HomeMy WebLinkAboutE17-0197 plans approved.pdfI: • Ln N .1 • -::c-.1.-~. P? _, ' 0 1-~ ~ I I 1 ~II 1 II -n 204 . I I I I! I I 33" . 22" 30" 21" / 12" ·12" l9" 30" All dimensions _size designations given are subject to verification on , job site and adjustment to fit job conditions. Mike _Laurie 2 --·~----,,.,,. PULL SQUARE CORNER CAB 2" OFF BACK V'v ,', I'-~ _r-q 01' .....\. I\.) I\.) ~ .....\. I\.) ~ ····-,NJ~---w w I 0 (J) .....\. 0 0 .i>-1~ I .....\. I\.) I\.) ~ 1\)1~ ~ 01 ' "'I~ °'· OJ I • N ·'::,~-1 w . . j "'~?~i ~ w ~-i I I\.) ~ .i>-1~ w (J) '\~ I----"'(j) This is an original design and must not be released or copied unless applicable fee has been paid or job order placed. :·, . v' o•,-1 Designed: 6/10/2017 ii Printed: 9/26/201 7 _j Ii I All Drawing#: 1 J~ca!(!_:_O 1/2" = 1'
Electrical load calculation for 955 Redsandstone unit B-2
General load
1181 sq. ft@ 3 v.a. per sq. ft.
2 small appliance circuits
dishwasher
laundry circuit
9,243 v.a. @ 100%
total
total general load
heat provided boiler
= 3,543 v.a. = 3,000 v.a.
= 1,200 v.a.
= 1,500 v.a.
9,243 v.a.
= 9,243 v.a.
9,243 v.a.
1,440 v.a.
9/27/17
10,683 v.a. @ 240 v. = 44.51 amps.
calculated load of 44.51 amps on existing 100 amp service.
scope of new work.
Lighting remodel of kitchen. Replace existing 300 watts of lighting with 112 watts of
high efficacy lighting, for an approximate . 78 amp. reduction in load.
[i7-DICi7