HomeMy WebLinkAboutVVMC Sprinklers.pdfMIRAGE® STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Form No. F_103005 Rev 15.1 Page 1 of 6 1. DESCRIPTION Viking Mirage® Standard and Quick Response Concealed Pendent Sprinkler VK462 and HP Sprinkler VK463 are thermosensitive glass-bulb spray sprinklers designed for installation on concealed pipe systems where the appearance of a smooth ceiling is desired. The sprinkler is pre-assembled with a threaded adapter for installation with a low-pro-file cover assembly that provides up to ½” (12.7 mm) of vertical adjustment. The two-piece design allows installation and testing of the sprinkler prior to installation of the cover plate. The “push-on”, “thread-off” design of the concealed cover plate assembly allows easy installation of the cover plate after the system has been tested and the ceiling finish has been applied. The cover assembly can be removed and reinstalled, allowing temporary removal of ceiling panels without taking the sprinkler system out of service or removing the sprinkler. The Electroless Nickel PTFE (ENT) coating has been investigated for installation in corrosive atmospheres and is cULus Listed as cor-rosion resistant as indicated in the Approval Charts. The ENT finish is only available for the sprinkler assembly, the cover plate is not plated. 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV FM Approval: Class 2015 NYC Approved: MEA 89-92-E, Volume 32 VdS Approved: Certificate G4080021 LPCB Approved: Ref. No. 096e/12 CE Certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032 CCCF Approved: Approved by the China Certification Center for Fire Products (CCCF) Refer to Approval Chart 1 Design Criteria for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications:Available since 2006. Minimum Operating Pressure: 7 psi (0.5 bar)*Maximum Working Pressure: Sprinkler VK463 is rated for use with water working pressures ranging from the minimum 7 psi (0.5 bar) up to 250 psi (17.2 bar) for high-pressure systems. High-pressure (HP) sprinklers can be identified by locating “250” stamped on the deflector. Sprinkler VK462 is rated to a maximum 175 psi (12 bar) wwp. Factory tested hydrostatically to 500 psi (34.5 bar)Thread size: 1/2” (15 mm) NPTNominal K-Factor: 5.6 U.S. (80.6 metric†)Glass-bulb fluid temperature rated to -65°F (-55°C)Patents Pending *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar). †Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. Material Standards:Sprinkler Body: Brass UNS-C84400Deflector: Copper UNS-C19500 for Sprinkler VK462 Phosphor Bronze UNS-C51000 for Sprinkler VK463Deflector Pins: Stainless Steel AlloyBulb: Glass, nominal 3 mm diameterPip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400Button: Brass UNS-C36000 Screws: 18-8 Stainless SteelBelleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with Teflon TapeYoke: Phosphor Bronze UNS-C51000Cover Adapter: Cold Rolled Steel UNS-G10080, Finish: Clear Chromate over Zinc Plating Viking Technical Data may be found on The Viking Corporation’s Web site at http://www.vikinggroupinc.com. The Web site may include a more recent edition of this Technical Data Page. (Added CCCF Approval) MIRAGE® STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Form No. F_103005 Rev 15.1 Page 2 of 6 Cover Assembly Materials:Cover: Copper UNS-C11000Base: Brass UNS-C26000 or UNS-C26800Springs: Nickel AlloySolder: Eutectic Ordering Information: (Also refer to the current Viking price list.)Viking Mirage® Standard and Quick Response Concealed Pendent Sprinklers and Cover Plate Assemblies must be ordered separately:Sprinkler: Base Part No. VK462 - 13503A for Brass finish and 13503JN for ENT finish. VK463 - HP Base Part No. 13667ASpecify sprinkler temperature rating by adding the appropriate suffix for the temperature rating to the base part number:Temperature Suffix: 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = EFor example, sprinkler VK463 with a 155 °F (68 °C) temperature rating = 13667AB. Cover Plate Assembly: Base Part No. 13504 (2-3/4” diameter), Base Part No. 13642 (3-5/16“ diameter), or Base Part No. 15394 (square cover plate, 3-5/16” diameter) Specify finish and temperature rating of the cover plate assembly by adding the appropriate suffixes for the finish and the cover temperature rating to the base part number:Finish Suffix: Polished Chrome = F, Brushed Chrome = F-/B, Bright Brass = B, Antique Brass = B-/A, Brushed Brass = B-/B, Brushed Copper = E-/B, Painted White = M-/W, Painted Ivory = M-/I, Painted Black = M-/BTemperature Suffix: 135 °F (57 °C) UL (139 °F (59 °C) FM and LPCB) = A, 165 °F (74 °C) = C For example, cover 13504 with a Polished Chrome finish and a 165 °F (74 °C) temperature rating = 13504FC. Note: Square cover plate 15394 cULus Listing is for the 135 °F (57 °C) temperature rated cover plate only. Refer to the Approval Chart. Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.)Sprinkler Wrenches**:A. Heavy Duty Wrench Part No. 14047W/B (available since 2006), orB. Head Cabinet Wrench Part No. 14031*** (available since 2006) C. Optional Concealed Cover Plate Installer Tool Part No. 14412 for cover 13504, or Part No. 14867 for the large diameter cover (available since 2007) **Requires a ½” ratchet (not available from Viking). ***Optional for removal of the protective cap. Ideal for sprinkler cabinets.Sprinkler Cabinet: Part No. 01731A (available since 1971) 4. INSTALLATIONRefer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, when the temperature around the sprinkler approaches its operating temperature, the cover plate detaches. Continued heating of the exposed sprinkler causes the heat-sensitive liquid in the glass bulb to expand and the bulb to shatter, releasing the yoke, pip-cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCERefer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY Viking Sprinklers VK462 and VK463 are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEEFor details of warranty, refer to Viking’s current list price schedule or contact Viking directly. MIRAGE® STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Form No. F_103005 Rev 15.1 Page 3 of 6 Approval Chart 1 (UL) Mirage® Concealed Pendent Sprinklers VK462 and VK463 Sprinkler Base Part No.1 SIN NPT Thread Size Nominal K-Factor Maximum Water Working Pressure Listings and Approvals4 (Refer also to Design Criteria) Inch mm U.S.metric2 cULus5 NYC VdS7 LPCB Standard Response Applications 13503A VK462 1/2”15 5.6 80.6 175 psi (12 bar)----AY1, CZ1 AY1, BZ1 AY1, CZ18 AV1, CW1 Quick Response Applications 13503A VK462 1/2”15 5.6 80.6 175 psi (12 bar)AV1, BX1 AV1, BW16 -------- 13503JN11 VK462 1/2”15 5.6 80.6 175 psi (12 bar)AV1, BX1 AV1, BW16 -------- 13667A VK463 1/2”15 5.6 80.6 250 psi (17.2 bar)3 AV1, BX1 AV1, BW16 -------- Sprinkler Temperature Ratings A - 155 °F (68 °C) B - 175 °F (79 °C) and 200 °F (93 °C) C - 200 °F (93 °C) Cover Plate Assembly Temperature Ratings9 V - 135 °F (57 °C) cULus Listed cover 135041, 136421 (large diam-eter), or 153941 (square cover plate) W - 165 °F (74 °C) cover 135041 or 136421 (large diameter) X - 165 °F (74 °C) cover 135041, or 136421 (large diameter) Y - 135 °F (57 °C) cover 135041 LPCB Approved as 139 °F (59 °C) Z - 165 °F (74 °C) cover 135041 Cover Plate Assembly Finishes10 1 - Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black Footnotes 1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 The Water Working Pressure rating is stamped on the deflector. 4 This chart shows the listings and approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional ap-provals. 5 Listed by Underwriter’s Laboratories for use in the U.S. and Canada. 6 Accepted for use, City of New York Department of Buildings, MEA Number 89-92-E, Vol. 32. 7 VdS Approved, standards VdS 2344:2005-12, VdS 2100-25:2008-01, and EN 12259-1:1999 + A1:2001 + A2:2004 + A3:2006, Certificate G4080021. 8 Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2032. 9 The 135/139 °F cover has an orange label. The 165 °F (74 °C) cover has a white label. 10Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. Listings and approv-als apply for any paint manufacturer. Contact Viking for additional information. 11 cULus Listed as corrosion resistant. NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1. TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Temperature Rating of Cover Assembly (Required)Bulb Color Ordinary 155 °F (68° C)100 °F (38 °C)135 °F (57 °C) cULus 139 °F (59 °C) FM and LPCB Red Intermediate 175 °F (79 °C)150 °F (65 °C)165 °F (74 °C)Yellow Intermediate 200 °F (93 °C)150 °F (65 °C)165 °F (74 °C)Green Cover Plate Finishes: Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black Sprinkler Finishes: Brass and ENT Corrosion Resistant Coatings3: ENT Footnotes 1 The sprinkler temperature rating is stamped on the sprinkler deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat-ible with or suitable for the proposed environment. For automatic sprinklers, the ENT coating is applied to all exposed exterior surfaces, including the waterway, but the Belleville spring is exposed. MIRAGE® STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Form No. F_103005 Rev 15.1 Page 4 of 6 Figure 1: Identification of Custom Paint Color for Concealed Covers Figure 2: Square Cover Assembly 15394 DESIGN CRITERIA - UL (Also refer to Approval Chart 1) cULus Listing Requirements: Mirage® Concealed Pendent Sprinklers VK462 and VK463 are cULus Listed as quick response for installation in accordance with the latest edition of NFPA 13 for standard coverage pendent spray sprinklers as indicated below. • For hazard occupancies up to and including Ordinary Hazard, Group II. • Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. Maximum spacing allowed is 15 ft. (4.6 m). • Minimum spacing allowed is 6 ft. (1.8 m) unless baffles are installed in accordance with NFPA 13. • Minimum distance from walls is 4 in. (102 mm). • Maximum distance from walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpendicular to the wall. • The sprinkler obstruction rules contained in NFPA 13 for standard coverage pendent spray sprinklers must be followed. NOTE: Concealed sprinklers must be installed in neutral or negative pressure plenums only. VdS Approval Requirements: a) The sprinkler can be installed in a concrete ceiling (massive ceiling) or in a false ceiling made of light materials. b) This sprinkler is deflector fixed type and can be only activated by heat. The housing is not tight. c) Follow installation guidelines of current standards, CEA4001VdS and EN12845. These sprinklers can only be installed in LH and OH occupan-cies, except in OH4. NOTES: Due to the design the sprinkler type ‘Domed-CCP’ shall not be installed in false ceilings in which the false ceiling space is protected by a water extinguishing system. Due to the design the sprinkler type ‘Domed-CCP’ shall not be installed in false ceilings in which during a fire the pressure above the false ceiling may be assumed to be higher than the pressure below the false ceiling. The criterion for the dropping of the cover relevant for this approval is heat. Steps of installation: 1. Prepare the sprinkler key. 2. Remove the plastic cover. 3. Hold the sprinkler with the wrench and fasten it. 4. Replace the plastic cover and do not remove until the cover is installed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page SR1-3 or QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and stan-dards, whenever applicable. MIRAGE® STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Form No. F_103005 Rev 15.1 Page 5 of 6 DESIGN CRITERIA - FM (Also refer to Approval Chart 2 above.) FM Approval Requirements: Viking Concealed Pendent Sprinkler VK462 is FM Approved as a standard response Non-Storage concealed pendent sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page SR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac-cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Approval Chart 2 (FM) Mirage® Standard Response Concealed Pendent Sprinkler VK462 Sprinkler Base Part No.1 SIN NPT Thread Size Nominal K-Factor Maximum Water Working Pressure FM Approvals3 (Refer also to Design Criteria below.)Inch mm U.S.metric2 13503A VK462 1/2”15 5.6 80.6 175 psi (12 bar)AW1, BX1 Sprinkler Temperature Ratings A - 155 °F (68 °C) B - 175 °F (79 °C) and 200 °F (93 °C) Cover Plate Assembly Temperature Ratings4 W - 139 °F (59 °C) cover 135041, 136421 (large diameter), or 153941 (square cover plate) X - 165 °F (74 °C) cover 135041, 136421 (large diameter), or 153941 (square cover plate) Cover Plate Assembly Finishes5 1 - Polished Chrome, Brushed Chrome, Bright Brass, Antique Brass, Brushed Brass, Brushed Copper, Painted White, Painted Ivory, or Painted Black Footnotes 1 Part number shown is the base part number. For complete part number, refer to current Viking price list schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. Check with the manufacturer for any additional approvals. 4 The 139 °F (59 °C) cover has an orange label. The 165 °F (74 °C) cover has a white label. 5 Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors. Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. NOTE: Custom colors are indicated on a label inside the cover assembly. Refer to Figure 1. MIRAGE® STANDARD AND QR CONCEALED PENDENT SPRINKLER VK462 AND HP SPRINKLER VK463 (K5.6) TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Form No. F_103005 Rev 15.1 Page 6 of 6 Figure 4: Sprinkler Dimensions and Cover Installation Figure 3: Sprinkler Installation and Correct Use of Wrenches (Added CCCF Approval) MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6)TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Form No. F_033314 16.01.28 Rev 16.1 Page 1 of 6 1. DESCRIPTION The Viking Microfast® Quick Response Pendent Sprinkler VK302 is a small thermosensitive glass bulb spray sprinkler available with various finishes and temperature ratings to meet design requirements. The special Polyester, Polytetrafluoroethelyne (PTFE), and Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive atmospheres and are listed/approved as corrosion resistant as indicated in the Approval Charts. (Note: FM Global approves ENT finish as corrosion resistant. FM Global has no approval classification for PTFE and Polyester coatings as corro- sion resistant.) 2. LISTINGS AND APPROVALS cULus Listed: Category VNIV FM Approved: Class Series 2000 VdS Approved: Certificates G414009 and G414010 LPCB Approved CE Certified: Standard EN 12259-1:1999, A3:2006 Certificate of Constancy of Performance 0832-CPR-S0021 CCCF Approved: Approved by the China Certification Center for Fire Products (CCCF) Refer to Approval Chart 1 and Design Criteria cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria for FM Approval requirements that must be followed. 3. TECHNICAL DATA Specifications: Minimum Operating Pressure: 7 psi (0.5 bar) Rated to 175 psi (12 bar) water working pressureFactory tested hydrostatically to 500 psi (34.5 bar)Thread size: 1/2” NPT, 15 mm BSP Nominal K-Factor: 5.6 U.S. (80.6 metric**) Glass-bulb fluid temperature rated to -65 °F (-55 °C) Overall Length: 2-1/4” (58 mm) *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar). Material Standards: Frame Casting: Brass UNS-C84400 or QM Brass Deflector: Phosphor Bronze UNS-C51000 or Copper UNS-C19500 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape Screw: Brass UNS-C36000 Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400 For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated For Polyester Coated Sprinklers: Belleville Spring-Exposed For ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap - ENT plated. Ordering Information: (Also refer to the current Viking price list.) Order Quick Response Pendent Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, Black PTFE = N, and ENT = JN Temperature Suffix: 135 °F (57 °C) = A, 155 °F (68 °C) = B, 175 °F (79 °C) = D, 200 °F (93 °C) = E, 286 °F (141 °C) = G For example, sprinkler VK302 with a Brass finish and a 155 °F (68 °C) temperature rating = Part No. 12979AB Viking Technical Data may be found on The Viking Corporation’s Web site at http://www.vikinggroupinc.com. The Web site may include a more recent edition of this Technical Data Page. Replaces Form F_033314 Rev 15.2 (Revised temperature suffix designation) MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6)TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Form No. F_033314 16.01.28 Rev 16.1 Page 2 of 6 Available Finishes And Temperature Ratings: Refer to Table 1. Accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.) Sprinkler Wrenches: A. Standard Wrench: Part No. 10896W/B (available since 2000). B. Wrench for Recessed Pendent Sprinklers: Part No. 13655W/B** (available since 2006)C. Optional Protective Sprinkler Cap Remover/Escutcheon Installer Tool*** Part No. 15915 (available since 2010) **A ½” ratchet is required (not available from Viking). ***Allows use from the floor by attaching a length of 1” diameter CPVC tubing to the tool. Ideal for sprinkler cabinets. Refer to Bulletin F_051808. Sprinkler Cabinets: A. Six-head capacity: Part No. 01724A (available since 1971)B. Twelve-head capacity: Part No. 01725A (available since 1971) 4. INSTALLATIONRefer to appropriate NFPA Installation Standards. 5. OPERATION During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. INSPECTIONS, TESTS AND MAINTENANCERefer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. AVAILABILITY The Viking Microfast® Quick Response Pendent Sprinkler VK302 is available through a network of domestic and international dis-tributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GUARANTEE For details of warranty, refer to Viking’s current list price schedule or contact Viking directly. Figure 1: Standard Sprinkler Wrench 10896W/B Protective Sprinkler Cap Wrench FlatProtective Sprinkler Clip MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6)TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Form No. F_033314 16.01.28 Rev 16.1 Page 3 of 6 TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Bulb Color Ordinary 135 °F (57 °C)100 °F (38 °C)Orange Ordinary 155 °F (68 °C)100 °F (38 °C)Red Intermediate 175 °F (79 °C)150 °F (65 °C)Yellow Intermediate 200 °F (93 °C)150 °F (65 °C)Green High 286 °F (141 °C)225 °F (107 °C)Blue Sprinkler Finishes: Brass, Chrome, White Polyester, Black Polyester, Black PTFE, and ENT Corrosion-Resistant Coatings3: White Polyester, Black Polyester, and Black PTFE. ENT in all temperature ratings except 135 °F (57 °C) Footnotes 1 The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Charts. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are com- patible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester, PTFE, and ENT coatings. For ENT coated automatic sprinklers, the waterway is coated Figure 2: Wrench 13655W/B for Recessed Pendent Sprinklers Carefully slide the wrench sideways around the protective cap, ensuring engagement with the sprinkler wrench flats Sprinkler wrench 13655W/B** for recessed pendent sprinklers ** A 1/2” ratchet is required (not available from Viking) MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6)TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Form No. F_033314 16.01.28 Rev 16.1 Page 4 of 6 Approval Chart 1 (UL)The Viking Microfast® Quick Response Pendent Sprinkler VK302 Maximum 175 PSI (12 Bar) WWP Base Part Number1 SIN Sprinkler Style Thread Size Nominal K-Factor Overall Length Listings and Approvals3 (Refer also to Design Criteria.) NPT BSP U.S.metric2 Inches mm cULus4 VdS LPCB 7 12979 VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2, C2X A1 A1Z, B1Y D1Z, C1Y --D3Z NOTICE - Product Below - Limited Availability (Contact Local Viking Office) 06662B VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2, C2X ---------- 18021 VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1X, B1Y A1 A1X, B1Y D1X, C1Y8 D1X, C1Y9 -- Approved Temperature Ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C)B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)C - 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) D - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C) Approved Finishes 1 - Brass, Chrome, White Polyester5,6, Black Polyes-ter5,6 2 - ENT5 3 - Chrome Approved Escutcheons X - Standard surface-mounted escutcheon or the Viking Micromatic® Model E-1 Recessed EscutcheonY - Standard surface-mounted escutcheon or the Viking Microfast® Model F-1 Adjustable Escutcheon, or recessed with the Viking Micro-matic® Model E-1, E-2, or E-3 Recessed EscutcheonZ - Standard surface-mounted escutcheon or the Viking Microfast® Model F-1 Adjustable Escutcheon Footnotes 1 Base part number shown. For complete part number, refer to Viking’s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Other approvals may be in process. 4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5 cULus Listed as corrosion-resistant. 6 Other colors are available on request with the same Listings and Approvals as the standard colors. 7 CE Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001. 8 CE Certified, Standard EN 12259-1, EC-certificates of conformity 0832-CPD-2001 and 0832-CPD-2003.9 MED Certified, Standard EN 12259-1, EC-certificates of conformity 0832-MED-1003 and 0832-MED-1008. DESIGN CRITERIA - UL (Also refer to Approval Chart 1 above.) cULus Listing Requirements: The Viking Microfast® Quick Response Pendent Sprinkler VK302 is cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers. • Designed for use in Light and Ordinary occupancies. • The sprinkler installation rules contained in NFPA 13 for standard spray pendent sprinklers must be followed. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in accor- dance with the latest edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6)TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Form No. F_033314 16.01.28 Rev 16.1 Page 5 of 6 Approval Chart 2 (FM)The Viking Microfast® Quick Response Pendent Sprinkler VK302 Maximum 175 PSI (12 Bar) WWP Base Part Number1 SIN Sprinkler Style Thread Size Nominal K-Factor Overall Length FM Approvals3 (Refer also to Design Criteria.)NPT BSP U.S.metric2 Inches mm 12979 VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2X, C2 NOTICE - Product Below - Limited Availability (Contact Local Viking Office) 06662B VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y, D2X, C2 18021 VK302 Pendent 1/2”15 mm 5.6 80.6 2-1/4 58 A1Z, B1Y Approved Temperature Ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C) B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) C - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), 286 °F (141 °C) D - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C) Approved Finishes 1 - Brass, Chrome, White Polyester4, and Black Polyester4 2 - ENT5 Approved Escutcheons X - Standard surface-mounted escutcheon or the Viking Micromatic® Model E-1 Recessed Escutcheon Y - Standard surface-mounted escutcheon or the Viking Microfast® Model F-1 Adjustable Escutcheon, or recessed with the Viking Micromatic® Model E-1 or E-2 Recessed Escutcheon Z - Standard surface-mounted escutcheon or the Viking Microfast® Model F-1 Adjustable Escutcheon Footnotes 1 Base part number shown. For complete part number, refer to Viking’s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This table shows the FM Approvals available at the time of printing. Other approvals may be in process. 4 Other colors are available on request with the same Approvals as the standard colors. 5 FM approved as corrosion resistant. DESIGN CRITERIA - FM (Also refer to Approval Chart 2 above.) FM Approval Requirements: The Viking Microfast® Quick Response Pendent Sprinkler VK302 is FM Approved as quick response Non-storage upright and pendent sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria. IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to page QR1-3 for general care, installation, and maintenance information. Viking sprinklers are to be installed in ac- cordance with the latest edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. MICROFAST® QUICK RESPONSE PENDENT SPRINKLER VK302 (K5.6)TECHNICAL DATA The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058 Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: techsvcs@vikingcorp.com Form No. F_033314 16.01.28 Rev 16.1 Page 6 of 6 Figure 4: Sprinkler Dimensions with the Model E-1 and E-2 Recessed Escutcheons Figure 3: Sprinkler Dimensions with a Standard Escutcheon and the Model F-1 Adjustable Escutcheon 1/2” (15 mm) NPT 2-1/4” (57 mm)1-3/4” (44.5 mm) 2” (51 mm)Max. 2-1/8” (54 mm) 1-1/2” (38 mm)Min. Installed with a standard 1/8” surface-mounted escutcheon Installed with a Microfast Model F-1 Adjustable Escutcheon Ceiling Opening Size: 2-5/16” (58.7 mm) minimum 2-1/2” (63.5 mm) maximum Note: At maximum, adapter is exposed 1/2” (12.7 mm) from face of ceiling 1-3/4” (44.5 mm)Max. 2-1/8” (54 mm) 1-1/8” (28.6 mm)Min. 2”” (51 mm)Max. 1-1/8” (28.6 mm)Min. 2-1/8” (54 mm) Ceiling Opening Size: 2-5-16” (58.7 mm) minimum 2-1/2” (63.5 mm) maximum Installed with a Model E-1 Recessed Escutcheon Installed with a Model E-2 Thread-on Recessed Escutcheon Replaces Form F_0333314 Rev 15.2 (Revised temperature suffix designation) microfast® and microfastHP® quick resPonse uPrigHt and conventional sPrinklers tecHnical data December 4, 2013 the viking corporation, 210 n industrial Park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com 1. descriPtion Viking Microfast® and MicrofastHP® Quick Response Upright and Conventional (Old Style) Sprinklers are small, thermosensitive, glass-bulb spray sprinklers available in several different finishes, temperature ratings, and K-Factors to meet design require- ments. The special Polyester, Polytetrafluoroethylene (PTFE), and Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive atmos-pheres and are listed/approved as corrosion resistant as indicated in the Approval Charts. (Note: fm global approves the ent coating as corrosion resistant. FM Global has no approval classification for PTFE and Polyester coatings as corrosion resistant.) 2. listings and aPProvals culus listed: Category VNIV fm approved: Classes 2002 and 2020 nYc approved: Calendar Number 219-76-SA and MEA 89-92-E, Volume 16 aBs certified: Certificate 04-HS407984B-PDA vds approved: Certificates G4060054, G4060056, G4880046, G4930039, and G4980020 lPc approved: Ref. No. 096e/03, TE30401, and TE30872 ce certified: Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001, 0832-CPD-2003, 0786-CPD-40131, 0786-CPD-40171, and 0786-CPD-40278 med certified: Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008 note: Other International approval certificates are available upon request. Refer to Approval Chart 1 and Design Criteria on pages 51c-d for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 51e for FM Approval requirements that must be followed. 3. tecHnical data specifications: Available since 1987.Minimum Operating Pressure: 7 psi (0.5 bar)* maximum Working Pressure: sprinklers vk315 and vk340 are rated for use with water working pressures ranging from the minimum 7 psi (0.5 bar) up to 250 psi (17 bar) for high-pressure systems. High-pressure (HP) sprinklers can be identified by locating “250” stamped on the de-flector. all other Part nos. not mentioned above are rated to a maximum 175 psi (12 bar) wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Testing: U.S.A. Patent No. 4,831,870 Thread size: Refer to the Approval Charts Nominal K-Factor: Refer to the Approval Charts Glass-bulb fluid temperature rated to -65 °F (-55 °C) Overall Length: Refer to the Approval Charts *cULus Listing, FM Approval, and NFPA 13 installs require a minimum of 7 psi (0.5 bar). The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi (0.35 bar). material standards: Frame Casting: Brass UNS-C84400 or QM Brass for Sprinklers 12978, 06766B, 07060, and 12281. Brass UNS-C84400 for all other sprinklers. Deflector: Brass UNS-C23000 or Copper UNS-C19500 for Sprinklers 12978, 06764B, and 12281. Copper UNS-C19500 for Sprinklers 06665B, 07060, and 14817. Brass UNS-C26000 for all other Sprinklers.Bushing (for Sprinklers 06719B, 06717B, and 12286): Brass UNS-C36000 Bulb: Glass, nominal 3 mm diameter Form No. F_080488 viking technical data may be found on the viking corporation’s Web site at http://www.vikinggroupinc.com. the Web site may include a more recent edition of this technical data Page. Sprinkler 51a Replaces page 51a-e, dated June 28, 2013. (Changed 06931 to VK3271) tecHnical data December 4, 2013 the viking corporation, 210 n industrial Park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com microfast® and microfastHP® quick resPonse uPrigHt and conventional sPrinklers Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE TapeScrew: Brass UNS-C36000Pip Cap and Insert Assembly: Copper UNS-C11000 and Stainless Steel UNS-S30400For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE CoatedFor Polyester Coated Sprinklers: Belleville Spring-ExposedFor ENT Coated Sprinklers: Belleville Spring-Exposed, Screw and Pipcap - ENT plated.ordering information: (Also refer to the current Viking price list.)Order Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, and Black PTFE = N, ENT = JNTemperature Suffix (°F/°C): 135°/57° = A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = GFor example, sprinkler VK300 with a 1/2” thread, Brass finish and a 155 °F/68 °C temperature rating = Part No. 12978AB available finishes and temperature ratings: Refer to Table 1. accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.) sprinkler Wrench: Standard Wrench: Part No. 10896W/B (available since 2000) sprinkler cabinets:A. Six-head capacity: Part No. 01724A (available since 1971)B. Twelve-head capacity: Part No. 01725A (available since 1971) 4. installationRefer to appropriate NFPA Installation Standards. 5. oPeration During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. insPections, tests and maintenanceRefer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. availaBilitY The Viking Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. guaranteeFor details of warranty, refer to Viking’s current list price schedule or contact Viking directly. Sprinkler 51b taBle 1: availaBle sPrinkler temPerature ratings and finisHes sprinkler temperature classification sprinkler nominal temperature rating1 maximum ambient ceiling temperature2 Bulb color Ordinary 135 °F (57 °C)100 °F (38 °C)Orange Ordinary 155 °F (68 °C)100 °F (38 °C)Red Intermediate 175 °F (79 °C)150 °F (65 °C)Yellow Intermediate 200 °F (93 °C)150 °F (65 °C)Green High 286 °F (141 °C)225 °F (107 °C)Blue sprinkler finishes: Brass, Chrome, White Polyester, Black Polyester, Black PTFE, and ENT corrosion-resistant coatings3: White Polyester, Black Polyester, and Black PTFE. ENT in all temperature ratings except 135 °F (57 °C) footnotes 1 The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards.3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated on pages 51c-e. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compatible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. Note that the spring is exposed on sprinklers with Polyester, ENT, and PTFE coatings. For ENT coated automatic sprinklers, the waterway is coated. microfast® and microfastHP® quick resPonse uPrigHt and conventional sPrinklers tecHnical data December 4, 2013 the viking corporation, 210 n industrial Park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com approval chart 1 (ul) microfast® and microfastHP® quick response upright and conventional sprinklers maximum 175 Psi (12 bar) WWP Base Part number1 sin thread size nominal k-factor overall length listings and approvals3 (refer also to design criteria on page 51d.) nPt BsP u.s.metric2 inches mm culus4 nYc8 vds lPcB upright-standard orifice 12978 VK300 1/2”15 mm 5.6 80.6 2-3/16 56 A1, B4 See Footnote 7.-------- 07060 VK345 --15 mm 5.6 80.6 2-3/16 56 ----A2 A2 B212 B215 conventional-standard orifice 06766B VK310 1/2”15 mm 5.6 80.6 2-3/16 56 A2 A2 --A2 B212 B215 upright-large orifice 06665B VK350 3/4”--8.0 115.2 2-5/16 59 A1, B4 A1 A2 A2 B212 -- 14817 VK350 --20 mm 8.0 115.2 2-5/16 59 A1, B4 A1 A2 A2 B212 -- 06764B16 VK350 1/2”15 mm 8.0 115.2 2-5/16 59 A1, B4 A1 A2 --A213 -- conventional-large orifice 06768B VK354 3/4”20 mm 8.0 115.2 2-5/16 59 A1 A2 --A2 B212 -- upright-small orifice11 06717B11 VK325 1/2”15 mm 2.8 40.3 2-3/16 56 A1 A1 -------- 06719B11 VK327 1/2”15 mm 4.2 57 2-3/16 56 A1 A1 -------- 06931B11 VK3271 --10 mm 4.2 57 2-3/16 56 ----A2 --C314 -- maximum 250 Psi (17 bar) WWP upright-standard orifice Base Part number1 sin thread size nominal k-factor overall length listings and approvals3 (refer also to design criteria on page 51d.) nPt BsP u.s.metric2 inches mm culus4 nYc9 vds lPcB 12281 VK315 1/2”15 mm 5.6 80.6 2-3/16 56 A1 A1 -------- upright-small orifice10 1228611 VK340 1/2”15 mm 2.8 40.3 2-3/16 56 A1 A1 -------- approved temperature ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) C - 155 °F (68 °C) approved finishes 1 - Brass, Chrome, White Polyester5,6, Black Polyester5,6, and Black PTFE5 2 - Brass, Chrome, White Polyester5,6, and Black Polyester5,6 3 - Brass and Chrome 4 - ENT5 footnotes 1 Base part number is shown. For complete part number, refer to Viking’s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals. 4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada. 5 cULus Listed as corrosion resistant. 6 Other colors are available on request with the same Listings and Approvals as the standard colors. 7 Meets New York City requirements, effective July 1, 2008. 8 Accepted for use, City of New York Board of Standards and Appeals, Calendar Number 219-76-SA. 9 Accepted for use, City of New York Department of Buildings, MEA 89-92-E, Vol. 16. 10 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only. exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally galvanized. 11The sprinkler orifice is bushed. 12 Certified, Standard EN 12259-1, EC-certificate of conformity 0832-CPD-2001 and 0832-CPD-2003. 13 Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40278. 14 Certified, Standard EN 12259-1, EC-certificate of conformity 0786-CPD-40131. 15 MED Certified, Standard EN 12259-1, EC-certificate of conformity 0832-MED-1003 and 0832-MED-1008. 16 The 1/2” NPT Large Orifice Sprinkler is Listed and Approved for retrofit only Sprinkler 51c tecHnical data December 4, 2013 the viking corporation, 210 n industrial Park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com microfast® and microfastHP® quick resPonse uPrigHt and conventional sPrinklers Sprinkler 51d figure 1: standard sprinkler Wrench 10896W/B design criteria - ul (Also refer to Approval Chart 1 on page 51c) culus listing requirements: Microfast® and MicrofastHP® Quick Response Upright and Conventional Sprinklers are cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest edition of NFPA 13 for standard spray sprinklers, or old style (conventional) sprinklers. Designed for use in Light and Ordinary Hazard occupancies (exception: small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet systems only). The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed. For conventional sprinklers, refer to the installation guidelines for old style (conventional) sprinklers. • • imPortant: always refer to Bulletin form no. f_091699 - care and Handling of sprinklers. also refer to page qr1-3 for general care, installation, and maintenance information. viking sprinklers are to be installed in accor- dance with the latest edition of viking technical data, the appropriate standards of nfPa, lPcB, aPsad, vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. microfast® and microfastHP® quick resPonse uPrigHt and conventional sPrinklers tecHnical data December 4, 2013 the viking corporation, 210 n industrial Park drive, Hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com Sprinkler 51e design criteria - fm (Also refer to Approval Chart 2 above.) fm approval requirements: The sprinklers indicated in Approval Chart 2 are FM Approved as quick response non-storage upright sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. note: the fm installation guidelines may differ from culus and/or nfPa criteria. imPortant: always refer to Bulletin form no. f_091699 - care and Handling of sprinklers. also refer to page qr1-3 for general care, installation, and maintenance information. viking sprinklers are to be installed in ac- cordance with the latest edition of viking technical data, the appropriate standards of nfPa, fm global, lPcB, aPsad, vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. approval chart 2 (fm) microfast® quick response upright sprinklers maximum 175 Psi (12 bar) WWP Base Part number1 sin thread size nominal k-factor overall length fm approvals3 (refer also to design criteria below.)nPt BsP u.s.metric2 inches mm standard orifice 12978 VK300 1/2”15 mm 5.6 80.6 2-3/16 56 A2, B3 07060 VK345 --15 mm 5.6 80.6 2-3/16 56 A2 large orifice 06665B VK350 3/4”--8.0 115.2 2-5/16 59 A2, B3 14817 VK350 --20 mm 8.0 115.2 2-5/16 59 A2, B3 06764B7 VK350 1/2”15 mm 8.0 115.2 2-5/16 59 A2, B3 small orifice4 06717B6 VK325 1/2”15 mm 2.8 40.3 2-3/16 56 A1 approved temperature ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) B - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141°C) approved finishes 1 - Brass and Chrome 2 - Brass, Chrome, White Polyester5, and Black Polyester5 3 - ENT8 footnotes 1 Base part number is shown. For complete part number, refer to Viking’s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This table shows the FM Approvals available at the time of printing. Check with the manufacturer for any additional approvals. 4 FM Approved as quick response non-storage pendent sprinklers. For specific application and installation requirements, reference the latest appli- cable FM Loss Prevention Data Sheets (including Data Sheet 2-0). 5 Other colors are available on request with the same Approvals as the standard colors. 6 The sprinkler orifice is bushed. 7 The 1/2” NPT Large Orifice Sprinkler is Listed and Approved for retrofit only 8 FM approved as corrosion resistant. microfast® and micro- fasthp® quick response horizontal sidewall sprinklers (vk305 & vk319) technical data February 3, 2014 the viking corporation, 210 n industrial park drive, hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com 1. descriptionViking Microfast® and MicrofastHP® Quick Response Horizontal Sidewall Sprinklers are small thermosensitive glass bulb spray sprinklers available with various finish-es and temperature ratings to meet design requirements. The special Polyester, Polytetrafluoroethelyne (PTFE), and Electroless Nickel PTFE (ENT) coatings can be used in decorative applications where colors are desired. In addition, these coatings have been investigated for installation in corrosive atmospheres and are listed/approved as corrosion resistant as indicated in the Approval Chart. 2. listinGs and approvals culus listed: Category VNIV fm approved: Class 2020 nYc approved: MEA 89-92-E, Volume 16 Refer to Approval Chart 1 and Design Criteria on page 43d for cULus Listing requirements, and refer to Approval Chart 2 and Design Criteria on page 43f for FM Approval requirements that must be followed. 3. technical data specifications:Available since 2003.Minimum Operating Pressure: 7 psi (0.5 bar) maximum working pressure: sprinkler vk319 is rated for use with water working pressures ranging from the minimum 7 psi (0.5 bar) up to 250 psi (17 bar) for high-pressure systems. high-pressure (hp) sprinklers can be identified by locating “250” stamped on the deflec-tor. sprinkler vk305 is rated to a maximum 175 psi (12 bar) wwp. Factory tested hydrostatically to 500 psi (34.5 bar) Nominal K-Factor: 5.6 U.S. (80.6 metric*) * Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. Glass-bulb fluid temperature rated to -65 °F (-55 °C) Overall Length: 2-11/16” (68 mm) material standards: Frame Casting: Brass UNS-C84400 Deflector: Copper UNS-C19500 Bulb: Glass, nominal 3 mm diameter Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE TapeScrew: Brass UNS-C36000 Pip Cap: Copper UNS-C11000 and Stainless Steel UNS-S30400 Pip Cap Attachment (for Sprinkler VK319): Brass UNS-C36000 For PTFE Coated Sprinklers: Belleville Spring-Exposed, Screw-Nickel Plated, Pip Cap-PTFE Coated For Polyester Coated Sprinklers: Belleville Spring-ExposedFor ENT Coated Sprinklers: Belleville Spring - Exposed, Screw and Pip cap - ENT plated. ordering information: (Also refer to the current Viking price list.) Order Quick Response Horizontal Sidewall Sprinklers by first adding the appropriate suffix for the sprinkler finish and then the ap- propriate suffix for the temperature rating to the sprinkler base part number. Finish Suffix: Brass = A, Chrome = F, White Polyester = M-/W, Black Polyester = M-/B, Black PTFE = N, and ENT = JNTemperature Suffix (°F/°C): 135°/68° = A, 155°/68° = B, 175°/79° = D, 200°/93° = E, and 286°/141° = G For example, sprinkler VK305 with a Brass finish and a 155 °F/68 °C temperature rating = Part No. 12121AB available finishes and temperature ratings: Refer to Table 1. accessories: (Also refer to the “Sprinkler Accessories” section of the Viking data book.) Form No. F_030103 viking technical data may be found on the viking corporation’s web site at http://www.vikinggroupinc.com. the web site may include a more recent edition of this technical data page. Sprinkler 43a Replaces page 43a-f, dated December 12, 2013. (Added ENT Finish) technical data February 3, 2014 the viking corporation, 210 n industrial park drive, hastings mi 49058telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com microfast® and micro- fasthp® quick response horizontal sidewall sprinklers (vk305 & vk319) sprinkler wrenches: A. Standard Wrench: Part No. 10896W/B (available since 2000). B. Wrench for recessed sprinklers with protective shields: Part No. 13655W/B** (available since 2003) **A ½” ratchet is required (not available from Viking). sprinkler cabinets: A. Six-head capacity: Part No. 01724A (available since 1971) B. Twelve-head capacity: Part No. 01725A (available since 1971) 4. installation Refer to appropriate NFPA Installation Standards. 5. operation During fire conditions, the heat-sensitive liquid in the glass bulb expands, causing the glass to shatter, releasing the pip cap and sealing spring assembly. Water flowing through the sprinkler orifice strikes the sprinkler deflector, forming a uniform spray pattern to extinguish or control the fire. 6. inspections, tests and maintenanceRefer to NFPA 25 for Inspection, Testing and Maintenance requirements. 7. availabilitY Viking Quick Response Horizontal Sidewall Sprinklers are available through a network of domestic and international distributors. See The Viking Corporation web site for the closest distributor or contact The Viking Corporation. 8. GuaranteeFor details of warranty, refer to Viking’s current list price schedule or contact Viking directly. Sprinkler 43b figure 1: standard sprinkler wrench 10896w/b microfast® and micro- fasthp® quick response horizontal sidewall sprinklers (vk305 & vk319) technical data February 3, 2014 the viking corporation, 210 n industrial park drive, hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com table 1: available sprinkler temperature ratinGs and finishes sprinkler temperature classification sprinkler nominal temperature rating1 maximum ambient ceiling temperature2 bulb color Ordinary 135 °F (57 °C)100 °F (38 °C)Orange Ordinary 155 °F (68 °C)100 °F (38 °C)Red Intermediate 175 °F (79 °C)150 °F (65 °C)Yellow Intermediate 200 °F (93 °C)150 °F (65 °C)Green High 286 °F (141 °C)225 °F (107 °C)Blue sprinkler finishes: Brass, Chrome, White Polyester, Black Polyester, Black PTFE, and ENT corrosion-resistant coatings3: White Polyester, Black Polyester, Black PTFE , and ENT footnotes 1 The sprinkler temperature rating is stamped on the deflector. 2 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. Refer to specific installation standards. 3 The corrosion-resistant coatings have passed the standard corrosion test required by the approving agencies indicated in the Approval Chart. These tests cannot and do not represent all possible corrosive environments. Prior to installation, verify through the end-user that the coatings are compat- ible with or suitable for the proposed environment. For automatic sprinklers, the coatings indicated are applied to the exposed exterior surfaces only. For ENT coated sprinklers, the waterway is coated. Note that the spring is exposed on sprinklers with Polyester, PTFE, and ENT coatings. Sprinkler 43c figure 2: wrench 13655w/b for recessed horizontal sidewall sprinklers technical data February 3, 2014 the viking corporation, 210 n industrial park drive, hastings mi 49058telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com microfast® and micro- fasthp® quick response horizontal sidewall sprinklers (vk305 & vk319) approval chart 1 (ul) microfast® and microfasthp® quick response horizontal sidewall sprinklers base part number1 sin maximum pressure thread size nominal k-factor overall length listings and approvals3 (refer also to design criteria below.) npt bsp u.s.metric2 inches mm culus4 nYc5 lpcb maximum 175 psi (12 bar) wwp for light or ordinary hazard occupancies. deflector must be located 4” to 12” (102 mm to 305 mm) below the ceiling. 12121 VK305 175 psi 1/2”15 mm 5.6 80.6 2-11/16 68 A1Y, B1X, C2W, D2Z A1Y ------ maximum 175 psi wwp for light hazard occupancies only. deflector must be located 4” to 6” (102 mm to 152 mm) below the ceiling. 12121 VK305 175 psi 1/2”15 mm 5.6 80.6 2-11/16 68 culus nYc lpcb A1Y, B1X, C2W, D2Z See Footnote 6.------ maximum 250 psi wwp for light or ordinary hazard occupancies. deflector must be located 4” to 12” (102 mm to 305 mm) below the ceiling. 12285 VK319 250 psi 1/2”15 mm 5.6 80.6 2-11/16 68 culus4 nYc5 lpcb A1Y, B1X, C2W, D2Z A1Y ------ approved temperature ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C)B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C)C - 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C)D - 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) approved finishes 1 - Brass, Chrome, White Polyester7,8, Black Polyester7,8, and Black PTFE7 2 - ENT7 approved escutcheonsW - Installed with standard surface-mounted escutcheons.X - Installed with standard surface-mounted escutcheons or the Viking Microfast® Model F-1 Adjustable Escutcheon, or re-cessed with the Viking Micromatic® Model E-1, E-2, E-3, or G-1 Recessed EscutcheonY - Installed with standard surface-mounted escutcheons or the Viking Microfast® Model F-1 Adjustable EscutcheonZ - Installed with standard surface-mounted escutcheons or re-cessed with the Viking Micromatic Model E-1 footnotes1 Base part number shown. For complete part number, refer to Viking’s current price schedule.2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.3 This table shows the listings and approvals available at the time of printing. Other approvals may be in process.4 Listed by Underwriters Laboratories Inc. for use in the U.S. and Canada.5 Accepted for use, City of New York Department of Buildings, MEA 89-92-E, Vol. 16. 6 Meets New York City requirements, effective July 1, 2008. 7 cULus Listed as corrosion-resistant.8 Other colors are available on request with the same Listings and Approvals as the standard colors. Sprinkler 43d desiGn criteria - ul (Also refer to Approval Chart 1 above.) culus listing requirements: Quick Response Horizontal Sprinklers VK305 and VK319 are cULus Listed as indicated in the Approval Chart for installation in accordance with the latest edition of NFPA 13 for sidewall standard spray sprinklers. Designed for use in Light and Ordinary Hazard occupancies.Locate the deflector 4” to 12“ (102 mm to 305 mm) below the ceiling. Protection areas and maximum spacing shall be in accordance with the tables provided in NFPA 13. Minimum spacing allowed is 6 ft. (1.8 m). Align the top of the deflector parallel with the ceiling. Locate no less than 4” (102 mm) from end walls.Maximum distance from end walls shall be no more than one-half of the allowable distance between sprinklers. The distance shall be measured perpendicular to the wall. The sprinkler installation and obstruction rules contained in NFPA 13 for sidewall standard spray sprinklers must be followed. • • • • • • • • important: always refer to bulletin form no. f_091699 - care and handling of sprinklers. also refer to page qr1-3 for general care, in-stallation, and maintenance information. viking sprinklers are to be installed in accordance with the latest edition of viking technical data, the appropriate standards of nfpa, lpcb, apsad, vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. microfast® and micro- fasthp® quick response horizontal sidewall sprinklers (vk305 & vk319) technical data February 3, 2014 the viking corporation, 210 n industrial park drive, hastings mi 49058 telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com Sprinkler 43e figure 3: sidewall sprinkler vk305 dimensions with a standard escutcheon and the model f-1 adjustable escutcheon figure 4: sidewall sprinkler vk305 dimensions with the model e-1 and e-2 recessed escutcheons technical data February 3, 2014 the viking corporation, 210 n industrial park drive, hastings mi 49058telephone: 269-945-9501 technical services: 877-384-5464 fax: 269-818-1680 email: techsvcs@vikingcorp.com microfast® and micro- fasthp® quick response horizontal sidewall sprinklers (vk305 & vk319) Form No. F_030103 figure 5: sidewall sprinkler vk305 dimensions with the model G-1 recessed escutcheons approval chart 2 (fm) microfast® quick response horizontal sidewall sprinklers maximum 175 psi wwp base part number1 sin maximum pressure thread size nominal k-factor overall length fm approvals3 (refer also to design criteria below.)npt bsp u.s.metric2 inches mm 12121 VK305 175 psi 1/2”15 mm 5.6 80.6 2-11/16 68 A1Y, B1X approved temperature ratings A - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), 200 °F (93 °C), and 286 °F (141 °C) B - 135 °F (57 °C), 155 °F (68 °C), 175 °F (79 °C), and 200 °F (93 °C) approved finish 1 - Brass approved escutcheons X - Installed with standard surface-mounted escutcheons or the Viking Microfast® Model F-1 Adjustable Escutcheon, or recessed with the Viking Micromatic® Model E-1, E-2, E-3, or G-1 Recessed EscutcheonY - Installed with standard surface-mounted escutcheons or the Viking Microfast® Model F-1 Adjustable Escutcheon footnotes 1 Base part number shown. For complete part number, refer to Viking’s current price schedule. 2 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0. 3 This table shows the FM Approvals available at the time of printing. Other approvals may be in process. Sprinkler 43f desiGn criteria - fm (Also refer to Approval Chart 2 above.) fm approval requirements: Horizontal Sidewall Sprinkler VK305 is FM Approved as a quick response non-storage sidewall sprinkler as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling. note: the fm installation guidelines may differ from culus and/or nfpa criteria. important: always refer to bulletin form no. f_091699 - care and handling of sprinklers. also refer to page qr1-3 for general care, installation, and maintenance information. viking sprinklers are to be installed in ac-cordance with the latest edition of viking technical data, the appropriate standards of nfpa, fm Global, lpcb, apsad, vds or other similar organizations, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. Replaces page 43a-f, dated December 12, 2013. (Added ENT Finish) Worldwide Contacts www.tyco-fire.com General Description TYCO Series DS-C Dry Type Sprinklers, 5.6K Concealed Pendent, Standard (5 mm Bulb) and Quick Response (3 mm Bulb) and Standard Coverage, are decorative sprinklers featuring a flat cover plate designed to conceal the sprinkler. This type of sprinkler is typically used to provide a sprinkler drop from an unheated attic into an area where aesthetics is a concern, such as nursing homes, restaurants, and schools. Each unit includes a Cover Plate Assembly that conceals the sprinkler operating components above the ceiling. The separable two-piece design of the Cover Plate and Support Cup Assemblies allows installation of the sprinklers and pressure testing of the fire protection system prior to installation of a suspended ceiling or application of the finish coating to a fixed ceiling. They also permit removal of suspended ceiling panels for access to building service equipment without having to first shut down the fire protec-tion system and remove sprinklers. Also, the separable two-piece design of the Sprinkler provides for 1/2 inch (12,7 mm) of vertical adjustment. Series DS-C Sprinklers are shipped with a Disposable Protective Cap. The Protective Cap is temporarily removed for installation, and then it can be replaced to help protect the sprinkler while the ceiling is installed or finished. The tip of the Protective Cap can also be used to mark the center of the ceiling hole into plaster board and ceiling tiles by gently pushing the ceiling product against the Protective Cap. When the ceiling installation is complete the Protective Cap is removed and the Cover Plate Assembly installed. NOTICE Series DS-C Dry Type Concealed Pendent Sprinklers described herein must be installed and maintained in compliance with this document and the applicable standards of the National Fire Protection Association, in addition to the standards of any authorities having jurisdiction. Failure to do so may impair the performance of these devices. The owner is responsible for main-taining their fire protection system and devices in proper operating condition. The installing contractor or sprinkler manufacturer should be contacted with any questions. Series DS-C Dry Type Concealed Pendent Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. Sprinkler Identification Numbers (SINs) TY3535 - 3 mm Bulb TY3555 - 5 mm Bulb Technical Data ApprovalsUL and C-UL Listed NYC Approved under MEA 352-01-E-2 Maximum Working Pressure175 psi (12,1 bar) Inlet Thread Connections• 1 inch NPT (Standard Order) • ISO 7-R1 Discharge CoefficientK=5.6 GPM/psi1/2 (80,6 LPM/bar1/2) Temperature Ratings• 155°F (68°C) Sprinkler with 139°F (59°C) Cover Plate • 200°F (93°C) Sprinkler with 165°F (74°C) Cover Plate Adjustment1/2 inch (12,7 mm) FinishesRefer to Ordering Procedure section. IMPORTANTAlways refer to Technical Data Sheet TFP700 for the “INSTALLER WARNING” that provides cautions with respect to handling and instal-lation of sprinkler systems and components. Improper handling and installation can permanently damage a sprinkler system or its compo-nents and cause the sprinkler to fail to operate in a fire situation or cause it to operate prematurely. Series DS-C Dry Type Sprinklers 5.6K Concealed Pendent Standard and Quick Response, Standard Coverage Page 1 of 8 JUNE 2013 TFP515 Worldwide Contacts www.tyco-fire.com INSERT FRAME BULB DEFLECTOR GUIDE PIN VENT HOLE CASING GUIDE TUBE SPRING INLET YOKE INLET BAND WATERTUBE BULB SEAT COMPRESSION SCREW EJECTION SPRING COVERPLATESOLDERTAB RETAINER WITH THREAD DIMPLES DEFLECTOR (DROPPED POSITION) PLUG WITHGASKETEDSPRINGPLATE SEAL SUPPORT CUP WITH ROLL FORMED THREADS THREAD INTO SUPPORT CUP UNTIL MOUNTING SURFACE IS FLUSH WITH CEILING COVER PLATERETAINERASSEMBLY SPRINKLERSUPPORT CUPASSEMBLY FIGURE 1 SERIES DS-C STANDARD COVERAGE DRY-TYPE CONCEALED PENDENT SPRINKLER ASSEMBLY Physical CharacteristicsInlet.....................CopperPlug .................... CopperYoke ..............Stainless SteelCasing ...............Galvanized Carbon SteelInsert ...................BronzeBulb Seat ..........Stainless SteelBulb ......................GlassDeflector.................BronzeFrame...................BronzeGuide Tube .........Stainless SteelWater Tube ......... Stainless SteelSpring.............Stainless SteelGasketed SpringPlate Seal .........Beryllium Nickel w/TEFLONSupport Cup........Chrome Plated SteelGuide Pins .........Stainless SteelCompression Screw . . . . . . . . BrassCover Plate................BrassRetainer ..................BrassEjection Spring......Stainless Steel Operation When TYCO Series DS-C Dry Type Concealed Pendent Sprinklers is in service, water is prevented from entering the assembly by the Plug with Gasketed Spring Plate Seal (Figure 1) in the Inlet of the Sprinkler. When exposed to heat from a fire, the Cover Plate, which is normally soldered to the Retainer at three points, falls away to expose the Sprinkler Assembly. At this point the Deflector supported by the Guide Pins drops down to its opera-tional position. The glass bulb contains a fluid that expands when exposed to heat. When the rated temperature is reached, the fluid expands sufficiently to shatter the glass bulb, and the Bulb Seat is released. The compressed Spring is then able to expand and push the Water Tube as well as the Guide Tube outward. This action simultaneously pulls inward on the Yoke, withdrawing the Plug with Gasketed Spring Plate Seal, from the Inlet, allowing the sprinkler to activate and flow water. TFP515Page 2 of 8 COVER PLATE RETAINER ASSEMBLY SPRINKLER FITTING (REFER TO DESIGN CRITERIA SECTION) FACE OF SPRINKLER FITTING 2-1/2" DIA. (63,5 mm) SPRINKLER SUPPORT CUP ASSEMBLY 1/2" (12,7 mm) THREADED ADJUSTMENT ORDER LENGTHS: 5" (127,0 mm) to 48" (1219,2 mm) IN 1/4" (6,4 mm) INCREMENTS FACE OF CEILING, RETAINING RING MOUNTING SURFACE 3/16" to 11/16" (4,8 to 17,5 mm) REFERENCE 3/16" (4,8 mm)FACTORY PRESET GAP 3/32" (2,4 mm) DEFLECTOR IN DROPPED POSITION 3-1/4" DIA. (82,6 mm) FIGURE 2 SERIES DS-C STANDARD COVERAGE DRY-TYPE CONCEALED PENDENT SPRINKLER INSTALLATION DIMENSIONS 2-1/2" DIA. (63,5 mm) CLEARANCE HOLE FIGURE 3 DISPOSABLE PROTECTIVE CAP ACCEPTS 1/2" SOCKET DRIVE ALIGN ARROWS WITH FRAME ARMS 7/8" (23 mm) SQUARE SUPPORT CUP FRAME ARM FIGURE 4 RFII SPRINKLER WRENCH TFP515 Page 3 of 8 Design Criteria TYCO Series DS-C 3 mm bulb-type Dry Type Concealed Pendent Sprinklers (TY3535) are UL and C-UL Listed as quick response, standard spray sprinklers for use in accordance with the current NFPA standard. Series DS-C 5 mm bulb-type Dry Type Concealed Pendent Sprinklers (TY3555) are UL and C-UL Listed as standard response, standard spray sprinklers for use in accordance with the current NFPA standard. Series DS-C Dry Type Sprinklers are only listed when installed with Series RFII Concealed Cover Plates having a factory-applied painted or metallic finish. Series DS-C Dry Type Sprinklers must not be used in applications where the air pressure above the ceiling is greater than that below. Down drafts through the Support Cup could delay sprinkler operation in a fire situation. Sprinkler FittingsInstall 1 inch NPT Series DS-C Dry Type Concealed Pendent Sprinklers in the 1 inch NPT outlet or run of the following fittings: • malleable or ductile iron threaded tee fittings that meet the dimen-sional requirements of ANSI B16.3 (Class 150) • cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16.4 (Class 125) Do not install Series DS-C Dry Type Concealed Pendent Sprinklers into elbow fittings. The Inlet of the sprinkler can contact the interior of the elbow. The unused outlet of the threaded tee is plugged as shown in Figures 5 and 6. You can also install Series DS-C Dry- Type Sprinklers in the outlet. The configuration shown in Figure 5 is only applicable for wet pipe systems where the sprinkler fitting and water-filled pipe above the sprinkler fitting are not subject to freezing and where the length of the Dry Type Sprinkler has the minimum exposure length depicted in Figure 7. Refer to the Exposure Length section. For wet pipe system installations of 1 inch NPT Series DS-C Dry Type Sprinklers connected to CPVC piping, use only the following TYCO CPVC fittings: • 1” x 1” NPT Female Adapter (P/N 80145). • 1” x 1” x 1” NPT Sprinkler Head Adapter Tee (P/N 80249). For dry pipe system installations, use only the side outlet of maximum 2-1/2 inch reducing tee when locating Series DS-C Dry Type Sprinklers directly below the branch line. Otherwise, use the configuration shown in Figure 6 to assure complete water drainage from above Series DS-C Dry Type Sprinklers and the branch line. Failure to do so may result in pipe freezing and water damage. NOTICE Do not install Series DS-C Dry Type Sprinklers into any other type fitting without first consulting the Technical Services Department. Failure to use the appropriate fitting may result in one of the following: • failure of the sprinkler to operate properly due to formation of ice over the Inlet Plug or binding of the Inlet Plug • insufficient engagement of the Inlet pipe-threads with consequent leakage DrainageIn accordance with the minimum requirements of the National Fire Protection Association for dry pipe sprinkler systems, branch, cross, and feed-main piping connected to Dry Sprinklers and subject to freezing temperatures must be pitched for proper drainage. Exposure LengthWhen using Dry Type Sprinklers in wet pipe sprinkler systems to protect areas subject to freezing temperatures, use Table A to determine a sprinkler’s appro-priate exposed barrel length to prevent water from freezing in the connecting pipes due to conduction. The exposed barrel length measurement must be taken from the face of the sprinkler fitting to the surface of the structure or insulation that is exposed to the heated area. Refer to Figure 7 for an example. For protected area temperatures between those given above, the minimum recommended length from the face of the fitting to the outside of the protected area may be determined by interpolating between the indicated values. Do not attempt to add additional insu-lation around the barrel in the heated area as a method to minimize conden-sation. This will reduce the calculated “Exposure Length”. Clearance SpaceIn accordance with Section 8.4.9.2 of the 2010 edition of NFPA 13, where dry sprinklers are connected to wet pipe sprinkler systems protecting insulated freezer structures, the clearance space around the sprinkler barrel of Dry Type Sprinklers must be sealed. Due to temperature differences between two areas, the potential for the formation of condensation in the sprinkler and subsequent ice build-up is increased. If this condensation is not controlled, ice build-up can occur that might damage the dry type sprinkler and/or prevent proper operation in a fire situation. Use of the Model DSB-2 Dry Sprinkler Boot, described in technical data sheet TFP591 and shown in Figure 8, will provide the recommended seal. NOTICE For applications where a bore greater than 1-3/4 inches in diameter has been cut through the entire height of an insulated freezer ceiling creating a cavity above the sprinkler support cup (Figure 8), the cavity must not be filled. TFP515Page 4 of 8 Installation TYCO Series DS-C Dry Concealed Pendent Sprinklers must be installed in accordance with this section. Series DS-C Dry Type Concealed Pendent Sprinklers must only be installed in fittings that meet the requirements of the Design Criteria section. Refer to the Design Criteria section for other important require-ments regarding piping design and sealing of the clearance space around the Sprinkler Casing. Do not install any bulb type sprinkler if the bulb is cracked or there is a loss of liquid from the bulb. With the sprinkler held horizontally, a small air bubble should be present. The diameter of the air bubble is approximately 1/16 inch (1,6 mm). A leak-tight 1 inch NPT sprinkler joint should be obtained by applying a minimum-to-maximum torque of 20 to 30 ft. lbs. (26,8 to 40,2 Nm). Higher levels of torque may distort the sprinkler Inlet with consequent leakage or impair-ment of the sprinkler. Do not attempt to compensate for insufficient adjustment in the Sprinkler Assembly by under or over-tightening the Sprinkler/Support Cup Assembly. Re-adjust the position of the sprinkler fitting to suit. Step 1. Install the sprinkler in the pendent position with the centerline of the sprinkler perpendicular to the mounting surface. Step 2. With a non-hardening pipe-thread sealant such as TEFLON pipe-thread sealant applied to the Inlet threads, hand-tighten the sprinkler into the sprinkler fitting. Step 3. Wrench-tighten the sprinkler using either: • a pipe wrench on the Inlet Band or the Casing (Figure 1). • the RFII Sprinkler Wrench on the wrench flat (Figure 4). Apply the wrench recess of the RFII Sprinkler Wrench to the wrench flat. Note: If sprinkler removal becomes necessary, remove the sprinkler using the same wrenching method noted above. Sprinkler removal is easier when a non-hardening sealant was used and torque guidelines were followed. After removal, inspect the sprinkler for damage. When using the RFII Sprinkler Wrench, temporarily remove the Protective Cap. Replace the Protective Cap (Figure 4) by pushing it upwards until it bottoms out against the Support Cup. The Protective Cap helps prevent damage to the Deflector and Arms during ceiling installation and/or during application of the finish coating of the ceiling. It may also be used to locate the center of the clearance hole by gently pushing the ceiling material up against the center point of the Protective Cap. As long as the Protective Cap remains in place, the system is considered to be “Out of Service”. Step 4. After installing the ceiling and applying a ceiling finish, with the 2-1/2 inch (63,5 mm) diameter hole and in preparation for installing the Cover Plate Assembly, remove and discard the Protective Cap, and verify that the Deflector moves up and down freely. If the Sprinkler has been damaged and the Deflector does not move up and down freely, replace the entire Sprinkler assembly. Do not attempt to modify or repair a damaged sprinkler. Step 5. Screw on the Cover Plate/Retainer Assembly until the Retainer (Figure 2) contacts the ceiling. Do not continue to screw on the Cover Plate/Retainer Assembly such that it lifts a ceiling panel out of its normal position. If the Cover Plate/Retainer Assembly cannot be engaged with the Support Cup or the Cover Plate/Retainer Assembly cannot be engaged suffi-ciently to contact the ceiling, reposition the Sprinkler Fitting. Ambient Temperature Exposed to Discharge End of Sprinkler Temperatures for Heated Areaa 40°F (4°C)50°F (10°C)60°F (16°C) Minimum Exposed Barrel Length, Inches (mm)b 40°F (4°C)0 0 0 30°F (-1°C)0 0 0 20°F (-7°C)4 (100)0 0 10°F (-12°C)8 (200)1 (25)0 0°F (-18°C)12 (305)3 (75)0 -10°F (-23°C)14 (355)4 (100)1 (25) -20°F (-29°C)14 (355)6 (150)3 (75) -30°F (-34°C)16 (405)8 (200)4 (100) -40°F (-40°C)18 (455)8 (200)4 (100) -50°F (-46°C)20 (510)10 (255)6 (150) -60°F (-51°C)20 (510)10 (255)6 (150) NOTES: a. For protected area temperatures that occur between values listed above, use the next cooler temperature.b. These lengths are inclusive of wind velocities up to 30 mph (18,6 kph). TABLE A EXPOSED SPRINKLER BARRELS IN WET PIPE SYSTEMS MINIMUM RECOMMENDED LENGTHS TFP515 Page 5 of 8 Care and Maintenance TYCO Series DS-C Dry Type Concealed Pendent Sprinklers must be maintained and serviced in accordance with this section. Before closing a fire protection system main control valve for maintenance work on the fire protection system that it controls, obtain permission to shut down the affected fire protection systems from the proper authorities and notify all personnel who may be affected by this action. (SEE DESIGN CRITERIASECTION) FACE OF SPRINKLER FITTING LENGTHEXPOSURE DSB-2 INTENDED FOR FREEZERSTRUCTURES HEATEDAREA FIGURE 7 EXPOSURE LENGTH INSULATEDFREEZERSTRUCTURE STRAP TIES(ENDS ONOPPOSINGSIDES OFBOOT) ADHESIVE 2-1/2" DIA.(63,5 mm)CLEARANCEHOLE DSB-2 BOOT DS-C DRY PENDENT CONCEALED SPRINKLER FIGURE 8 MODEL DSB-2 DRY SPRINKLER BOOT WITH DRY-TYPE SPRINKLER SIDE OUTLET PLUGGED TO WET SYSTEM FITTING(SEE DESIGN CRITERIASECTION) SPRINKLERDSB-2 INTENDED FOR FREEZERSTRUCTURES HEATED AREA FIGURE 5 SPRINKLER FITTING HEATED AREA RUN OUTLET PLUGGED TO DRY SYSTEM DSB-2 INTENDED FOR FREEZER STRUCTURES FITTING(SEE DESIGN CRITERIASECTION) SPRINKLER AREASUBJECT TO FREEZING FIGURE 6 SPRINKLER FITTING UNHEATED AREA Absence of the Cover Plate Assembly may delay sprinkler operation in a fire situation. A Vent Hole is provided in the Bulb Seat (Figure 1) to indicate if the Dry Sprinkler is remaining dry. Evidence of leakage from the Vent Hole indicate potential leakage past the Inlet seal and the need to remove the sprinkler to determine the cause of leakage; for example, an improper installation or an ice plug. Close the fire protection system control valve and the system drain before removing the sprinkler. When properly installed, there is a nominal 3/16 inch (4,8 mm) air gap between the lip of the Cover Plate and the ceiling, as shown in Figure 2. This air gap is necessary for proper operation of the sprinkler. If the ceiling is to be repainted after the installation of the Sprinkler, care must be exercised to ensure that the new paint does NOT seal off any of the air gap. Do not pull the Cover Plate relative to the Enclosure. Separation may result. Sprinklers which are found to be leaking or exhibiting visible signs of corrosion must be replaced. Automatic sprinklers must never be painted, plated, coated, or otherwise altered after leaving the factory. Modified sprinklers must be replaced. Sprinklers that have been exposed to corrosive products of combustion, but have not operated, should be replaced if they cannot be completely cleaned by wiping the sprinkler with a cloth or by brushing it with a soft bristle brush. Care must be exercised to avoid damage to the sprinklers - before, during, and after installation. Sprinklers damaged by dropping, striking, wrench twist/slippage, or the like, must be replaced. Also, replace any sprinkler that has a cracked bulb or that has lost liquid from its bulb. (Ref. Installation Section.) If a sprinkler must be removed, do not reinstall it or a replacement without reinstalling the Cover Plate Assembly. If a Cover Plate Assembly becomes dislodged during service, replace it immediately. The owner is responsible for the inspection, testing, and maintenance of their fire protection system and devices in compliance with this document, as well as with the applicable standards of the National Fire Protection Association (for example, NFPA 25), in addition to the standards of any other Authorities Having Jurisdiction. The installing contractor or sprinkler manufacturer should be contacted relative to any questions. Automatic sprinkler systems are recom-mended to be inspected, tested, and maintained by a qualified Inspection Service in accordance with local requirements and/or national codes. TFP515Page 6 of 8 Ordering Procedure Contact your local distributor for avail-ability. When placing an order, indicate the full product name, including description and Part Number (P/N). Dry Type Sprinkler AssembliesWhen ordering 5.6 K-Factor Series DS-C Standard Coverage Dry Type Concealed Pendent Sprinklers, specify the following information: • SIN Quick Response TY3535 or Standard Response TY3555 • Temperature Rating • Order Length Dry Type Sprinklers are furnished based upon Order Length as measured from the face of the ceiling to the face of the sprinkler fitting (Figure 2). After the measurement is taken, round it to the nearest 1/4 inch increment. • Inlet Thread Connection 1 inch NPT or ISO 7-R1 • Part Number from Table B. Separately Ordered Cover PlateSpecify: Series RFII Concealed Cover Plate with (temperature), (finish), and P/N (below). 139°F (59°C) Cover Plate for use with 155°F (68°C) Sprinkler Grey White (RAL9002) ......P/N 56-792-0-135 Brass ................... P/N 56-792-1-135 Pure White* (RAL9010) ......P/N 56-792-3-135 Signal White (RAL9003) .....P/N 56-792-4-135 Jet Black (RAL9005) ........P/N 56-792-6-135 Chrome ..................P/N 56-792-9-135 Custom .................. P/N 56-792-X-135 165°F (74°C) Cover Plate for use with 200°F (93°C) Sprinkler Grey White (RAL9002) ......P/N 56-792-0-165Brass ................... P/N 56-792-1-165 Pure White* (RAL9010) ......P/N 56-792-3-165Signal White (RAL9003) .....P/N 56-792-4-165 Jet Black (RAL9005) ........P/N 56-792-6-165Chrome ..................P/N 56-792-9-165 Custom .................. P/N 56-792-X-165* Eastern Hemisphere Sales Only Sprinkler WrenchSpecify: RFII Sprinkler Wrench, P/N 56-000-1-075. Sprinkler BootSpecify: Model DSB-2 Dry Sprinkler Boot, P/N 63-000-0-002. This Part Number includes one Boot, two Strap Ties, and 1/3 oz. of Adhesive (a sufficient quantity for installing one boot). P/N* 60 – XXX – 1 – XXX Note * Use Prefix “I” for ISO 7-R1 Connection (for example, I-60-461-1-180). ** Dry-Type Sprinklers are furnished based upon “Order Length” as measured per Figure 2, for each individual sprin- kler where it is to be installed. After the measurement is taken, round it to the nearest 1/4 inch increment. SIN 46 Quick Response (3 mm Bulb)TY3535 86 Standard Response (5 mm Bulb)TY3555 ORDER LENGTH** 055 5.50” 082 8.25” 180 18.00” 187 18.75” 372 37.25” 480 48.00” TABLE B SERIES DS-C STANDARD COVERAGE, DRY-TYPE CONCEALED PENDENT SPRINKLERS WITH 1 INCH NPT CONNECTION PART NUMBER SELECTION TEMPERATURE RATING 1 155°F (68°C) 3 200°F (93°C) TFP515 Page 7 of 8