2016 Dwelling Unit Electric Service & Feeder Load Calculator o
x. a,
220.12 General Lighting Load (IO
3 va/ft2 of floor area,including unused space adaptable for future use. 10/17/17
Floor Area= 4500 ft2 13.600 va
Basement Floor Area= oift2 - va
220.52(A) Small Appliance Load
1500 va for each 20 amp branch circuit required per 210.1(C)(1)in EACH kitchen,
pantry, breakfast room,dining room,or similar areas.
#of Small Appliance Branch Circuits 4 4'1500 va= 6,000 va
220.52(B) Laundry Load
#of Laundry Branch Circuits= x"1500 va= 1,500 va
Total General Lighting&Appliance Load= 21,000 va
220.42 Lighting Load Feeder Demand Factors
First 3000 or less at l00% 3,000 va
From 3001 to 120,000 at 35% 6,300 va
Remainder over 120,000 at 25% - va
Total Lighting Demand Load= va
220.54 Electric Clothes Dryers
Qty 1 Electric Dryer#1 5.00 kw 5,000 w
Qty 0 Electric Dryer#2 kw w
220.55 Electric Cooking-Ranges,Stove Tops and Wall Ovens
Qty 0 Wall Oven Nameplate - kw
Qty 1 Electric Range Nameplate 11.99 kw
Qty 0 Wall Oven Nameplate - kw
Electric Cooking Demand Load= *NAME? w
220.51 Fixed Electric Space Heating Loads or Air Conditioning Load:
Fixed Electric Space Heat#1 - kw AC#1/Geo 13 SEER 3 Ton 4.5 kva
Fixed Electric Space Heat#2 - kw AC#2/Geo - kva
Fixed Electric Space Heat#3 - kw AC#3/Geo - kva
Fixed Electric Space Heat#4 - kw AC#4/Geo - kva
Fixed Electric Space Heat#5 - kw AC#5/Geo - kva
Total Heat&AC Load= 4,455 va
220.14 Appliance load--Dwelling Units
Qty Description va(watts) Qty Description va(watts)
1 Central Furnace 1,200 0 -
1 Dishwasher 1,200 0 -
1 Refrigerator 1,440 0 -
1 Microwave 1,580 0 -
1 Range Hood 240 0 -
4 Vent Fan 400 0 -
0 - 0 -
Total Connected Appliance Load= 8.050 va
220.53 Appliance load--Dwelling Units Total Appliance Demand Load= 4 va
220.50 Motor Loads @ 120 Volts
Qty Description va(watts) Qty Description va(watts)
1 1/2hpSump/EjectPump 375 0 0
1 1/2hpGarbage Disposa 375 0 -
2 1/2hpGar/DoorOpener 375 0 -
0L - 0', -
Total Motor Load= 1,5'C+0 va
430.24 Several Motors or a Motor(s)and Other Loads) 25%of Largest Motor Load= 94 va
Total Motor Demand Load= 1,694 va
TOTAL CALCULATED DEMAND LOAD in Volt-amperes= #NAME? va
TOTAL CALCULATED DEMAND LOAD In AMPS @1201240V 1ph3W= *NAME? amps
EXISTING SERVICE SIZE NEW AMPS
MINIMUM SERVICE SIZE moan AMPS SERVICE SIZE REQUESTED= 300 amps