HomeMy WebLinkAboutB17-0092_E-002-1_1498849080.pdf2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP, P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
CENTRAL
WING
RENOVATION
3/10/2017
6:49:44 AM
15924.00
E-002.1
ELECTRICAL SCHEDULES
2017
03/10/17
PERMIT
VAIL
VALLEY
MEDICAL
CENTER
180 S. Frontage
Road
West,
Vail, CO 81657
Type Description Lamp
Apparent
Load
Ballast
Voltage Manufacturer Catalog Series Finish Mounting Depth Note
D1 6" DIAMETER LED DOWNLIGHT, CLEAR ALZAK
SEMI-DIFFUSED REFLECTOR
LED
3500K
1800 LUMENS
0-10V - 10% DIMMING
90+ CRI
26 VA 277 V LITEFRAME LC6LED SERIES CLEAR
ALZAK
RECESSED 0' - 4 3/4"
D2 6" DIAMETER LED DOWNLIGHT, CLEAR ALZAK
SEMI-DIFFUSED REFLECTOR
LED
3500K
1800 LUMENS
0-10V - 1% DIMMING
90+ CRI
26 VA 277 V LITEFRAME LC6LED SERIES CLEAR
ALZAK
RECESSED 0' - 4 3/4"
D3 6" DIAMETER LED WALLWASH DOWNLIGHT, CLEAR
ALZAK SEMI-DIFFUSED REFLECTOR
LED
3500K
1400 LUMENS
90+ CRI
22 VA 277 V LITEFRAME LC6LED SERIES CLEAR
ALZAK
RECESSED 0' - 4 3/4"
P1 4' LINEAR HOLLOW RECTANGULAR LED
DECORATIVE PENDANT
LED
3500K
3000 LUMENS
0-10V 10% DIMMING
40 VA 277 V FOCAL POINT FNRS SERIES PALLADIUM
SILVER
PENDANT 0' - 1 19/32"
S1 4' LED LENSED STRIPLIGHT, MEDIUM LUMEN
OUTPUT
LED
3500K
5000 LUMENS
80+ CRI
48 VA 277 V COLUMBIA LCL SERIES WHITE SURFACE
T1 2' x 4' RECESSED LED FLAT EDGE LIT PANEL
TROFFER, EXTRUDED ALUMINUM PAINTED WHITE,
WHITE TRANSLUCENT LENS
LED
3500K
5870 LUMENS
80+ CRI
50 VA 277 V MAXLITE MLFP SERIES WHITE RECESSED 0' - 2 3/16"
T2 2' x 2' RECESSED LED FLAT EDGE LIT PANEL
TROFFER, EXTRUDED ALUMINUM PAINTED WHITE,
WHITE TRANSLUCENT LENS
LED
3500K
4120 LUMENS
80+ CRI
40 VA 277 V MAXLITE MLFP SERIES WHITE RECESSED 0' - 2 3/16"
T3 2' x 4' RECESSED LED VOLUMETRIC TROFFER,
SATINE CURVED CENTER LENS
LED
3500K
3843 LUMENS
0-10V 10% DIMMING
82+ CRI
47 VA 277 V PINNACLE ADEO SERIES WHITE RECESSED 0' - 3"
T4 2' x 2' RECESSED LED VOLUMETRIC TROFFER,
SATINE CURVED CENTER LENS
LED
3500K
3647 LUMENS
0-10V 10% DIMMING
82+ CRI
36 VA 277 V PINNACLE ADEO SERIES WHITE RECESSED 0' - 3"
UC1 4' LED UNDERCABINET LIGHT WITH INTEGRAL
ROCKER SWITCH
LED
3500K
2400 LUMENS
82 CRI
29 VA 277 V H.E. WILLIAMS 1SF SERIES WHITE SURFACE
W1 2' DECORATIVE LED RECTANGULAR SHAPED
VANITY LIGHT WITH WHITE ACRYLIC LENS AND
ANTIQUE BRONZE ACCENT BODY AND END CAPS
LED
3000K
1200 LUMENS
20 VA 277 V LBL LIGHTING BA823 SERIES ANTIQUE
BRONZE
WALL
W2 4' LED DIRECT / INDIRECT LINEAR WALL MOUNT
WITH FLUSH LENS, 275 LUMENS PER FOOT UP,
625 LUMENS PER FOOT DOWN
LED
3500K
3600 LUMENS
0-10V 10% DIMMING
40 VA 277 V FOCAL POINT FSM4BW WHITE WALL
X1 UNIVERSAL LED EDGE-LIT EXIT SIGN, SINGLE
FACE, GREEN LETTERS, WHITE PANEL
LED 3 VA 277 V EXITRONIX 900 SERIES WHITE CEILING
GENERAL NOTES:
A. Catalog number refers to first name listed under manufacturer per luminaire type. Remaining manufacturers listed are considered to be equivalent products for this project and shall meet all criteria listed including that called for by the specific
luminaire catalog number. Catalog numbers do not necessarily represent complete catalog numbers. All items listed in the description shall be provided.
B. Refer to lighting specifications for additional requirements.
C. Provide unit pricing for all luminaires by type and submit with bid form.
L U M I N A I R E S C H E D U L E
Key # Item HP FLA Load Eq Load (VA) Voltage
Feeders Protection
Notes
Wire Ground Conduit Breaker Disconnect Fuse
EF 16 EXHAUST FAN 1.5 0 A 0 VA 2390 VA 208V 3ph 2#12 #12G 3/4" 20 A 30 A 2P 20 A
EF 17 EXHAUST FAN 1.5 0 A 0 VA 2390 VA 208V 3ph 2#12 #12G 3/4" 20 A 30 A 2P 20 A
M E C H A N I C A L E Q U I P M E N T S C H E D U L E
GENERAL NOTES:
A. Prior to work, verify electrical requirements (voltage, amperage, recommended OCPD, conductors, and disconnect) for each piece of equipment.
B. Prior to work, verify exact location for each piece of equipment.
C. Coordinate and provide all field connections as required.
D. Coordinate 120V power connections to dampers and other control circuits. Group equipment control circuits such that failure of one control circuit does not affect operation of other equipment. For
example, do not connect a damper associated with one air handling unit to the same branch circuit as dampers associated with a different air handling unit.
E. Feeders, breakers, disconnects, and fusing applies to field-installed and/or factory-installed equipment.
F. Coordinate location of VFD(s) and working space clearances. If installed remote from equipment, provide circuit connection from VFD to motor(s).
SPECIFIC NOTES:
1. Connect equipment to emergency power.
Key Item HP FLA Load Eq Load (VA) Voltage
Feeders Protection
Notes
Wire Ground Conduit Breaker Disconnect Fuse
ADO AUTO DOOR OPERATOR 0 0 A 200 VA 200 VA 120V 1ph 2#12 #12G 3/4” 20 A
CBR01 COFFEE MAKER 0 0 A 1400 VA 1400 VA 120V 1ph 2#12 #12G 3/4” 20 A NEMA
5-20R
CBS01 PHARMACY HOOD 0 4 A 0 VA 516 VA 120V 1ph 2#12 #12G 3/4” 20 A
CLF01 PHARMACY HOOD 0 4 A 0 VA 516 VA 120V 1ph 2#12 #12G 3/4” 20 A
COPY COPIER 0 0 A 1000 VA 1000 VA 120V 1ph 2#12 #12G 3/4” 20 A
DIS01 DISINFECTOR 0 5 A 0 VA 600 VA 120V 1ph 2#12 #12G 3/4” 20 A
FAX FAX MACHINE 0 0 A 1000 VA 1000 VA 120V 1ph 2#12 #12G 3/4” 20 A
FZU01 UNDERCOUNTER FREEZER 0 8 A 0 VA 960 VA 120V 1ph 2#12 #12G 3/4” 20 A NEMA
5-20R
HDRY HAND DRYER 0 0 A 200 VA 200 VA 120V 1ph 2#12 #12G 3/4” 20 A
ICG01 NUC MED CAMERA 0 0 A 4992 VA 4992 VA 208V 1ph 2#10 #10G 3/4” 30 A NEMA
L6-30R
IUS02 ULTRASOUND 0 0 A 1200 VA 1200 VA 120V 1ph 2#12 #12G 3/4” 20 A NEMA
5-20R
MNTR MONITOR 0 0 A 200 VA 200 VA 120V 1ph 2#12 #12G 3/4” 20 A NEMA
5-20R
MTR01 CARDIAC MONITOR 0 0 A 180 VA 180 VA 120V 1ph 2#12 #12G 3/4” 20 A NEMA
5-20R
OVN01 NUC MED MICROWAVE 0 14 A 0 VA 1680 VA 120V 1ph 2#12 #12G 3/4” 20 A NEMA
5-20R
OVN03 PHARMACY MICROWAVE 0 0 A 1200 VA 1200 VA 120V 1ph 2#12 #12G 3/4” 20 A NEMA
5-20R
PRNT PRINTER 0 0 A 120V 1ph 2#12 #12G 3/4” 20 A
REF02 PHARMACY REFRIGERATOR 0 8 A 0 VA 900 VA 120V 1ph 2#12 #12G 3/4” 20 A NEMA
5-20R
REF03 PHARMACY REFRIGERATOR 0 8 A 0 VA 900 VA 120V 1ph 2#12 #12G 3/4” 20 A NEMA
5-20R
REF05 COMPACT REFRIGERATOR 0 0 A 500 VA 500 VA 120V 1ph 2#12 #12G 3/4” 20 A NEMA
5-20R
RFU05 UNDERCOUNTER
REFRIGERATOR
0 5 A 0 VA 600 VA 120V 1ph 2#12 #12G 3/4” 20 A NEMA
5-20R
RFU06 UNDERCOUNTER
REFRIGERATOR
0 5 A 0 VA 600 VA 120V 1ph 2#12 #12G 3/4” 20 A NEMA
5-20R
SAF01 PYXIS 0 2 A 0 VA 205 VA 120V 1ph 2#12 #12G 3/4” 20 A NEMA
5-20R
WRM02 GEL WARMER 0 1 A 0 VA 156 VA 120V 1ph 2#12 #12G 3/4” 20 A NEMA
5-20R
O W N E R E Q U I P M E N T S C H E D U L E
GENERAL NOTES:
A. Prior to work, verify electrical requirements (voltage, amperage, recommended OCPD, conductors, and disconnect) for each piece of equipment.
B. Prior to work, verify exact location for each piece of equipment with Architect and/or owner.
SPECIFIC NOTES:
1. Verify exact mounting height with architect and provide appropriate suspension length.
2. Verify finish with architect.
3. Provide all mounting hardware, lamp heads, accessories, etc. for a complete and operational track lighting system.
4. Provide all mounting hardware, connectors, drivers, accessories, etc. for a complete and operational cove lighting system.
5. Refer to pole base detail for more information.
6. Refer to architectural drawings for mounting details.
SPECIFIC NOTES:
1. Connect equipment to emergency power.
2. Connect equipment to generator stand-by power.
3. Equipment furnished with integral disconnect switch.
06/30/17