Loading...
HomeMy WebLinkAboutMeadow Lane Primary.pdf Short Circuit Calculation Single Phase iscConduit MAIN HOUSE Fault "X" Available Feeder Tye Wire Constant Volts "f" "N1" Isc at (2) 40 CCT 200A 10KAIC UTILITY 11 ,600 Size Steel PVC Type "C" # Sets Length L to L Factor multiplier Fault NEMA LOAD ERS METER 11 ,600 600 X AL 20093 1 80 240 0.3844 07221 8,376IN LOWER LEVVELEL LOCATED MECHANICAL ROOM A,B 8,376 " 4/0 X AL 11184 1 40 ' 240 0.2496 0.8002 6,703 PNL PNL A B Isc(L-L)=6,703A Isc(L-L)=6,703A 3#4/0 AL,#4 AL G-2"c 200/2 200/2 EXISTING PAD MOUNTED UTILITY I GARAGE EXTERIOR NEMA TRANSFORMER BY HOLY CROSS ENERGY (50 KVA) ALL-IN-ONE (CONFIRM TRANSFORMER SIZE PRIOR TO CONSTRUCTION) 0 400A 122 0/240V 1PH 3W 10 KAIC WITH 320A UTILITY METER T N. G 3#600 CU-3" PVC Isc(L-L)=8,376AX #4 CU TO Isc(L-L)=11,600A UFER GND #1/0 CU TO CWS ONE LINE DIAGRAM 1. ALL WORK SHOWN IS NEW. 0 %, FULL CONTACT % 4872 MEADOW LANE A.�'•0 REG/Si+++ ELECTRICAL Ilr • •• • �� PRIMARY RESIDENCE 0 if SYSTEMS f 1 `i�� B�G••Av •� So SYSTEMS PROJECT VAIL, CO. 81657 X52 Pl. 0 ���� �� / GREEN MTN. DWG TITLE ONE LINE DIAGRAM �t '•. i ELECT. CONSULT. PROJECT NO. SHEET 4POO . � 41 840 SOUTH TAFT ST. ++,;��� .� -' 10-09-18 18043 q LAKEWOOD, CO. 80228 DATE El j‘•ww:�•`� PHI 303-989-8016 bill-gmec@comcastnet REVISED SERVICE LOAD CALCULATON: 400A "ALL-IN-ONE" (OPTIONAL METHOD) PANEL A LOAD CALCULATION LIGHTING 5,388 S.F. @ 3VA/S.F.= 16,164 VA LIGHTING 5,388 S.F. @ 3VA/S.F.= 16,164 VA 6 SMALL APPLIANCE CCTS.© 1 ,500 VA EA.= 9,000 VA 6 SMALL APPLIANCE CCTS.© 1 ,500 VA EA.= 9,000 VA LAUNDRY CIRCUIT= 1 ,500 VA DISPOSAL= 1 ,200 VA DISHWASHER= 1 ,500 VA DISHWASHER= 1 ,500 VA DRYER= 5,000 VA DISPOSAL= 1 ,200 VA DISPOSAL= 1 ,200 VA MICROWAVE= 1 ,500 VA MICROWAVE= 1 ,500 VA RANGE= 12,000 VA RANGE= 12,000 VA REFRIG= 1 ,200 VA REFRIG= 1 ,200 VA RANGE HOOD= 600 VA RANGE HOOD= 600 VA TOTAL GENERAL LOAD= 44,364 VA HUMIDIFIER= 1 ,000 VA FIRST 10,000 VA @ 100%= 10,000 VA SNOW MELT PUMPS= 2,200 VA REMAINDER@ 40%= 13,746 VA FUTURE CAR CHARGER= 15,360 VA PANEL A LOAD= 23,746 VA= 99 AMPS TOTAL GENERAL LOAD= 68,224 VA FIRST 10,000 VA @ 100%= PANEL B LOAD CALCULATION 10,000 VA REMAINDER@ 40%= 23,290 VA LAUNDRY CIRCUIT= 1 ,500 VA HVAC LOAD= 8,676 VA @ 100%= 11 ,028 VA DRYER= 5,000 VA HUMIDIFIERS= 4,000 VA SERVICE LOAD = 44,318 VA= 186 AMPS SNOW MELT PUMPS= 2,200 VA TOTAL GENERAL LOAD= 8,500 VA @ 100%= 7,500 VA HVAC LOAD= 11 ,028 VA @ 100%= 11 ,028 VA FUTURE CAR CHARGER= 15,360 VA PANEL B LOAD= 33,888 VA= 141 AMPS -.�,� FULL CONTACT 4872 MEADOW LANE -;.�% GEST`+� ELECTRICAL • ��.� ::••����, SYSTEMS PROJECT PRIMARY RESIDENCE , , :, • �, VAIL, CO. 81657 i1.1114„,f 3 052 �� GREEN MTN, DWG TITLE ELECTRICAL LOAD CALCULATIONS • .S ELECT. CONSULT. k �� w%�'•••• •••• /I /J 840 SOUTH TAFT ST. PROJECT NO. SHEET /01,A `�� r�l LAKEWOOD, CD. 80228 DATE 10-09-18 18043 EI.2 v i f `�`-f..��•� PHI 303-989-8016 bill-gmec@corocast.net REVISED