HomeMy WebLinkAboutB17-0092_E-301-1_1498849080.pdf2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP, P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
CENTRAL
WING
RENOVATION
3/10/2017
6:58:10 AM
15924.00
E-301.1
ELECTRICAL PANEL
SCHEDULES
2017
03/10/17
PERMIT
VAIL
VALLEY
MEDICAL
CENTER
180 S. Frontage
Road
West,
Vail, CO 81657
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 119 A
K Kitchen 4320 VA 90.00% 3888 VA Total Demand Load: 42929 VA
G General 8316 VA 100.00% 8316 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 169 A
M Motor 624 VA 125.00% 780 VA Total Connected Load: 60840 VA
R Receptacle 46040 VA 60.86% 28020 VA
L Lighting 1540 VA 125.00% 1925 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 41 % A-B 34 % B-C 5 % C-A
Total Amps: 195 A 139 A 186 A
Total Load: 22620 VA 16636 VA 21584 VA
83 Spare -- 20 A 1 0 VA 2160 VA 84
1 81 DOOR CONTROL G 20 A 1 0 VA 1620 VA 82
1 79 FA EXTENDER G 20 A 1 200 VA 5140 VA
3 100 A R; G NEW PANEL 'NL1D'
80
2
1 77 CAMERA POWER R 20 A 1 180 VA 180 VA 1 20 A R L-111,112,113 78 1
1 75 RAY DAMPERS G 20 A 1 200 VA 360 VA 1 20 A R R-SERVER RM 113 76 1
73 Spare -- 20 A 1 0 VA 1080 VA 1 20 A R R-SERV RM 111,112,113 74 1
71 Spare -- 20 A 1 0 VA 540 VA 1 20 A R R-CARDIO ECHO DEFIB 72 1
69 Spare -- 20 A 1 0 VA 500 VA 1 20 A R R-CARDIO STRESS... 70 1
67 360 VA 1 20 A R R-CARDIO STRESS PRT 68 1
2 65 R-OFFICE R 20 A 1 1260 VA 360 VA 1 20 A R R-PT TREADMILL 66 1
1 63 R-BREAK ROOM DISP K 20 A 1 1620 VA 300 VA 1 20 A G R-CARDIO TECH WORK 64 1
61 Spare -- 20 A 1 0 VA 180 VA 1 20 A R R-CARDIO TREADMILL 62 1
1 59 PRE-ACTION COMP. M 20 A 1 624 VA 1200 VA 1 20 A G R-ULTRASOUND 60 2
2 57 R-OFFICE R 20 A 1 900 VA 720 VA 1 20 A R R-CARDIO READING 58 1
1 55 R-MRI CONTROL ROOM R 20 A 1 900 VA 900 VA 1 20 A R R-CARDIO ECHO READ 56 1
2 53 R-OFFICE COPIER G 20 A 1 1000 VA 540 VA 1 20 A R R-CARDIO ECHO 54 1
2 51 R-OFFICE R 20 A 1 1080 VA 720 VA 1 20 A R R-CARDIO CLEAN CHG 52 1
2 49 R-OFFICE R 20 A 1 1260 VA 720 VA 1 20 A R R-CARDIO CLEAN CHG 50 1
2 47 R-OFFICE R 20 A 1 540 VA 1080 VA 1 20 A R R-CARDIO TECH WORK 48 1
1 45 R-BREAK ROOM R 20 A 1 540 VA 540 VA 1 20 A R R-CARDIO CORRIDOR 46 1
1 43 R-BRK MICROWAVE K 20 A 1 1500 VA 360 VA 1 20 A R R-CARDIO ABG ROOM 44 1
1 41 R-BRK REF K 20 A 1 1200 VA 720 VA 1 20 A R R-CARDIO RECEPTION 42 1
1 39 MAG DOOR HOLDERS G 20 A 1 0 VA 360 VA 1 20 A R R-CORR/STAFF RECESS 40 2
1 37 R-SHF WORK ROOM R 20 A 1 540 VA 600 VA 1 20 A G R-ULTRASND DISINFECT 38 2
1 35 R-SHF OFFICE NORTH R 20 A 1 360 VA 540 VA 1 20 A R R-CARDIO OFFICE 36 1
2 33 R-CONF ROOM - A/V R 20 A 1 360 VA 876 VA 1 20 A R; G R-ULTRASOUND 34 2
2 31 R-COPIER G 20 A 1 1000 VA 180 VA 1 20 A R R-CARDIO CONTROL RR 32 1
2 29 R-OFFICE/COPY R 20 A 1 540 VA 360 VA 1 20 A R CARDIO CNTL CHG 30 1
1 27 R-PRE-OP CHECK IN R 20 A 1 720 VA 360 VA 1 20 A R CARDIO CNTL CHG 28 1
1 25 R-PRE-OP CHECK IN R 20 A 1 720 VA 180 VA 1 20 A R R-CARDIO STRESS TRD 26 1
1 23 R-MRI MECH ROOM R 20 A 1 1080 VA 540 VA 1 20 A R R-CARDIO STRESS RM 24 1
1 21 R-SHF CORRDIOR R 20 A 1 900 VA 720 VA 1 20 A R R-CARDIO SLEEP RMS 22 1
2 19 R-CONFERENCE ROOM R; G 20 A 1 560 VA 1440 VA 1 20 A R R-CARDIO CONTROL 20 1
1 17 R-SHF OFFICES R 20 A 1 1260 VA 900 VA 1 20 A R R-OFFICE 18 2
15 0 VA 900 VA 1 20 A R R-OFFICE 16 2
1 13
PANEL 'MRI' R; G 50 A 2
1360 VA 920 VA 1 20 A R; G R-SHF BIOMECH OFFICE 14 1
1 11 L-MRI L 20 A 1 1540 VA 900 VA 1 20 A R R-OFFICE 12 2
1 9 R-SHF OFFICES R 20 A 1 1080 VA 180 VA 1 20 A R R-SHF BIOMECH COPIER 10 1
1 7 R-SHF OFFICES R 20 A 1 720 VA 720 VA 1 20 A R R-SHF OFFICES 8 1
1 5 R-SHF OFFICE, VISITOR R 20 A 1 1440 VA 540 VA 1 20 A R R-SHF OFFICES 6 1
1 3 R-SHF OFFICE, RR R 20 A 1 540 VA 540 VA 1 20 A R R-SHF OFFICES 4 1
1 1 R-SHF RECEPTION R 20 A 1 540 VA 540 VA 1 20 A R R-OFFICE 2 2
Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note
1. EXISTING LOAD
2. NEW LOAD
Circuit Notes:
Enclosure: Type 1 MCB Rating: 200 A
Mounting: Surface Wire: 4 Bus Rating: 200 A
Supply From: Phase: 3 Mains Type: MLO
Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000
Panel L1E
EXISTING
General Notes:
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 25 A
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 8920 VA
G General 2260 VA 100.00% 2260 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 25 A
M Motor 0 VA 0.00% 0 VA Total Connected Load: 8920 VA
R Receptacle 6660 VA 100.00% 6660 VA
L Lighting 0 VA 0.00% 0 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 222 % A-B 38 % B-C 133 % C-A
Total Amps: 44 A 14 A 19 A
Total Load: 5140 VA 1620 VA 2160 VA
41 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 42
39 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 40
37 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 38
35 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 36
33 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 34
31 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 32
29 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 30
27 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 28
25 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 26
23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24
21 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 22
19 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 20
17 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 18
15 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 16
13 Spare -- 20 A 1 0 VA 200 VA 1 20 A G R-NUC. MED - PRINTER 14
11 Spare -- 20 A 1 0 VA 540 VA 1 20 A R R-NUC. MED - CONTROL 12
9 Spare -- 20 A 1 0 VA 180 VA 1 20 A G R-NUC. MED - COMP. 10
7 R-OFFICE R; G 20 A 1 1280 VA 1680 VA 1 20 A G R-NUC. MED - MICRO 8
5 R-OFFICE R 20 A 1 720 VA 900 VA 1 20 A R R-NUC. MED - HOT LAB 6
3 R-OFFICE R 20 A 1 720 VA 720 VA 1 20 A R R-NUC. MED 4
1 R-OFFICE R 20 A 1 1080 VA 900 VA 1 20 A R R-NUC. MED 2
Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note
Circuit Notes:
Enclosure: Type 1
Mounting: Surface Wire: 4 Bus Rating: 100 A
Supply From: L1E Phase: 3 Mains Type: MLO
Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000
Panel NL1D
General Notes:
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 116 A
K Kitchen 3000 VA 100.00% 3000 VA Total Demand Load: 96227 VA
G General 35277 VA 100.00% 35277 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 141 A
M Motor 0 VA 0.00% 0 VA Total Connected Load: 117429 VA
R Receptacle 61320 VA 58.15% 35660 VA
L Lighting 17832 VA 125.00% 22290 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 18 % A-B 12 % B-C 5 % C-A
Total Amps: 132 A 155 A 139 A
Total Load: 36512 VA 42774 VA 38143 VA
-- 41 Space -- -- -- 0 VA 33665... 42
-- 39 Space -- -- -- 0 VA 36751... 40
-- 37 Space -- -- -- 0 VA 29373...
3 20 A R; K; G; L
PANEL 'NL1A'
VIA XFMR
38
1
-- 35 Space -- -- -- 0 VA 0 VA -- -- -- Space 36 --
-- 33 Space -- -- -- 0 VA 0 VA -- -- -- Space 34 --
-- 31 Space -- -- -- 0 VA 0 VA -- -- -- Space 32 --
-- 29 Space -- -- -- 0 VA 0 VA -- -- -- Space 30 --
-- 27 Space -- -- -- 0 VA 0 VA -- -- -- Space 28 --
-- 25 Space -- -- -- 0 VA 0 VA -- -- -- Space 26 --
-- 23 Space -- -- -- 0 VA 0 VA -- -- -- Space 24 --
-- 21 Space -- -- -- 0 VA 0 VA -- -- -- Space 22 --
-- 19 Space -- -- -- 0 VA 0 VA -- -- -- Space 20 --
-- 17 Space -- -- -- 0 VA 0 VA -- -- -- Space 18 --
-- 15 Space -- -- -- 0 VA 0 VA -- -- -- Space 16 --
-- 13 Space -- -- -- 0 VA 0 VA -- -- -- Space 14 --
-- 11 Space -- -- -- 0 VA 439 VA 1 20 A L L-PHARMACY 12 2
1 9 L-ENTRY/CORRIDORS L 20 A 1 1523 VA 294 VA 1 20 A L L-NUC MED 10 2
1 7 L-STOR/REST/ELEC L 20 A 1 333 VA 2522 VA 1 20 A L L-ADMIN 8 2
1 5 L-LABS L 20 A 1 1589 VA 2450 VA 1 20 A L L-EXAM/MRI 6 1
1 3 L-OFFICES/CONF/BRK L 20 A 1 1756 VA 2450 VA 1 20 A L L-LOBBY/CORR 4 1
1 1 L-PT ENT/GYM/TRTMNT L 20 A 1 1834 VA 2450 VA 1 20 A L L-GYM/CARDIO 2 1
Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note
1. EXISTING LOAD
2. NEW LOAD
Circuit Notes:
Enclosure: Type 1
Mounting: Surface Wire: 4 Bus Rating: 125 A
Supply From: Phase: 3 Mains Type: MLO
Location: Voltage: 480/277 Wye A.I.C. Rating: 18,000
Panel NH1A
EXISTING
General Notes:
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 33 A
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 11947 VA
G General 8497 VA 100.00% 8497 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 32 A
M Motor 1176 VA 125.00% 1470 VA Total Connected Load: 11653 VA
R Receptacle 1980 VA 100.00% 1980 VA
L Lighting 0 VA 0.00% 0 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 78 % A-B 163 % B-C 47 % C-A
Total Amps: 33 A 19 A 49 A
Total Load: 3761 VA 2240 VA 5652 VA
41 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 42
39 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 40
37 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 38
1 35 FA POWER EXTEND G 20 A 1 500 VA 0 VA 1 20 A -- Spare 36
33 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 34
31 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 32
29 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 30
27 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 28
25 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 26
1 23 MRI EXHAUST FAN M 20 A 1 1176 VA 0 VA 1 20 A -- Spare 24
21 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 22
19 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 20
2 17 R-PHARMACY PRINTERS G 20 A 1 1000 VA 0 VA 1 20 A -- Spare 18
2 15 R-PHARMACY PRINTER G 20 A 1 500 VA 0 VA 1 20 A -- Spare 16
2 13 R-PHARMACY REF G 20 A 1 900 VA 540 VA 1 20 A R R-PHARMACY DESK 14 2
2 11 R-PHARMACY REF G 20 A 1 900 VA 516 VA 1 20 A G R-PHARMACY HOOD 12 2
2 9 R-PHARMACY PRINTER G 20 A 1 200 VA 540 VA 1 20 A R R-FACP ROOM 10 1
2 7 R-PHARMACY WRK STAT R 20 A 1 900 VA 516 VA 1 20 A G R-PHARMACY HOOD 8 2
1 5 R-PHARMACY REFER. G 20 A 1 600 VA 960 VA 1 20 A G R-PHARMACY UC FREEZ 6 2
1 3 R-PHARMACY PRINTER G 20 A 1 400 VA 600 VA 1 20 A G R-PHARMACY UC REF 4 2
1 1 R-PHARMACY REGISTER G 20 A 1 700 VA 205 VA 1 20 A G R-PHARMACY PYXIS 2 2
Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note
1. EXISTING LOAD
2. NEW LOAD
Circuit Notes:
Enclosure: Type 1
Mounting: Surface Wire: 4 Bus Rating: 100 A
Supply From: Phase: 3 Mains Type: MLO
Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000
Panel EL1C
EXISTING
General Notes:
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 20 A
K Kitchen 1800 VA 90.00% 1620 VA Total Demand Load: 17042 VA
G General 13524 VA 100.00% 13524 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 20 A
M Motor 0 VA 0.00% 0 VA Total Connected Load: 16986 VA
R Receptacle 720 VA 100.00% 720 VA
L Lighting 942 VA 125.00% 1178 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 55 % A-B 26 % B-C 23 % C-A
Total Amps: 17 A 26 A 20 A
Total Load: 4573 VA 6950 VA 5489 VA
-- 41 Space -- -- -- 0 VA 5256 VA 42
-- 39 Space -- -- -- 0 VA 6432 VA 40
-- 37 Space -- -- -- 0 VA 4356 VA
3 45 A R; K; G PANEL 'CL1A' VIA XFMR
38
1
-- 35 Space -- -- -- 0 VA 0 VA -- -- -- Space 36 --
-- 33 Space -- -- -- 0 VA 0 VA -- -- -- Space 34 --
-- 31 Space -- -- -- 0 VA 0 VA -- -- -- Space 32 --
-- 29 Space -- -- -- 0 VA 0 VA -- -- -- Space 30 --
-- 27 Space -- -- -- 0 VA 0 VA -- -- -- Space 28 --
-- 25 Space -- -- -- 0 VA 0 VA -- -- -- Space 26 --
-- 23 Space -- -- -- 0 VA 0 VA -- -- -- Space 24 --
-- 21 Space -- -- -- 0 VA 0 VA -- -- -- Space 22 --
-- 19 Space -- -- -- 0 VA 0 VA -- -- -- Space 20 --
-- 17 Space -- -- -- 0 VA 0 VA -- -- -- Space 18 --
-- 15 Space -- -- -- 0 VA 0 VA -- -- -- Space 16 --
-- 13 Space -- -- -- 0 VA 0 VA -- -- -- Space 14 --
-- 11 Space -- -- -- 0 VA 0 VA -- -- -- Space 12 --
-- 9 Space -- -- -- 0 VA 0 VA -- -- -- Space 10 --
-- 7 Space -- -- -- 0 VA 0 VA -- -- -- Space 8 --
2 5 L-PHARMACY L 20 A 1 233 VA 0 VA 1 20 A -- Spare 6
2 3 L-ULTRASND/NUC MED L 20 A 1 518 VA 0 VA 1 20 A -- Spare 4
1 1 L-ELEC/IT L 20 A 1 217 VA 0 VA 1 20 A -- Spare 2
Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note
1. EXISTING LOAD
2. NEW LOAD
Circuit Notes:
Enclosure: Type 1
Mounting: Surface Wire: 4 Bus Rating: 100 A
Supply From: Phase: 3 Mains Type: MLO
Location: Voltage: 480/277 Wye A.I.C. Rating: 10,000
Panel CH1A
EXISTING
06/30/17