HomeMy WebLinkAboutF16-0067 FIREPLACE AREA.pdf MERIDIAN INTERMOUNTAIN FIRE & SECURITY P.O. BOX 3940 AVON, CO 81620 HYDRAULIC CALCULATIONS FOR CUMMINGS RESIDENCE 5147 GORE CIRCLE VAIL, CO DATE: 11/1/16 2 HSW FIREPLACE AREA -DESIGN DATA- OCCUPANCY CLASSIFICATION: NFPA 13D DENSITY: .05 gpm/sq ft, 19 gpm min AREA OF APPLICATION: 2 sprinklers COVERAGE PER SPRINKLER: 16' x 18' max NUMBER OF SPRINKLERS CALCULATED: 2 heads TOTAL SPRINKLER WATER FLOW REQUIRED: 38.0 gpm FLOW AND PRESSURE (@ SOURCE) : 38.0 gpm @ 42.0 psi SPRINKLER ORIFICE SIZE: K=4.4 CONTRACTOR CERTIFICATION NUMBER: CO LIC #16-S-04222 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 2 DATE: 9/1/2014\DOCS\LEWS CALCS\CUMMINGS RES VAIL\2 HSW FIREPLACE AREA.SDF JOB TITLE: Cummings residence; fireplace area 0 0 'b • • • • E a.) (1) i 0-1 a a • • (1) b is U U • O N • • o sa o • in • • G • N [� m a m co a ro (nm r E • N Z' Sa a) a) • °O w a, u e m 0 • C7 a • cn O a) • a s ro a • ro 5 • rn H L H co o >1 • RI • • • •H • r-- 1244 w •• m • • • LU N • CO O tb -H in to � O tl O = >-1 LC- g U • -H a +' w as a +' • LU LU H 0 0 O co O N r N !` O O O O O O O O O O O O O O O O rl LU r- O SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 3 DATE: 9/1/2014\DOCS\LEWS CALCS\CUMMINGS RES VAIL\2 HSW FIREPLACE AREA.SDF JOB TITLE: Cummings residence; fireplace area NFPA WATER SUPPLY DATA SOURCE STATIC RESID. FLOW AVAIL. TOTAL REQ'D NODE PRESS. PRESS. @ PRESS. @ DEMAND PRESS. TAG (PSI) (PSI) (GPM) (PSI) (GPM) (PSI) 1 75.0 35.0 822.0 74 . 9 38.0 52.0 AGGREGATE FLOW ANALYSIS: TOTAL FLOW AT SOURCE 38.0 GPM TOTAL HOSE STREAM ALLOWANCE AT SOURCE 0.0 GPM OTHER HOSE STREAM ALLOWANCES 0.0 GPM TOTAL DISCHARGE FROM ACTIVE SPRINKLERS 38.0 GPM NODE ANALYSIS DATA NODE TAG ELEVATION NODE TYPE PRESSURE DISCHARGE NOTES (FT) (PSI) (GPM) 8 31.1 K= 4.40 18. 6 19.0 7 31.1 K= 4.40 18. 6 19.0 5 31.1 - - - - 19.3 - - - 4 16.1 - - - - 29.7 - - - 3 10.0 - - - - 32. 9 - - - 2 10.0 - - - - 45. 9 - - - 1 0.0 SOURCE 52.0 38.0 SPRINKLER SYSTEM HYDRAULIC ANALYSIS Page 4 DATE: 9/1/2014\DOCS\LEWS CALCS\CUMMINGS RES VAIL\2 HSW FIREPLACE AREA.SDF JOB TITLE: Cummings residence; fireplace area NFPA PIPE DATA Pipe Tag K-fac Add Fl Add Fl To Fit: L C (Pt) Frm Node El (ft) PT (q) Node/ Nom ID Eq.Ln. F (Pe) Notes To Node El (ft) PT Tot. (Q) Disch Act ID (ft. ) T Pf/ft. (Pf) Pipe: 8 4 .40 19.0 Disch 7.3 5.08 150 0. 6 5 31.1 19.3 0.0 1.000 7.30 0.0 8 31.1 18. 6 19.0 1.142 12.38 0.052 0. 6 Pipe: 7 4 .40 19.0 Disch 7.3 5.08 150 0. 6 5 31.1 19.3 0.0 1.000 7.30 0.0 7 31.1 18. 6 19.0 1.142 12.38 0.052 0. 6 Pipe: 5 0.0 0.0 14.8 46.71 150 10.4 4 16.1 29.7 38.0 1.250 14.80 -6.5 5 31.1 19.3 38.0 1.425 61.51 0.063 3. 9 Pipe: 4 0.0 0.0 17.85 150 3.2 3 10.0 32. 9 38.0 5 2.000 2E:12.0 24.00 -2. 6 4 16.1 29.7 38.0 1. 959 T:12.0 41.85 0.013 0. 6 Pipe: 3 0.0 Fixed Pressure Loss Device 2 10.0 45. 9 38.0 4 13.0 psi, 38.0 gpm 3 10.0 32. 9 38.0 Pipe: 2 Source 0.0 3E:18.0 102.00 150 6.1 1 0.0 52.0 38.0 3 2.000 T:12.0 31.00 -4 .3 2 10.0 45. 9 38.0 1. 959 G: 1.0 133.00 0.013 1.8 NOTES (HASS) : (1) Calculations were performed by the HASS 8.4 computer program under license no. 5003013219 granted by HRS Systems, Inc. 208 Southside Square Petersburg, TN 37144 (931) 659-9760 (2) The system has been calculated to provide an average imbalance at each node of 0.011 gpm and a maximum imbalance at any node of 0.066 gpm. (3) Total pressure at each node is used in balancing the system. Maximum water velocity is 7. 6 ft/sec at pipe 5. (4) Items listed in bold print on the cover sheet are automatically transferred from the calculation report. (5) Available pressure at source node 1 under full flow conditions is 74 .75 psi compared to the minimum required pressure of 0.00 psi.