Loading...
HomeMy WebLinkAboutE18-0170_VRC N4 proposed load calculation_1535640317.pdf islA OF,fr4! Load Calculation VRC N4 GeneralLightingandReceptacleDemandLoad: J-Auvp 08/30/18 1350 sq. ft. x 3VA= 4050 1,500 VA x 2= 3000 1,500 VA x 1 = 1500 Total connected load: 8,550 3,000 VA @ 100% = 3,000 VA@35% = 1,942.5 679.875 Totalgenerallightingand Receptacledemandload: 3,680 Rangedemandload: 12,000VA 8,000 DryerLoad: 5,000 Fixedapplianceload: demand Dishwasher 1200 1 1,200 Microwave 1800 1 1,800 Garbage disposal 800 1 800 jetted tub 1800 0 0 other 1800 0 0 humidifier 1800 0 0 toto toilet 1600 0 0 elevator 5000 0 0 Sub-Zero 1200 0 0 A/C 3400 0 0 Hot tub 12000 0 0 Totalfixedapplianceload: 3,800 islA OFdele Load Calculation VRC N4 1 Heatingload: demand 30,0D 08/30/18 electric heat 250 58 14,500 water heater 4000 3 12,000 heat tape 0 0 0 steam generator 12,000 2 24,000 Totalheatingload: 50,500 25%oflargestmotor: 1,200 Totals: General lighting and receptacles: 3,680 Range: 8,000 Dryer: 5,000 Fixed appliance: 3,800 Heating: 50,500 25% of largest motor: 1,200 Total: VA 72,180 AMPS 300.75 Installed Service Size: 125A single phase Secondary Conductors: unknown Distance from vault to meter: unknown *VI OFge ' ! .5,140 Load Calculation VRC N4 1 oji qua HCEloadforminfo 08/30/18 owner's name owners phone electrician name A-PHASE ELECTRIC, LLC electrician email address john@aphaseelectricllc.com electrician phone# 970-904-0593 type of service subdivision lot block filing 911 address within city limits city secondary voltage secondary wire size secondary wire type number of conductors per phase cable distance to transformer meter location(structure or ped) nearby HC asset amperage main fuse/breaker size ct's required PV system calculated max demand name of engineer contacted house square footage major electrical loads site sketch