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 13 Make: Price Model # SDV8 RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM VAV-7 1 8" CD Massage / Spa Waiting 160 110 150 2 6" CD Room 120 80 85 85 3 6" CD Room 121 80 110 85 4 6" CD Room 122 60 120 65 5 6" CD Room 123 60 40 60 6 6" CD Room 124 60 40 55 7 6" CD Hallway 40 40 45 Total: 540 545 545 Plenum Return R1 - - - OA 110 110 110 Total 110 110 110 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name: Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 14 Make: Price Model # SDV8 RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM VAV-8 1 12"x6" S grille Engineer Storage 310 325 325 Total: 310 325 325 Plenum Return R1 - - - OA 65 65 65 Total 65 65 65 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name: Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 15 Make: Price Model # SDV8 RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM VAV-9 1 8" CD Women's Bathroom 205 220 210 2 6" CD W Employee Locker Room 105 40 110 3 6" CD W Employee Locker Room 105 160 100 Total: 415 420 420 Plenum Return R1 - - - OA 85 85 85 Total 85 85 85 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 16 Make: Twin City Model # TL900S RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM EF-5 1 6" EAG Women's Bathroom 95 75 90 2 6" EAG Women's Bathroom 95 80 95 3 6" EAG W Employee Locker Room 95 80 95 4 6" EAG W Employee Locker Room 95 100 105 5 6" EAG Men's Bathroom 95 125 110 6 6" EAG Men's Bathroom 95 120 110 7 6" EAG M Employee Locker Room 95 100 90 8 6" EAG M Employee Locker Room 95 100 85 Total: 760 780 780 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 17 Make: Twin City Model # TL1500S RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM EF-6 1 12" EAG Men's Bathroom 450 475 475 2 12" EAG Women's Bathroom 450 445 445 Total: 900 920 920 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name:Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 18 Make: Twin City Model # DCRD150B RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM EF-7 1 Constant Volume Building Pressure Relief 1335 1340 1340 Total: 1335 1340 1340 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results Job Name: Double Tree Hotel Address: 2211 North Frontage Road Vail, CO 81657 Date: 12/14/2017 Sheet 19 Make: Twin City Model # BCRD240D RTU Outlet Area Design FPM FPM No. No. Code Served CFM Vel. CFM Vel. CFM EF-8 1 Variable Speed by Building Pressurization Controller Economizer Pressure Relief 5080 0 - 5080 0 - 5080 Total:5080 Remarks TEST EQUIPMENT: ALNOR ELECTRONIC BALOMETER, MODEL APM150 AIR DISTRIBUTION DATA SHEET Initial Results Final Results