HomeMy WebLinkAboutB14-0240_B14-0240 Certificate of Compliance_1419897480.pdf T. Certificate of Compliance — FS-ONE 1.1111111jTl
�1 - -024cD
Northbrook,Illinois•(708)272-8800
Melville,New York•(516)271-6200
® Underwriters Laboratories Inc.® Santa Clara,California•(408)985-2400
Research Triangle Park,
North Carolina•(919)549-1400
CERTIFICATE OF COMPLIANCE
CERTIFICATE NUMBER: 211097 - R 13 2 4 0 A
ISSUE DATE: October 21, 1997
Issued to: Hilti Construction Chemicals Inc.
5400 S. 122nd East Avenue
Tulsa, OK 74146 USA
Report Reference: R13240, February 14, 1997
This is to Certify that
representative samples of:
Fill, Void or Cavity Materials, one part Sealant
designated as FS One (also identified as CP 612)
Have been investigated by Underwriters Laboratories Inc. in accordance with the Standard(s)
indicated on this Certificate.
Standard(s)for Safety: UL 1479, Fire Tests of Through-Penetration
Firestops;
UL 2079, Tests for Fire Resistance of Building
Joint Systems.
Additional Information:
This material is a one part intumescent firestop sealant for use in
through-penetration firestop systems. These sealants are Classified
as "Fill, Vold or Cavity Materials" for use in various Through-
Penetration Firestop Systems as specified in Volume 2 of UL's Fire
Resistance Directory.
Only those products bearing the UL Classification Marking should be considered as being
covered by UL's Classification and Follow-Up Service.
The UL Classification Marking includes:the name"Underwriters Laboratories Inc.';the word'Classified";a control
number(may be alphanumeric)assigned by UL;a statement to indicate the extent of UL's evaluation of the product;
and,the product category name(product identity)as indicated in the appropriate UL Directory.
" 1
J
Engineer: ti,��,�' �'1� ---�—Review Engineer: 6 V--
Underwriters
Laboratories Inc. Underwriters Laboratories Inc.
Niknla Mnrnri1nvir A. M. Ramirez
2000-44C(6/92)
234 Saving Lives through innovation 8 education•Hilti Firestop Guide 2001•Hilti U.S.: 1-800-879-8000/www.us.hilti.com
N1`�.1 Material Safety Data Sheet
Signs and Symptoms of Exposure: Possibly irritating upon contact with the eyes or upon repeated contact
with the skin.
Routes of Exposure: Dermal,
Medical Conditions Aggravated
by Exposure: Eye and skin conditions.
EMERGENCY AND FIRST AID PROCEDURES
Eyes: Immediately flush with plenty of water. Call a physician if symptoms occur.
Skin: Immediately wipe off material and wash with soap and water. Material can adhere to the skin.
If material has adhered to the skin, use an abrasive containing hand cleaner. If material does not
come off, buff with a pumice stone.
Inhalation: Move victim to fresh air if discomfort develops. Call a physician if symptoms persist.
Ingestion: Seek medical attention. Do not induce vomiting unless directed by a physician. Never give anything
by mouth to an unconscious person.
Other: Referral to a physician is recommended if there is any question about the seriousness of the
injury/exposure.
CONTROL MEASURES AND PERSONAL PROTECTIVE EQUIPMENT
Ventilation: General (natural or mechanically induced fresh air movements).
Eye Protection: Not required, however, safety glasses should be worn in most industrial settings.
Skin Protection: Avoid skin contact.Cloth gloves are suitable for hand protection.
Respiratory Protection: None normally required. Where ventilation is inadequate to control vapors, use a NIOSH-approved
respirator with organic vapor cartridges. Never enter a confined space without an appropriate
air-supplied respirator.
PRECAUTIONS FOR SAFE HANDLING AND USE
Handling and Storing
Precautions: Store in a cool, dry area preferably between 50°and 100° F. Keep from freezing.
Do not store in direct sunlight. Avoid contact with the eyes or skin. Practice good
hygiene; i.e. always wash thoroughly after handling and before eating or smoking.
For industrial use only. Keep out of reach of children. Follow label/use instructions.
Spill Procedures: Immediately wipe away spilled material before it hardens. Place in a container for
proper disposal in accordance with all applicable local, state,or federal requirements.
REGULATORY INFORMATION
Hazard Communication: This MSDS has been prepared in accordance with the federal OSHA Hazard Communication
Standard 29 CFR 1910.1200.
HMIS Codes: Health 1, Flammability 0, Reactivity 0, PPE B
DOT Shipping Name: Not regulated.
TSCA Inventory Status: Chemical components listed on TSCA inventory.
SARA Title III,
Section 313: This product contains 1-5% ethylene glycol(CAS 107-21-1)and 1-5% zinc oxide(re:zinc
compounds)which are subject to reporting under Section 313 of SARA Title III(40 CFR Part 372).
EPA Waste Code(s): Not regulated by EPA as a hazardous waste.
Waste Disposal
Methods: Consult with regulatory agencies or your corporate personnel for disposal methods that
comply with local, state, and federal safety, health and environmental regulations.
CONTACTS
Customer Service: 1 800 879 8000
Technical Service: 1 800 879 8000
Emergency: 1 800 879 4444
Health/Safety: 1 800 879 6000 Steve Gerrard (x6309) Jerry Metcalf(x6704)
The information and recommendations contained herein are based upon data believed to be correct; however, no guarantee or
warranty of any kind expressed or implied is made with respect to the information provided.
Saving Lives through innovation&education•Hilti Firestop Guide 2001 •Hilti U.S.: 1-800-879-8000/www.us.hilti.com 211
•
L . Material Safety Data Sheet N1`�111.11
HILTI, INC.: P.O. Box 21148,Tulsa,OK 74121; Ph: 1 800 879 6000; Emergency No.: 1 800 879 4444
PRODUCT NAME: FS-ONE High Performance Intumescent Firestop Sealant MSDS No.: 259
Revision No.: 008
DESCRIPTION: One-part acrylic-based sealant Date: 05/19/99
Page: 1 of 2
INGREDIENTS AND EXPOSURE LIMITS
Ingredients: CAS Number: PEL: TLV: TEL:
Calcium carbonate 01317-65-3 5 mg/m3(T) 10 mg/m3(T) NE
Ammonium polyphosphate 68333-79-9 NE NE NE
Boron trioxide 01303-86-2 15 mg/m3(R) 10 mg/m3 NE
Alkylphenolethersulfate, sodium salt 69011-84-3 NE NE NE
Talc 14807-96-6 20 mppcf 2 mg/m3 NE
Zinc oxide 01314-13-2 5 mg/m3(T) 10 mg/m3 NE
Expandable graphite 12777-87-6 5 mg/m3(T) 2 mg/m3(T) NE
Ethylene glycol 00107-21-1 NE C:100 mg/m3(A) NE
Polybutene 09003-29-6 NE NE NE
Iron oxide 01309-37-1 10 mg/m3 5 mg/m3 NE
Glass filament 65997-17-3 NE 5 mg/m3(T) NE
Silicon dioxide 14808-60-7 0.05 mg/m3(T) 0.1 mg/m3(T) NE
Abbreviations: PEL=OSHA Permissible Exposure Limit. TLV=ACGIH Threshold Limit Value. C=Ceiling. STEL= Short Term
Exposure Limit. NE= None Established. NA= Not Applicable. (T)indicates"as total dust". (R)indicates"as respirable
fraction". (A)indicates"as an aerosol". mppcf= million particles per cubic foot.
PHYSICAL DATA
Appearance: Red paste. Odor: Odorless.
Vapor Density: (air= 1) Not determined. Vapor Pressure: 23mbar®20C/68F
Boiling Point: Not applicable. VOC Content: None.
Evaporation Rate: Not applicable. Solubility in Water: Soluble.
Specific Gravity: 1.5 pH: Notdetermined.
FIRE AND EXPLOSION HAZARD DATA
Flash Point: Non-flammable.
Flammable Limits: Not applicable.
Extinguishing Media: Not applicable. Use extinguishing media as appropriate for surrounding fire.
Special Fire Fighting Procedures: None known. Use a self-contained breathing apparatus when fighting
fires involving chemicals.
Unusual Fire and Explosion Hazards: None known. Thermal decomposition products can be formed.
REACTIVITY DATA
Stability: Stable.
Hazardous Polymerization: Will not occur.
Incompatibility: Strong acids, peroxides, and oxidizing agents.
Decomposition Products: Thermal decomposition can yield CO and CO2.
Conditions to Avoid: None known.
HEALTH HAZARD DATA
Known Hazards: None known.
Carcinogenicity: IARC classifies crystalline silica(quartz sand)as Gp I based upon evidence
among workers in industries where there has been long-term and chronic
exposure(via inhalation)to silica dust; e.g. mining,quarry,stone crushing,
refractory brick and pottery workers. This product does not pose a dust
hazard;therefore, this classification is not relevant. Based upon the nature
and intended use of this product, it does not pose an increased cancer
risk to workers.
210 Saving Lives through innovation&education•Hilti Firestop Guide 2001 •Hilti U.S.:1-800-879-8000/www.us.hilti.com
Mg`Tg Installation Instructions •
FS-ONE Technical Data
FS-ONE Intumescent Firestop
High Performance Intumescent (at 73°F(23°C)and 50%relative humidity)
Chemical basis: Water-based intumescent acrylic dispersion
Firestop Sealant
Density: Approx.1.5 g/cm3
Color: Red
Product description Working time: Approx.20-30 min
• Intumescent(expands when exposed to fire)firestop sealant that Curing time: Approx.14-21 days
helps protect combustible and non-combustible penetrations for Shore A Hardness: Approx.35
up to 4 hours fire rating Movement capability: Approx.5%
Intumescent Activation: Approx 250°F(121°C)
Product features Expansion rate(unrestricted): Up to 3-5 times original volume
• Smoke,gas and water resistant Temperature resistance(cured): -40°F(-40°C)to 212°F(100°C)
• Contains no halogen,solvents or asbestos A$Ilication temrerature: 35°F 2°C to 100°F 38°C
• High fire rating properties Surface burning characteristics: Flame Spread:0
• Water based,easy to clean (ASTM E 84-96) Smoke Development:5
Sound transmission classification: 50
Tested in accordance with ASTM E 90-97
• UL 1479 Approvals
• ASTM E 814 ICBG Evaluation Service,Inc. Report No.5071
• ASTM E 84
California State Fire Marshal Listing No.1200:108
Installation instructions for FS-ONE City of New York MEA 326-96-M Vol.II
Cable Installation
1.Clean opening. 2.Pack mineral wool. . pp y - NE. 4.Smooth FS-ONE. 5.leave competed sea . asten rdenti ication
(If required) undisturbed for 48 hours. plate(if required).
PI,e installation
V044 ri 0.3yt
H4 ?IR ,Er
h'kk•
1.Clean opening. 2.Pack mineral wool. 3.Apply FS-ONE. 4.Smooth FS-ONE. 5.Leave completed seal 6.Fasten identification
(If required) undisturbed for 48 hours. plate(if required).
Opening Notice about approvals
1. Clean the opening.Surfaces to which FS-ONE will be applied should be • Check that the penetration has been sealed according to the specified
cleaned of loose debris,dirt,oil,moisture,frost and wax.Structures drawing in the UL Fire Resistance Directory or Hilti Firestop Manual.For
supporting penetrating items must be installed in compliance with further advice,please contact Hilti customer service.Refer to Hilti product
local building and electrical standards. literature and UL fire resistance directory for specific application details.
Application of firestop sealant Not for use...
2. Install the prescribed backfilling material type and depth to obtain the • High movement expansion joints
desired rating(if required).Leave sufficient depth for applying FS-ONE. • Underwater
3. Application of firestop sealant:Apply FS-ONE to the required depth in • On materials where oil,plasticizers or solvents may bleed i.e.impregnated
order to obtain the desired fire rating.Make sure FS-ONE contacts all wood,oil based seals,green or partially vulcanized rubber
surfaces to provide maximum adhesion.For application of FS-ONE use a • In any penetration other than those specifically described in this manual
standard caulking gun,foil pack gun,bulk loader and bulk gun.With FS- or the test reports
ONE buckets,Graco type sealant pumps may be used.(Contact pump Safety precautions
manufacturer for proper selection). • Before handling,read the product and Material Safety Data Sheet for
4. Smoothing of firestop sealant:To complete the seal,tool immediately to detailed use and health information
give a smooth appearance.Excess sealant,prior to curing,can be cleaned • Keep out of reach of children
away from adjacent surfaces and tools with water. • Wear suitable gloves and eye protection
5. Leave completed seal undisturbed for 48 hours. Storage
6. For maintenance reasons,a penetration seal could be permanently marked • Store only in the original packaging in a location protected from moisture
with an identification plate.In such a case,mark the identification plate at temperatures between 40°F(5°C)and 86°F(30°C)
and fasten it in a visible position next to the seal. • Observe expiration date on the packaging
Saving Lives through innovation&education•Hilti Firestop Guide 2001 •Hilti U.S.:1-800-879-8000/www.us.hilti.com 13
Product Information Fyi`��i
k
FS-ONES - .Y
r • �
High Performance '«, •
Intumescent Firestop Sealant '
Product description vivl(d.1
ll/
• Intumescent(expands when exposed to fire)firestop sealant that iii
hiI'
helps protect combustible and non-combustible penetrations for
up to 4 hours fire rating
Areas of application l
• Steel,copper and EMT pipes tii
• Insulated steel and copper pipes b,T *r
• Cable bundles �, ,"~^•
• Closed or vented plastic pipes ..
• HVAC penetrations
For use with
• Concrete,masonry,drywall and wood floor assemblies Internationally tested and approved
• Wall and floor assemblies rated up to 4 hours
P,SS IF,, FILL,VOID OR CAVITY MATERIALS
Examples0 O CLASSIFIED BY
UNDERWRITERS LABORATORIES,INC.
FOR USE IN TROUGH-PENETRATION
• Sealing around plastic pipe penetrations in fire rated FIRESTOPSYSTEMS APPROVED
�PenalrAionF slops
construction SEE UL FIRE RESISTANCE DIRECTORY CmwAlhm
•por,,Ml R
Aueaesr,,,,,a•on Appra.tl(l,,,,
6817
• Sealing around combustible and non-combustible penetrations
in fire rated construction
System advantage/Customer benefits
• Protects most typical firestop penetration applications
• Easy to work with and fast cleanup
• Can be repenetrated when laying new cables
• Can be painted
FS-ONE
Intumescent Firestop Sealant
Ordering
Description Color Package contents Volume Item No. . _ M ii
FS-ONE,tube red 10.1 oz.(300 ml) 18 Ina 00259579
FS-ONE,foil red (Qty 20)20.2 oz.(600 ml) 36 in' 00311387 _ I
FS-ONE,pail red 5 Gallons(19 Iter) 1155 In' 00259578 .y.
CB 200 P1-300/310 ml Dispenser 00055205 L ..ti_. .----
600
-600 ml Foil Dispenser 00024669
12 Saving Lives through innovation&education•Hilti Firestop Guide 2001 •Hilti U.S.:1-800-879-8000/www.us.hilti.com