HomeMy WebLinkAboutVVMC Hydr Calcs.pdf AUTOMATIC FIRE SPRINKLER SYSTEM HYDRAULIC CALCULATIONS FOR VAIL VALLEY MEDICAL CENTER 181 WEST MEADOW DRIVE VAIL, CO 81657 PHASE 1 WEST WING PROJECT WATER FLOW TEST REPORT FOR VAIL VALLEY MEDICAL CENTER 181 WEST MEADOW DRIVE VAIL, CO 81657 DATE: 02-25-16 TIME: 1:00PM LOCATION OF CONTROL HYDRANT: W. MEADOW DRIVE, SW CORNER OF HOSPTAL LOCATION OF FLOW HYDRANT: APPOX. 250 FT. EAST OF CONTROL HYDRANT STATIC PRESSURE: 146 PSI RESIDUAL PRESSURE: 140PSI FLOW IN GPM: 1482 GPM (1) 2-1/2” OUTLET WITH 78 PSI PITOT DISCHARGE COEFFICIENT: 0.9 TEST BY: EAGLE RIVER WATER & SANITATION DISTRICT WITNESSED BY: FRONTIER FIRE PROTECTION: KEVIN MURRAY Frontier Fire Protection Inc. 2617 W. Holden Place Your Street Address 2 Denver, CO 80204 303-629-0221 Job Name : 15-3990 4th Floor CALC Building : FP 5 of 5 Location : 181 West Meadow Drive Vail, CO 81657 System : 1 Contract : 15-3990 Data File : 15-3990 4th Floor CALC Area 1.WXF Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Frontier Fire Protection Inc.Page 1 15-3990 4th Floor CALC Date HYDRAULIC CALCULATIONS for Project name:VVMC 4th Floor CALC Location:181 West Meadow Drive Vail, CO 81657 Drawing no:FP 5 of 5 Date:05/12/16 Design Remote area number:1 Remote area location:4th Floor - NE Corner Occupancy classification:Light Hazard Density:0.1 - Gpm/SqFt Area of application:970 - SqFt Coverage per sprinkler:165 - SqFt Type of sprinklers calculated:Viking VK462 No. of sprinklers calculated:9 In-rack demand:N/A - GPM Hose streams:100 - GPM Total water required (including hose streams):278.993 - GPM @ 111.676 - Psi Type of system:Wet Pipe System Volume of dry or preaction system:N/A - Gal Water supply information Date:02-25-16 Location:South Side of Hospital on West Meadow Drive Source:Flow Test by Eagle River Water & Sanitation Name of contractor:Frontier Fire Protection LLC Address:2617 W. Holden Place Denver, CO 80204 Phone number:303-629-0221 Name of designer:K. Murray Authority having jurisdiction:Vail Fire Department Notes: (Include peaking information or gridded systems here.) Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Frontier Fire Protection Inc.Page 2 15-3990 4th Floor CALCDate 10203040E50R60U70S80S90E100R110P120130140150200 400 600 800 1000 1200 1400 1600 1800FLOW ( N ^ 1.85 )City Water Supply:Demand:C1C2C1 - Static Pressure : 146 C2 - Residual Pressure: 140 C2 - Residual Flow : 1482 D1 - Elevation : 29.958 D2 - System Flow : 278.993 D2 - System Pressure : 111.676 Hose ( Demand ) : _______D3 - System Demand : 278.993 Safety Margin : 34.051 D1D2Water Supply Curve CComputer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Frontier Fire Protection Inc.Page 3 15-3990 4th Floor CALCDate Fitting Legend Abbrev. Name ½ ¾ 1 1¼ 1½ 2 2½ 3 3½ 4 5 6 8 10 12 14 16 18 20 24 E NFPA 13 90' Standard Elbow 1 2 2 3 4 5 6 7 8 10 12 14 18 22 27 35 4045 50 61 T NFPA 13 90' Flow thru Tee 3 4 5 6 8 10 12 15 17 20 25 30 35 50 60 71 81 91 101 121 Units Summary Diameter Units Inches Length Units Feet Flow Units US Gallons per Minute Pressure Units Pounds per Square Inch Note: Fitting Legend provides equivalent pipe lengths for fittings types of various diameters. Equivalent lengths shown are standard for actual diameters of Sched 40 pipe and CFactors of 120 except as noted with *. The fittings marked with a * show equivalent lengths values supplied by manufacturers based on specific pipe diameters and CFactors and they require no adjustment. All values for fittings not marked with a * will be adjusted in the calculation for CFactors of other than 120 and diameters other than Sched 40 per NFPA. Fittings Used SummaryComputer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Frontier Fire Protection Inc.Page 4 15-3990 4th Floor CALC Date Node Elevation K-Fact Pt Pn Flow Density Area Press No.Actual Actual Req. 1 49.17 5.6 8.68 na 16.5 0.1 165 7.0 404 50.33 8.29 na 2 50.0 9.52 na 3 50.33 14.64 na 4 49.17 19.32 na 5 49.17 21.34 na 6 49.17 21.52 na 7 50.33 48.96 na ST1 50.33 53.35 na 9 -5.0 82.11 na 10 -5.0 82.32 na BF2 -12.12 85.47 na BF1 -12.12 97.59 na UG -20.0 111.64 na TEST -20.0 111.68 na 14 49.17 5.6 8.29 na 16.13 0.1 96 7.0 405 50.33 7.89 na 15 49.17 5.6 9.07 na 16.87 0.1 99 7.0 409 50.0 8.79 na 16 49.67 10.66 na 17 49.67 15.09 na 18 49.17 19.15 na 19 49.17 5.6 9.76 na 17.49 0.1 144 7.0 408 50.0 9.48 na 20 49.17 5.6 13.39 na 20.49 0.1 165 7.0 403 50.0 13.14 na 21 49.17 5.6 13.79 na 20.79 0.1 144 7.0 407 49.67 13.64 na 22 49.67 14.27 na 23 48.67 5.6 17.51 na 23.43 0.1 140 7.0 406 49.5 17.29 na 24 48.67 5.6 17.54 na 23.45 0.1 101 7.0 402 49.5 17.32 na 25 48.67 5.6 18.11 na 23.83 0.1 136 7.0 401 49.5 17.9 na 26 49.17 21.34 na HOSE 44.67 54.93 na 100.0 The maximum velocity is 12.76 and it occurs in the pipe between nodes 16 and 17 Pressure / Flow Summary - STANDARD Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Frontier Fire Protection Inc.Page 5 15-3990 4th Floor CALC Date Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 1 16.50 1.049 0.0 1.170 8.681 K Factor = 5.60 to 120.0 0.0 0.0 -0.502 404 16.5 0.0915 0.0 1.170 0.107 Vel = 6.13 404 0.0 1.049 2E 4.0 3.000 8.286 to 120.0 T 5.0 9.000 0.143 2 16.5 0.0912 0.0 12.000 1.094 Vel = 6.13 2 16.13 1.049 2E 4.0 12.330 9.523 to 120.0 0.0 4.000 -0.143 3 32.63 0.3218 0.0 16.330 5.255 Vel = 12.11 3 20.49 1.38 2E 6.0 14.040 14.635 to 120.0 0.0 6.000 0.502 4 53.12 0.2085 0.0 20.040 4.179 Vel = 11.39 4 23.45 1.61 T 8.0 2.460 19.316 to 120.0 0.0 8.000 0.0 5 76.57 0.1937 0.0 10.460 2.026 Vel = 12.07 5 23.83 2.635 0.0 6.290 21.342 to 120.0 0.0 0.0 0.0 6 100.4 0.0289 0.0 6.290 0.182 Vel = 5.91 6 78.59 2.635 13E 107.083 223.310 21.524 to 120.0 0.0 107.082 -0.502 7 178.99 0.0846 0.0 330.392 27.940 Vel = 10.53 7 0.0 2.635 4E 32.948 18.960 48.962 to 120.0 0.0 32.948 0.0 ST1 178.99 0.0846 0.0 51.908 4.390 Vel = 10.53 ST1 100.00 4.026 7E 70.0 126.630 53.352 to 120.0 0.0 70.000 23.963 9 278.99 0.0244 0.0 196.630 4.796 Vel = 7.03 9 0.0 6.357 2T 75.44 2.080 82.111 to 120.0 0.0 75.440 0.0 10 278.99 0.0026 0.0 77.520 0.205 Vel = 2.82 10 0.0 6.357 E 17.603 8.370 82.316 to 120.0 0.0 17.603 3.084 BF2 278.99 0.0026 0.0 25.973 0.068 Vel = 2.82 BF2 0.0 4.26 0.0 6.750 85.468 to 120.0 0.0 0.0 12.000 * * Fixed Loss = 12 BF1 278.99 0.0185 0.0 6.750 0.125 Vel = 6.28 BF1 0.0 6.357 6E 105.616 96.970 97.593 to 120.0 T 37.72 143.336 13.413 * * Fixed Loss = 10 UG 278.99 0.0026 0.0 240.306 0.634 Vel = 2.82 UG 0.0 8.27 0.0 50.000 111.640 to 120.0 0.0 0.0 0.0 TEST 278.99 0.0007 0.0 50.000 0.036 Vel = 1.67 0.0 278.99 111.676 K Factor = 26.40 14 16.13 1.049 0.0 1.170 8.294 K Factor = 5.60 to 120.0 0.0 0.0 -0.502 405 16.13 0.0872 0.0 1.170 0.102 Vel = 5.99 405 0.0 1.049 3E 6.0 11.000 7.894 to 120.0 0.0 6.000 0.143 2 16.13 0.0874 0.0 17.000 1.486 Vel = 5.99 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Frontier Fire Protection Inc.Page 6 15-3990 4th Floor CALC Date Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 0.0 16.13 9.523 K Factor = 5.23 15 16.87 1.049 0.0 0.830 9.073 K Factor = 5.60 to 120.0 0.0 0.0 -0.359 409 16.87 0.0940 0.0 0.830 0.078 Vel = 6.26 409 0.0 1.049 2E 4.0 9.160 8.792 to 120.0 T 5.0 9.000 0.143 16 16.87 0.0950 0.0 18.160 1.725 Vel = 6.26 16 17.49 1.049 0.0 12.500 10.660 to 120.0 0.0 0.0 0.0 17 34.36 0.3542 0.0 12.500 4.427 Vel = 12.76 17 20.80 1.38 2E 6.0 11.200 15.087 to 120.0 0.0 6.000 0.217 18 55.16 0.2235 0.0 17.200 3.845 Vel = 11.83 18 23.43 1.61 T 8.0 3.690 19.149 to 120.0 0.0 8.000 0.0 6 78.59 0.2032 0.0 11.690 2.375 Vel = 12.39 0.0 78.59 21.524 K Factor = 16.94 19 17.49 1.049 0.0 0.830 9.760 K Factor = 5.60 to 120.0 0.0 0.0 -0.359 408 17.49 0.1012 0.0 0.830 0.084 Vel = 6.49 408 0.0 1.049 2E 4.0 1.160 9.485 to 120.0 T 5.0 9.000 0.143 16 17.49 0.1016 0.0 10.160 1.032 Vel = 6.49 0.0 17.49 10.660 K Factor = 5.36 20 20.49 1.049 0.0 0.830 13.391 K Factor = 5.60 to 120.0 0.0 0.0 -0.359 403 20.49 0.1349 0.0 0.830 0.112 Vel = 7.61 403 0.0 1.049 2E 4.0 3.000 13.144 to 120.0 T 5.0 9.000 -0.143 3 20.49 0.1362 0.0 12.000 1.634 Vel = 7.61 0.0 20.49 14.635 K Factor = 5.36 21 20.79 1.049 0.0 0.500 13.789 K Factor = 5.60 to 120.0 0.0 0.0 -0.217 407 20.79 0.1400 0.0 0.500 0.070 Vel = 7.72 407 0.0 1.049 2E 4.0 0.500 13.642 to 120.0 0.0 4.000 0.0 22 20.79 0.1400 0.0 4.500 0.630 Vel = 7.72 22 0.0 1.049 T 5.0 0.830 14.272 to 120.0 0.0 5.000 0.0 17 20.79 0.1398 0.0 5.830 0.815 Vel = 7.72 0.0 20.79 15.087 K Factor = 5.35 23 23.43 1.049 0.0 0.830 17.510 K Factor = 5.60 to 120.0 0.0 0.0 -0.359 406 23.43 0.1735 0.0 0.830 0.144 Vel = 8.70 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087 Frontier Fire Protection Inc.Page 7 15-3990 4th Floor CALC Date Hyd. Qa Dia. Fitting Pipe Pt Pt Ref. "C" or Ftng's Pe Pv ******* Notes ****** Point Qt Pf/Ft Eqv. Ln. Total Pf Pn 406 0.0 1.049 2E 4.0 0.810 17.295 to 120.0 T 5.0 9.000 0.143 18 23.43 0.1744 0.0 9.810 1.711 Vel = 8.70 0.0 23.43 19.149 K Factor = 5.35 24 23.45 1.049 0.0 0.830 17.539 K Factor = 5.60 to 120.0 0.0 0.0 -0.359 402 23.45 0.1747 0.0 0.830 0.145 Vel = 8.71 402 0.0 1.049 2E 4.0 1.580 17.325 to 120.0 T 5.0 9.000 0.143 4 23.45 0.1747 0.0 10.580 1.848 Vel = 8.71 0.0 23.45 19.316 K Factor = 5.34 25 23.83 1.049 0.0 0.830 18.107 K Factor = 5.60 to 120.0 0.0 0.0 -0.359 401 23.83 0.1795 0.0 0.830 0.149 Vel = 8.85 401 0.0 1.049 2E 4.0 4.330 17.897 to 120.0 2T 10.0 14.000 0.143 26 23.83 0.1799 0.0 18.330 3.298 Vel = 8.85 26 0.0 3.26 0.0 4.710 21.338 to 120.0 0.0 0.0 0.0 5 23.83 0.0008 0.0 4.710 0.004 Vel = 0.92 0.0 23.83 21.342 K Factor = 5.16 HOSE 100.00 2.635 E 8.237 5.670 54.928 Qa = 100.00 to 120.0 T 16.474 24.711 -2.451 ST1 100.0 0.0288 0.0 30.381 0.875 Vel = 5.88 0.0 100.00 53.352 K Factor = 13.69 Final Calculations - Hazen-Williams Computer Programs by Hydratec Inc. Route 111 Windham N.H. USA 03087