Fire Protection Hydraulic and
Equipment Submittal
Red Lion #3
304 Bridge St
Vail Village, CO 81657
WSFP #CS2947
Prepared by:
Joshua Adam
Project Manager
Western States Fire Protection Co.
7026 South Tucson Way
Centennial. CO 80112
(720) 895-5216
Email: josh.adam@wsfp.us
Model RFC Series Residential Sprinklers
Flat Cover Plate, Concealed Pendent Sprinkler cULus Listed
Bulletin 006 Rev. K February 2017
Product Features
• cULus Listed as Residential Sprinklers
• Push-On cover plate installation
• Low water flow requirements
Product Description
Model RFC Series residential sprinklers are flat cover plate,
concealed pendent sprinklers intended for installation in
accordance with NFPA 13, NFPA 13R, or NFPA 13D. The
sprinklers are cULus Listed as Residential Sprinklers in ac-
cordance with UL 1626.
Model RFC30, RFC43, and RFC49 sprinklers have a 165°F
(74°C) temperature rated fusible-link operating element.
Model RFC58 sprinklers are offered with either a 165°F
(74°C) or 212°F (100°C) temperature rated fusible-link op-
erating element. Sprinklers with a 165°F (74°C) temperature
rating are ordinary temperature classification and should
be used with a 135°F (57°C) temperature rated cover plate.
Sprinklers with a 212°F (100°C) temperature rating are inter-
mediate temperature classification and should be used with
a 165°F (74°C) temperature rated cover plate.
Model RFC Series sprinklers are installed with a Model RFC
cover plate. Model RFC cover plates may be installed by
either pushing or threading the cover plate into the sprinkler
cup. Model RFC30, RFC43, and RFC49 sprinklers allow 1/2”
(13 mm) of cover plate adjustment. Model RFC58 sprinklers
allow 3/4” (19 mm) of cover plate adjustment.
Model RFC cover plates are available in a variety of finishes
as listed in Table H. In addition, Model RFC cover plates
may be ordered as either traditional solid cover plates or
perforated cover plates.
Sprinkler Model Nominal K-Factor
gpm/psi1/2 (l/min/bar1/2)
Max. Coverage Area
ft x ft (m x m)
Sprinkler
Identification
Number (SIN)
RFC30 3.0 (43.2)14 x 14 (4.3 x 4.3)RA0611
RFC43 4.3 (62)20 x 20 (6.1 x 6.1)RA0612
RFC49 4.9 (70.6)20 x 20 (6.1 x 6.1)RA0616
RFC58 5.8 (84)20 x 20 (6.1 x 6.1)RA0613
Table A
www.reliablesprinkler.com
Model RFC43Model RFC30
Model RFC49 Model RFC58
Model RFC Cover Plate
Solid Perforated
Bulletin 006 Rev. K
February 2017
Page 2 of 7
www.reliablesprinkler.com
Model RFC30 Residential Sprinkler SIN RA0611
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2” NPT or ISO 7-1 R1/2 Nominal K-Factor: 3.0 (43.2 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast-response
Temperature Rating
165°F (74°C) sprinkler
135°F (57°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC
Listings and Approvals
cULus Listed
Model RFC30 Sprinkler Components and Dimensions Figure 1
Model RFC30 Sprinkler Hydraulic Design Criteria Table B
Minimum Flow and Residual Pressure
Max. Coverage Area
ft. x ft.
(m x m)
Flow
gpm
(l/min)
Pressure
psi
(bar)
12 x 12
(3.6 x 3.6)
9
(34)
9.0
(0.62)
14 x 14
(4.3 x 4.3)
10
(38)
11.0
(0.76)
Notes: 1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table B above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bottom View
Bulletin 006 Rev. K
February 2017
Page 3 of 7
www.reliablesprinkler.com
Model RFC43 Residential Sprinkler SIN RA0612
Technical Specifications
Style: Flat Concealed Pendent
Threads: 1/2” NPT or ISO 7-1 R1/2 Nominal K-Factor: 4.3 (62 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity
Fast-response
Temperature Rating
165°F (74°C) sprinkler
135°F (57°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC
Listings and Approvals
cULus Listed
Model RFC43 Sprinkler Components and Dimensions Figure 2
Model RFC43 Sprinkler Hydraulic Design Criteria Table C
Minimum Flow and Residual Pressure
Max. Coverage Area
ft. x ft.
(m x m)
Flow
gpm
(l/min)
Pressure
psi
(bar)
12 x 12
(3.6 x 3.6)
12
(45)
7.8
(0.54)
14 x 14
(4.3 x 4.3)
13
(49)
9.1
(0.63)
16 x 16
(4.9 x 4.9)
13
(49)
9.1
(0.63)
18 x 18
(5.5 x 5.5)
18
(68)
17.5
(1.21)
20 x 20
(6.1 x 6.1)
21
(79)
23.8
(1.64)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table C above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bottom View
Model RFC49 Residential Sprinkler SIN RA0616
Technical Specifications
Style: Flat Concealed Pendent Threads: 1/2” NPT or ISO 7-1 R1/2
Nominal K-Factor: 4.9 (70.6 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy
Yoke: Brass Alloy Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity Fast-response
Temperature Rating
165°F (74°C) sprinkler
135°F (57°C) cover plate
Cover Plate
Model RFC cover plate
Sprinkler Wrench
Model FC
Listings and Approvals
cULus Listed
Model RFC49 Sprinkler Components and Dimensions Figure 3
Model RFC49 Sprinkler Hydraulic Design Criteria Table D
Minimum Flow and Residual Pressure
Max. Coverage Area
ft. x ft.
(m x m)
Flow
gpm
(l/min)
Pressure
psi
(bar)
16 x 16
(4.9 x 4.9)
13
(49.0)
7.0
(0.48)
18 x 18
(5.5 x 5.5)
17
(64.3)
12.0
(0.83)
20 x 20
(6.1 x 6.1)
20
(75.7)
16.7
(1.15)
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table D above and (2) the flow required to achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bulletin 006 Rev. K
February 2017
Page 4 of 7
www.reliablesprinkler.com
Bottom View
Model RFC58 Residential Sprinkler SIN RA0613
Technical Specifications Style: Flat Concealed Pendent
Threads: 1/2” NPT or ISO 7-1 R1/2
Nominal K-Factor: 5.8 (84 metric)
Max. Working Pressure: 175 psi (12 bar)
Min. Spacing: 8 ft. (2.4 m)
Material Specifications
Thermal Sensor: Nickel Alloy Solder Link
Sprinkler Body: Brass Alloy
Levers: Bronze Alloy Yoke: Brass Alloy
Sealing Assembly: Nickel Alloy with PTFE
Load Screw: Bronze Alloy
Towers: Copper Alloy
Pins: Stainless Steel
Deflector: Chrome Plated Bronze Alloy
Cup: Steel
Cover Plate Finishes
(See Table H)
Sensitivity Fast-response
Temperature Ratings
Ordinary:
165°F (74°C) sprinkler
135°F (57°C) cover plate
Intermediate:
212°F (100°C) sprinkler
165°F (74°C) cover plate
Cover Plate
Model RFC Cover Plate
Sprinkler Wrench
Model FC
Listings and Approvals
cULus Listed
Model RFC58 Sprinkler Components and Dimensions Figure 4
Model RFC58 Sprinkler Hydraulic Design Criteria Table E
Minimum Flow and Residual Pressure
Max. Coverage Area(2)
ft. x ft.
(m x m)
Flow
gpm
(l/min)
Pressure
psi
(bar)
16 x 16
(4.9 x 4.9)
16
(60.6)
7.6
(0.53)
18 x 18
(5.5 x 5.5)
18
(68.1)
9.6
(0.66)
20 x 20
(6.1 x 6.1)
20
(75.7)
11.9
(0.82)
Bulletin 006 Rev. K
February 2017
Page 5 of 7
www.reliablesprinkler.com
Notes:
1. For NFPA 13 installations the flow per sprinkler must be the greater of: (1) the flow listed in Table E above and (2) the flow required to
achieve a minimum design density of 0.1 gpm/sq ft over the design area of the sprinkler.
2. For coverage area dimensions less than those listed above, use the minimum required flow for the next larger max. coverage area listed.
Bottom View
Standard Finishes Special Application Finishes
White Polyester Off White Paint Black Paint Raw Brass
Chrome Plated Bright Brass Finished Bronze Black Plated
Satin Chrome Stainless Steel
Clad(3)
Custom Color
Paint(2)
Notes:
1. Paint or any other coating applied over the factory finish will void all approvals and warranties.
2. Custom color paint is semi-gloss, unless specified otherwise. 3. Stainless steel clad cover plates are Type 316 Stainless Steel on the finished side and C102 Copper Allow on the back side. Cover plates
are not listed or approved as corrosion resistant. Stainless steel clad cover plates are not available perforated.
Cover Plate Finishes(1) Table H
Bulletin 006 Rev. KFebruary 2017 Page 6 of 7www.reliablesprinkler.com
Sprinkler
Model
Cover
Plate
Model
Cover Plate
Diameter
inch
(mm)
Recommended
Hole Diameter
in Ceiling
inch
(mm)
Cover Plate
Adjustment
inch
(mm)
Min. to
Max. Face
of Fitting to
Ceiling(1)
inch
(mm)
Min. to Max.
Dropped Deflector
Distance below
Ceiling
inch
(mm)
Cover Plate
Temperature
Rating
RFC30
RFC43
RFC49
RFC 3-5/16(84)2-5/8(67)1/2(13)1-1/2 to 2(38 to 51)1/2 to 1(13 to 25)135°F(57°C)
RFC58 RFC 3-5/16
(84)
2-5/8
(67)
3/4
(19)
1-1/2 to 2-1/4
(38 to 57)
1/4 to 1
(6 to 25)
135°F(2)
(57°C)or 165°F(3)
(74°C)
Notes:
1. Face of fitting to ceiling dimensions are based on a nominal thread make up. Verify dimensions based on fitting and thread sealing method prior
to installation. A 1/2” x 1/2” brass nipple extension (Reliable P/N 6999991900) is available where necessary for replacement of existing sprinklers.
2. For use with 165°F (74°C) temperature rated sprinklers where the Maximum Ceiling Temperature does not exceed 100°F (38°C). 3. For use with 212°F (100°C) temperature rated sprinklers with the Maximum Ceiling Temperature does not exceed 150°F (66°C).
Table JInstallation Dimensions
Installation
Model RFC series sprinklers are intended to be installed in ac-
cordance with NFPA 13, NFPA 13R, or NFPA 13D, as well as the
requirements of applicable authorities having jurisdiction. Mod-
el RFC series sprinklers must not be installed in ceilings with
positive pressure in the space above. Ensure that the 4 slots in
the cup are open and unobstructed following installation. Model
RFC series sprinklers are shipped with a protective cap that
should remain on the sprinkler until installed. The protective cap
should be replaced following installation of the sprinkler and
permanently removed only when the cover plate is installed and
the sprinkler system is placed in service following construction.
Model RFC series sprinklers are installed with the Model FC
wrench. The use of any other wrench to installed Model RFC se-
ries sprinklers is not permitted and may damage the sprinkler.
Temporarily remove the protective cap during installation of the
sprinkler. Insert the Model FC wrench over the sprinkler until the
wrench engages the body. Do not wrench any other part of the
sprinkler/cup assembly. The Model FC wrench is designed to
be turned with a standard 1/2” square drive. Tighten the sprin-
kler into the fitting after applying a PTFE based thread sealant
to the sprinkler’s threads. Recommended installation torque is 8
to 18 ft/lb (11 to 24 N/m).
Do not exceed the maximum recommended torque. Exceeding
the maximum recommended torque may cause leakage or im-
pairment of the sprinkler. Use care when inserting or removing
the wrench from the sprinkler to avoid damage to the sprinkler.
Install the cover plate by hand by pushing the cover plate into
the cup and turning the cover in the clockwise direction until it
is tight against the ceiling.
Application
Model RFC series sprinklers are intended for installation where
residential sprinklers are permitted or required by NFPA 13,
NFPA 13R, and NFPA 13D. The sprinklers are concealed pen-
dent residential sprinklers.
Model RFC 30, RFC43, and RFC49 sprinklers are available in
ordinary temperature classification for installation where the
Maximum Ceiling Temperature does not exceed 100°F (38°C).
Model RFC58 sprinklers are available in either ordinary or in-
termediate temperature classification for installation where the
Maximum Ceiling Temperature does not exceed 100°F (38°C)
or 150°F (66°C), respectively.
Guarantee
For the Reliable Automatic Sprinkler Co., Inc. guarantee, terms,
and conditions, visit www.reliablesprinkler.com.
Patents
Model RFC30, RFC43, RFC49, and RFC58 sprinklers are
covered by U.S. Patent No. 9,248,327 and U.S. Patent No.
7,275,603.
Model RFC30 and RFC43 sprinklers are additionally covered
by U.S. Patent No. 8,776,903.
Ordering Information
Specify the following when ordering.
Sprinkler
• Model (RFC30, RFC43, RFC49, RFC58)
• Temperature Rating
Cover Plate
• Model RFC
• Temperature Rating
• Finish (See Table H)
Sprinkler Wrench
• Model FC
Maintenance
Model RFC series sprinklers should be inspected and the
sprinkler system maintained in accordance with NFPA 25. Do
not clean sprinklers with soap and water, ammonia or any other
cleaning fluids. Remove dust by gentle vacuuming. Replace
any sprinkler cover plate assembly which has been painted
(other than factory applied) or damaged in any way. A stock of
spare sprinklers should be maintained to allow quick replace-
ment of damaged or operated sprinklers. Prior to installation,
sprinklers should be maintained in the original cartons and
packaging until used to minimize the potential for damage to
sprinklers that would cause improper operation or non-oper-
ation.
Bulletin 006 Rev. K
February 2017
Page 7 of 7
www.reliablesprinkler.com
Model FC
Listings and Approvals
Listed by Underwriters Laboratories, Inc. and UL Certified for
Canada (cULus)
UL Listing Category
Residential Automatic Sprinkler
UL Guide Number
VKKW
Wrench P/N 9999970261