HomeMy WebLinkAboutGentex Photoelectric System Smoke Detector GENTEX
CORPORATION
Photoelectric System 8000 /
Smoke Detector 8003
Applications
The Gentex 8000/8003 Series of photoelectric smoke detectors are SERIES
designed for commercial, industrial, residential and institutional
applications. The 8000/8003 is engineered to provide outstanding
performance wherever reliable fire protection is required.
The Gentex 8000/8003 Series provides an exclusive patented three •
position test feature that simulates a 0.85%and a 3.5%actual smoke I1I1I1l
condition, in full compliance with ANSI/UL 268 Standards for installation I'IIIII
per NFPA 72 and the International Codes (IBC/IFC/IRC).The test feature I
has the capability to let you know when maintenance is required.
•
A standard Form A dry relay contact for connection to the system initiating _
circuit and an auxiliary Form C dry relay contact is provided on all models
for use as remote annunciation as a releasing device. Other options
include reverse/local 90dBA solid-state piezo horns and 135°F (57.2°C)
fixed temperature self-restoring integral or isolated thermals to meet your
specific requirements. Easy Wash®-
The 8003 Series provides the temporal 3 evacuation tone as a standard On Site
feature.When testing the 8003 Series it may take up to 16 seconds longer ''
Maintenance
to go in or out of alarm.
Program
Standard Features Product Listings
• Available in 120VAC and 24VDC SIGNALING
• Listed for releasing device service •
• Horn frequency 3100 Hz (nominal)
• Temporal 3 evacuation sounding device (8003 Series) LISTED
• Patented three position test
• Nominal 2.5% sensitivity • ANSI/UL 268 Listed
• Easy Wash®on-site maintenance washing program • CSFM:7272-0569:102
• Form A/Form C dry relay contacts • MEA#928-84-SA
• Quick-disconnect wiring harness • MSFM Listing#1929
• 5-to-1 signal-to-noise ratio
• Pulsing LED sensing chamber Product Compliance
• Fully insect screened • NFPA 72
• Solid-state LED condition indicator • IBC/IFC/IRC
• Mounting hardware adapts to standard junction boxes • Quality Management System is certified to:
• Dust cover to prevent contamination during installation ISO 9001:2008
• Protective high air velocity gasket
• 24 month warranty from date of purchase
MEMBER
ASSEMBLED IN
THE LISA
8000 (8240/8100) Series - Solid State Piezo Sounder (P Models only)
Reverse/
Model Part Integral 135°F Isolated 135°F Non-Latching
Number Number Voltage Local 90dBA Thermal Thermal Circuit"Y"
Piezo
8240 908-1201-002 24VDC
8240Y 908-1207-002 24VDC •
8240T 908-1203-002 24VDC •
8240P 908-1202-002 24VDC •
8240PT 908-1205-002 24VDC • •
8240PTY 908-1209-002 24VDC • • •
8240PY 908-1208-002 24VDC • •
8240PH 908-1206-002 24VDC • •
8240PHY 908-1210-002 24VDC • • •
8100 908-1233-002 120VAC
8100Y 908-1239-002 120VAC •
8100T 908-1234-002 120VAC •
8100P 908-1236-002 120VAC • (local)
8100PY 908-1240-002 120VAC • (local) •
8003 (8243/8103) Series - Temporal 3 Piezo Sounder (P Models only)
Reverse/
Model Part Integral 135°F Isolated 135°F Non-Latching
Number Number Voltage Local 90dBA Thermal Thermal Circuit"Y"
Piezo
8243P 908-1211-002 24VDC •
8243PT 908-1212-002 24VDC • •
8243PTY 908-1215-002 24VDC • • •
8243PY 908-1214-002 24VDC • •
8243PH 908-1213-002 24VDC • •
8243PHY 908-1216-002 24VDC • • •
8103P 908-1243-002 120VAC • (local)
8103PY 908-1246-002 120VAC • (local) •
NOTES
• The 8000/8003 Series are round units.
• When testing 8103P/8243P Series, it may take up to 16 seconds longer for smoke alarm to go in or out of alarm mode.
• It is recommended that 8000/8003 Series smoke detector be tested monthly.
• Refer to Technical Bulletin 002 for Easy Wash°on site washing instructions
• 8100P/8240P units produce a non-temporal audible alarm and are therefore not intended for locations where the desired
action of the occupant(s) is evacuation.
• 8103P/8243P units produce a temporal 3 audible alarm. Per NFPA 72, the American National Standard Audible
Emergency Evacuation Signal as defined In ANSI S3.41, is required whenever the intended response is to evacuate the
building.
Wiring for Releasing Device Service
Normally Closed Configuration Normally Open Configuration
120 VAC 120 VAC
POWER SUPPLY POWER SUPPLY
WHITE WHITE
BLACK WHITE
BLACK
I
NOTE:The
blue wire �
YELLOW must be I • BLUE
WHITESMOKE
DETECTOR
ORANGE capped off ORANGE
SMOKE
DETECTOR when wiring •
for closed BLACK I BLACK
contacts.
YELLOW • BL
•WHITE UE •
WHITE
SMOKE ORANGE •
.WHITE SMOKE • ORANGE • .WHITE
DETECTOR DETECTOR
BLACK BLACK
—0 BLACK �—
BLACK
• • •• • • ••
RELEASE RELEASE RELEASE RELEASE
DEVICE I DEVICE 2
DEVICE I DEVICE 2
Detector Wiring Diagram For "H" — Isolated Thermal
— — NOTE:Supervision of - -
power is necessary and is POSITIVE 3
POSITIVE 3 / accomplished by installing II-- POWER NOTE:
` POWER
an End of Line Relay As- NEGATIVE 12 IN
��
NEGATIVE 12 / IN sembly.The EOL Relay 12OVAC
C` Assembly contacts are POSITIVE 6
POSITIVE 6 closed when energized / POWER (8100 & 8103)
< and are wired in series NEGATIVE 15 OUT
~- POWER with the alarm loop.Power / Hot(Black)Wire:
NEGATIVE 15< ....4OUT failure or a break in the VIOLET 10 Pin 3& Pin 6
power loop de-energizes
the EOL Relay,causing VIOLET 13 , Neutral
VIOLET 10 / the relay contacts to open. 1 ALARM White Wire:
C` / This results in a trouble VIO/BLK 1 CONTACTS (White)
VIOLET 13/ signal at the control panel. VIO/BLK 4 Pin 12&Pin 15
c` ALARM 24VDC
VIO/BLK 1 CONTACTS BLUE 7
T �. (8240 & 8243)
VIO/BLK 4<
, I ORANGE 8 , AALLACRMSORY Positive
YELLOW 9 CONTACTS (Red)Wire:
BLUE 7
<
BROWN 2 Pin 3& Pin 6
ORANGE 8ACCESSORY ALARM
BROWN
5 , Negative
YELLOW 9 ` CONTACTS GRAY 11 I I HEAT (Black)Wire:
- - T SENSOR Pin 12&Pin 15
GRAY 14 ,�
__
PLUG DETECTOR
PLUG DETECTOR
Supervised Wiring Diagrams
SINGLE LOOP PANEL FUNCTIONAL DIAGRAM POWER rSHOWN 1 DOUBLE LOOP PANEL FUNCTIONAL DIAGRAM POWER rSHOWN
BPW LENERGIZED SpWy LENERGIZED
FIRST LAST RELAY MODULE FIRST LAST RELAY MODULE
UL LISTED SMOKE SMOKE UL LISTED SMOKE SMOKE
CONTROL DETECTOR DETECTOR CONTROL DETECTOR DETECTOR
PANEL RED IN OUT RED I O T RED PANEL RED IN OUT RED IN 06T RED
POWER. �I WO BLK •�� L POWERO BLK O O BLK O O BLK pig
ALARM: RENNIN VIOL 101. - ALARM, VIOL O O VIOL VIOL
LOOP VIO/BLK BOWVIO/BLKMid VIO/BLK �� L LOOP O VIO/BLK a i o VIO/BLK O • o VIO/BLK
END OF LINE BLU BLU
ORN ACCESSORY • : .LU RESISTOR LOOP C� ORN 'ACCESSORY
Ala YEL'LONTACTS . TEL RETURN O TEL'CON ACTS ALARM I' O TEL
DC[*BLK DC DM
11
AC[WHTHNEUT] AC[WHT NEUT]
8000 /
8003
SERIES
Electrical Specifications
Model Numbers 8240 8100
Operating Voltage Nominal: 24VDC 120VAC
Range Min: 18VDC 110VAC
Max: 30VDC 130VAC
Frequency — 60HZ
Current Consumption at Nominal Operating Voltage(Milliamperes):
Standby 6mA 70mA
Alarm 60mA 70mA
Note:For"P"Option (Horn),Alarm Current Consumption is unchanged.
Sensitivity 2.5%Nominal
Alarm Contacts 1 Form A—N.O.(Resistive)
1 Amp at 24 VDC
0.6A at 120 VAC
Auxiliary 1 Form C—N.O.(Resistive)
1 Amp at 24 VDC
0.6A at 120 VAC
Temperature 40°- 100°F(4.4°-38°C)
Humidity 10%-93%Relative Humidity
Size Diameter at base:5.75 in.(14.605 cm)
Overall diameter: 6.25 in.(16.51 cm)
Depth:2.625 in.
Architect & Engineering Specifications
The photoelectric smoke detector shall be a Gentex Model 8100/8103/8240/8243 or approved equal and shall operate on the photoelectric
light scattering principle and shall be listed by Underwriter's Laboratories, Inc.,the State of California Fire Marshal and the Bureau of
Standards and Appeals(NYC).
The smoke detector shall contain an infrared LED light source and a light sensing photodiode.These components shall be positioned such
that when smoke particles enter the sensing area,light from the LED reflects onto the photodiode.When the amount of light reflected onto the
photodiode reaches a predetermined level,the detector shall latch into alarm.
The smoke detector shall contain a test knob that,when in TEST 2 Position,scatters the detector's LED light source to the equivalent of a
nominal.85%actual smoke condition,when in TEST 1 position the detector shall simulate an equivalent of a nominal 3.5%actual smoke
condition.Test feature shall indicate when maintenance is required without the need of additional equipment. A magnetic switch closure or
other switch closure,or smoke generating equipment which does not scatter the light beam or test sensitivity is not sufficient.
The smoke detector shall be able to contain an optional internal 90dBA horn(at 10 feet)which emits an intermittent tone when the detector
alarms.Also have the provision of reverse polarity operation.The horn shall have the capability of being self-restoring.
The smoke detector shall be able to provide a self-restoring integral/isolated heat sensor set to alarm at 135°F(57.2°C)fixed temperature.
The smoke detector shall be provided from the manufacturer with all internal wiring(power in,power out and alarm contacts have 2 wires,
auxiliary relay contacts each have 1 wire) leading into a plug-in terminal socket for ease of field installation.Screws are not acceptable since
they make service more difficult.The manufacturer shall further supply the field wiring harness with plug connector for connection to insulated
wire connectors. The smoke detector shall mount to a 2"x 3"switch box or 4"octagon junction box using a standard bracket that does not
have to be purchased separately.The smoke detector shall be listed for wall or ceiling mounting.
24 units per carton
32 pounds per carton
Important Notice: 551-0039-03
G E IV T E X These materials have been prepared by Gentex Corporation("Genres")for informational pur-
poses only,are necessarily summary,and are not purported to serve as legal advice and should
not be used as such.Gentex makes no representations and warranties,express or implied,that
CORPORATION these materials are complete and accurate,up-to-date,or in compliance with all relevant local,
state and federal laws,regulations and rules.The materials do not address all legal considera-
tions as there is inevitable uncertainty regarding interpretation of laws,regulations and rules and
Fire Protection Products Group•www.gentex.com the application of such laws,regulations and rules to particular fact patterns.Eachperson'sactiv-
ities can differently affect the obligations that exist under applicable laws,regulations or rules.
10985 Chicago Drive •Zeeland, Michigan 49464 Therefore,these materials should be used only(or informational purposes and should not be
ubstieing sal legal ie. ewb
616.392.7195 • 1.800.436.8391 • 616.392.4219 Fax actiousednas ora failuresto acttutefor in sereliaknceprofesupon the ioninformatioadvn ccontainedGentinx thisill mnotateerial.responsible for any
Gentex Corporation reserves the right to make changes to the product data sheet at their discretion.