ELECTRICAL PANEL
SCHEDULES
2017
03/10/17
PERMIT
VAIL
VALLEY
MEDICAL
CENTER
180 S. Frontage
Road
West,
Vail, CO 81657
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 206 A
K Kitchen 3000 VA 100.00% 3000 VA Total Demand Load: 74177 VA
G General 35277 VA 100.00% 35277 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 277 A
M Motor 0 VA 0.00% 0 VA Total Connected Load: 99789 VA
R Receptacle 61320 VA 58.15% 35660 VA
L Lighting 192 VA 125.00% 240 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 27 % A-B 9 % B-C 17 % C-A
Total Amps: 245 A 312 A 286 A
Total Load: 29373 VA 36751 VA 33665 VA
119 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 120
117 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 118
115 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 116
113 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 114
111 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 112
109 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 110
107 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 108
105 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 106
103 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 104
101 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 102
2 99 R-PHARMACY FAX G 20 A 1 1000 VA 900 VA 1 20 A R R-PHARMACY DESK 100 2
2 97 R-PHARMACY DESK R 20 A 1 900 VA 720 VA 1 20 A R R-PHARMACY DESK 98 2
2 95 R-PHARMACY R; G 20 A 1 920 VA 500 VA 1 20 A G R-PHARMACY UC REF 96 2
2 93 R-PHARMACY COFFEE G 20 A 1 1400 VA 360 VA 1 20 A R R-PHARMACY DESK 94 2
2 91 R-PHARMACY DESK R 20 A 1 900 VA 1200 VA 1 20 A G R-PHARMACY MICRO 92 2
89 1664 VA 4803 VA 90
1 87 TREADMILL G 20 A 2
1664 VA 4803 VA 88
1 85 R-WAITING/CORRIDOR R 20 A 1 720 VA 4803 VA
3 40 A G TREADMILL
86
1
1 83 R-HUARDS OFFICE R 20 A 1 900 VA 360 VA 1 20 A R R-BIOMOTION PITS 84 1
1 81 TREADMILL G 20 A 1 1500 VA 360 VA 1 20 A R R-BIOMOTION FLR BOX 82 1
1 79 CONF RM FLOOR BOX R 20 A 1 180 VA 1250 VA 80
77 Spare -- 20 A 1 0 VA 1250 VA
2 20 A G SERVER 78
1
1 75 R-NORTH OFFICES R 20 A 1 1620 VA 64 VA 1 20 A L L-UC & NICHE LIGHTS 76 1
1 73 R-BIOMOTION XRAY G 20 A 1 1000 VA 1000 VA 1 20 A G PT - WATER COOLER 74 1
1 71 R-BIOMOTION XRAY G 20 A 1 1000 VA 720 VA 1 20 A R R-VALET/EXTERIOR 72 1
1 69 R-BIOMOTION R 20 A 1 720 VA 1000 VA 1 20 A G BIOMOTION SHADES 70 1
1 67 R-MAIL/PLOT ROOM R 20 A 1 720 VA 720 VA 1 20 A R R-BIOMOTION CNTL 68 1
1 65 R-LOBBY GREETER R; L 20 A 1 848 VA 560 VA 1 20 A R; G R-BIOMOTION 66 1
1 63 R-LOBBY R 20 A 1 1080 VA 1080 VA 1 20 A R R-BIOMOTION 64 1
1 61 R-HUARDS LAB PRINT G 20 A 1 200 VA 540 VA 1 20 A R R-INCUBATOR/HOOD 62 1
1 59 LAB SERVICE PANELS R 20 A 1 720 VA 720 VA 1 20 A R LAB SERVICE PANELS 60 1
1 57 LAB SERVICE PANELS R 20 A 1 720 VA 720 VA 1 20 A R LAB SERVICE PANELS 58 1
1 55 R-HUARDS LAB R 20 A 1 1080 VA 1080 VA 1 20 A R R-HUARDS LAB 56 1
1 53 R-LOCKERS/TLT R 20 A 1 900 VA 720 VA 1 20 A R LAB SERVICE PANELS 54 1
1 51 R-SF RM - OFFICE/ELEC R 20 A 1 1080 VA 1080 VA 1 20 A R R-HUARDS LAB 52 1
49 Spare -- 20 A 1 0 VA 360 VA 1 20 A R R-MICROSCOPY 50 1
1 47 R-STAFF RM - MICRO R 20 A 1 1500 VA 1080 VA 1 20 A R R-HUARDS LAB 48 1
1 45 R-STAFF RM - COFFEE R 20 A 1 1500 VA 1500 VA 1 20 A K R-KITCHEN - DISPOSAL 46 1
1 43 R-STAFF ROOM R; G 20 A 1 740 VA 0 VA 1 20 A -- Spare 44
1 41 R-MAIL/PLOT ROOM R 20 A 1 1080 VA 1500 VA 1 20 A K R-KITCHEN - COFFEE 42 1
1 39 R-ICE MACHINE R 20 A 1 1500 VA 600 VA 1 20 A G R-CONF ROOM - TVS 40 1
1 37 R-CORRIDORS R 20 A 1 360 VA 720 VA 1 20 A R R-CONFERENCE ROOM 38 1
1 35 R-FRONT DESK - PRINT R; G 20 A 1 560 VA 1440 VA 1 20 A R R-OFFICES 36 1
1 33 R-FRONT DESK R 20 A 1 1080 VA 1000 VA 1 20 A G R-MAIL - COPIER 34 1
1 31 R-FRONT DSK - COPIER R 20 A 1 1000 VA 1260 VA 1 20 A R R-CORRIDOR 32 1
1 29 R-THERP. WORKSTAT R 20 A 1 740 VA 1260 VA 1 20 A R R-OFFICES 30 1
1 27 R-THERP. WORKSTAT R 20 A 1 720 VA 1080 VA 1 20 A R R-OFFICES 28 1
1 25 R-THERP. WORKSTAT R 20 A 1 720 VA 1080 VA 1 20 A R R-OFFICES 26 1
1 23 R-PHY. THER. - WAITING R 20 A 1 540 VA 1000 VA 1 20 A G R-MED REC - COPIER 24 1
1 21 R-PRIV. TREATMENT R 20 A 1 720 VA 1080 VA 1 20 A R R-MEDICAL RECORDS 22 1
1 19 R-OCCUP. THERAPY R 20 A 1 540 VA 900 VA 1 20 A R R-MEDICAL RECORDS 20 1
1 17 R-OCCUP. THER- TABLE R; G 20 A 1 1100 VA 900 VA 1 20 A R R-MEDICAL RECORDS 18 1
1 15 R-THERAPY FLR BX R 20 A 1 180 VA 980 VA 1 20 A R; G R-HUARDS LAB - TVS 16 1
1 13 R-THERAPY FLR BX R 20 A 1 180 VA 900 VA 1 20 A R R-HUARDS LAB OFFICES 14 1
1 11 R-PHY. THER. - BEDS R 20 A 1 1080 VA 900 VA 1 20 A R R-HUARDS MICROSCO. 12 1
1 9 R-PHY. THER. - BEDS R 20 A 1 1080 VA 1080 VA 1 20 A R R-HUARDS MICROSCO. 10 1
1 7 R-PHY. THER. - BEDS R 20 A 1 900 VA 900 VA 1 20 A R R-HUARDS LAB CONF. 8 1
1 5 R-PHY. THER. - BEDS R 20 A 1 900 VA 1500 VA 1 20 A G R-HUARDS LAB - ICE 6 1
1 3 R-PHY. THER - TVS G 20 A 1 600 VA 900 VA 1 20 A R R-HUARDS LAB OFFICES 4 1
1 1 R-PHYSICAL THERAPY R 20 A 1 900 VA 900 VA 1 20 A R R-HUARDS LAB OFFICES 2 1
Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note
1. EXISTING LOAD
2. NEW LOAD
Circuit Notes:
Enclosure: Type 1 MCB Rating: 250 A
Mounting: Surface Wire: 4 Bus Rating: 250 A
Supply From: T75 Phase: 3 Mains Type: MCB
Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000
Panel NL1A
EXISTING
General Notes:
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 29 A
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 10375 VA
G General 10375 VA 100.00% 10375 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 29 A
M Motor 0 VA 0.00% 0 VA Total Connected Load: 10375 VA
R Receptacle 0 VA 0.00% 0 VA
L Lighting 0 VA 0.00% 0 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 46 % A-B 16 % B-C 26 % C-A
Total Amps: 35 A 24 A 28 A
Total Load: 4175 VA 2900 VA 3300 VA
41 0 VA 0 VA 1 20 A -- Spare 42
39 0 VA 0 VA 1 20 A -- Spare 40
37
SPD -- 30 A 3
0 VA 0 VA 1 20 A -- Spare 38
35 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 36
33 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 34
31 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 32
29 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 30
27 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 28
25 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 26
23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24
21 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 22
19 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 20
2 17 PHARMACY ADO G 20 A 1 400 VA 18
1 15 LWR LVL - DOOR PWR G 20 A 1 600 VA 500 VA 1 20 A G 1ST FLR LAB - AAP 16 1
1 13 2ND FLR - DOOR PWR G 20 A 1 400 VA 700 VA 1 20 A G 2ND FLR - CARD READR 14 1
1 11 AREA ALARM PANEL G 20 A 1 500 VA 400 VA 1 20 A G LWR LVL - DOOR PWR 12 1
1 9 AREA ALARM PANEL G 20 A 1 500 VA 300 VA 1 20 A G LWR LVL - ELEV SMOKE 10 1
1 7 AREA ALARM PANEL G 20 A 1 1000 VA 1375 VA 1 20 A G 1ST FLR EGRESS DRS 8 1
1 5 1ST FLR - FA PWR SUPP G 20 A 1 500 VA 1500 VA 1 20 A G 1ST FLR EGRESS DRS 6 1
1 3 1ST FLR - DOOR CNTL G 20 A 1 500 VA 500 VA 1 20 A G 2ND FLR - FA PWR SUPP 4 1
1 1 2ND FLR - DOOR PWR G 20 A 1 200 VA 500 VA 1 20 A G 2ND FLR - DOOR PWR 2 1
Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note
1. EXISTING LOAD
2. NEW LOAD
Circuit Notes:
Enclosure: Type 1
Mounting: Surface Wire: 4 Bus Rating: 100 A
Supply From: T15 Phase: 3 Mains Type: MCB
Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000
Panel SL1A
EXISTING
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 86 A
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 31050 VA
G General 15404 VA 100.00% 15404 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 83 A
M Motor 14554 VA 107.50% 15646 VA Total Connected Load: 29958 VA
R Receptacle 0 VA 0.00% 0 VA
L Lighting 0 VA 0.00% 0 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 9 % A-B 44 % B-C 56 % C-A
Total Amps: 100 A 92 A 64 A
Total Load: 11597 VA 10647 VA 7713 VA
41 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 42
39 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 40
37 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 38
35 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 36
33 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 34
2 31 FIRE/SMOKE DAMPER M 20 A 1 50 VA 0 VA 1 20 A -- Spare 32
29 797 VA 797 VA 30
27 797 VA 797 VA 28
25
EF-16 M 20 A 3
797 VA 797 VA
3 20 A M EF-17
26
23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24
1 21 R-FUME HOOD G 20 A 1 1200 VA 150 VA 1 20 A M DI-2 22 1
1 19 R-FUME HOOD G 20 A 1 1200 VA 996 VA 1 20 A G R-TRI-GAS INCUBATOR 20 1
1 17 WASHER DISINFECTOR G 20 A 1 1500 VA 840 VA 1 20 A G STEAM STER. CNTRL 18 1
15 2028 VA 2184 VA 16
1 13 HAC-1 M 20 A 2 2028 VA 2184 VA
2 20 A M CU-ELEV2 14
1
1 11 R-LAB HOOD G 20 A 1 1200 VA 180 VA 1 20 A G R-BIO-REACTOR 12 1
1 9 R-LAB HOOD G 20 A 1 996 VA 996 VA 1 20 A G R-INCUBATOR 10 1
1 7 R-LAB HOOD G 20 A 1 1200 VA 996 VA 1 20 A G R-LAB HOOD 8 1
1 5 R-LAB HOOD G 20 A 1 1200 VA 1200 VA 1 20 A G R-LAB HOOD 6 1
1 3 FIRE/SMOKE DAMPERS M 20 A 1 300 VA 1200 VA 1 20 A G R-INCUBATOR 4 1
1 1 FIRE/SMOKE DAMPERS M 20 A 1 850 VA 500 VA 1 20 A G MECHANICAL CNTRLS 2 1
Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note
1. EXISTING LOAD
2. NEW LOAD
Circuit Notes:
Enclosure: Type 1 MCB Rating: 100 A
Mounting: Surface Wire: 4 Bus Rating: 100 A
Supply From: Phase: 3 Mains Type: MCB
Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000
Panel QL1A
EXISTING
General Notes:
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 39 A
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 32020 VA
G General 10375 VA 100.00% 10375 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 33 A
M Motor 0 VA 0.00% 0 VA Total Connected Load: 27691 VA
R Receptacle 0 VA 0.00% 0 VA
L Lighting 17316 VA 125.00% 21645 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 4 % A-B 19 % B-C 25 % C-A
Total Amps: 37 A 35 A 30 A
Total Load: 9968 VA 9548 VA 8174 VA
41 3300 VA 4260 VA 42
39 2900 VA 4260 VA
40
1
37
PANEL 'SL1A' VIA XFMR G 25 A 3
4175 VA 4260 VA
3 25 A L PANEL 'SH3A'
38
1
35 0 VA 0 VA 1 20 A -- Spare 36
33 0 VA 0 VA 1 20 A -- Spare 34
1
31
SPD -- 30 A 3
0 VA 0 VA 1 20 A -- Spare 32
29 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 30
27 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 28
25 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 26
23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24
21 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 22
19 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 20
17 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 18
15 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 16
13 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 14
11 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 12
9 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 10
7 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 8
1 5 L-BASEMENT EGRESS L 20 A 1 424 VA 190 VA 1 20 A L L 6
1 3 L-1ST FLOOR EGRESS L 20 A 1 1916 VA 472 VA 1 20 A L L-ADMIN/NUC MED 4 2
1 1 L-2ND FLOOR EGRESS L 20 A 1 839 VA 694 VA 1 20 A L L-EXTERIOR 2 1
Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note
1. EXISTING LOAD
2. NEW LOAD
Circuit Notes:
Enclosure: Type 1
Mounting: Surface Wire: 4 Bus Rating: 100 A
Supply From: Phase: 3 Mains Type: MLO
Location: Voltage: 480/277 Wye A.I.C. Rating: 10,000
Panel SH1A
EXISTING
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 44 A
K Kitchen 1800 VA 90.00% 1620 VA Total Demand Load: 15864 VA
G General 13524 VA 100.00% 13524 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 45 A
M Motor 0 VA 0.00% 0 VA Total Connected Load: 16044 VA
R Receptacle 720 VA 100.00% 720 VA
L Lighting 0 VA 0.00% 0 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: 51 % A-B 22 % B-C 24 % C-A
Total Amps: 36 A 55 A 45 A
Total Load: 4356 VA 6432 VA 5256 VA
-- 41 Space -- -- -- 0 VA 0 VA -- -- -- Space 42 --
-- 39 Space -- -- -- 0 VA 0 VA -- -- -- Space 40 --
-- 37 Space -- -- -- 0 VA 0 VA -- -- -- Space 38 --
-- 35 Space -- -- -- 0 VA 0 VA -- -- -- Space 36 --
-- 33 Space -- -- -- 0 VA 0 VA -- -- -- Space 34 --
-- 31 Space -- -- -- 0 VA 0 VA -- -- -- Space 32 --
29 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 30
27 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 28
25 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 26
23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24
21 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 22
19 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 20
17 2496 VA 0 VA 1 20 A -- Spare 18
2 15
R-NUC. MED CAMERA G 30 A 2
2496 VA 0 VA 1 20 A -- Spare 16
1 13 LAB EQUIPMENT -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 14
2 11 R-NUC. MED - UREF G 20 A 1 600 VA 720 VA 1 20 A R R-NUC. MED - CONTROL 12 2
9 1248 VA 1248 VA 10
1 7 LAB FREEZER G 20 A 2 1248 VA 1248 VA
2 20 A G LAB FREEZER 8
1
1 5 R-CONF. - UC REF K 20 A 1 600 VA 840 VA 1 20 A G LAB FREEZER 6 1
1 3 R-KITCHEN - REF K 20 A 1 600 VA 840 VA 1 20 A G LAB FREEZER 4 1
1 1 R-STAFF ROOM - REF K 20 A 1 600 VA 1260 VA 1 20 A G LAB FREEZER 2 1
Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note
1. EXISTING LOAD
2. NEW LOAD
Circuit Notes:
Enclosure: Type 1 MCB Rating: 100 A
Mounting: Surface Wire: 4 Bus Rating: 100 A
Supply From: T30 Phase: 3 Mains Type: MCB
Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000
Panel CL1A
EXISTING
O Other 0 VA 0.00% 0 VA
E Existing 0 VA 0.00% 0 VA Total Demand Current: 0 A
K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 265 VA
G General 0 VA 0.00% 0 VA
C Continuous 0 VA 0.00% 0 VA Total Connected Current: 0 A
M Motor 0 VA 0.00% 0 VA Total Connected Load: 212 VA
R Receptacle 0 VA 0.00% 0 VA
L Lighting 212 VA 125.00% 265 VA Power Factor: 1
Load Type Connected Load Demand Factor Demand Load Panel Totals
Phase Balance: % A-B % B-C % C-A
Total Amps: 1 A 0 A 0 A
Total Load: 212 VA 0 VA 0 VA
41 0 VA 0 VA 42
39 0 VA 0 VA 40 1
37
PANEL 'EH3A' -- 100 A 3
0 VA 0 VA
3 70 A -- PANEL 'EL2A'
38
1
35 0 VA 0 VA 36
33 0 VA 0 VA 2 20 A -- OR #4
34
1
1
31
PANEL 'CL2LAB' -- 70 A 3
0 VA 0 VA 32
-- 29 Space -- -- -- 0 VA 0 VA
2 20 A -- OR #3
30
1
-- 27 Space -- -- -- 0 VA 0 VA 28
-- 25 Space -- -- -- 0 VA 0 VA
2 20 A -- OR #2 'B'
26
1
-- 23 Space -- -- -- 0 VA 0 VA 24
-- 21 Space -- -- -- 0 VA 0 VA
2 20 A -- OR #1 'A'
22
1
-- 19 Space -- -- -- 0 VA 0 VA 20
-- 17 Space -- -- -- 0 VA 0 VA
2 20 A -- C-SECTION OR
18
1
-- 15 Space -- -- -- 0 VA 0 VA 16
-- 13 Space -- -- -- 0 VA 0 VA
2 20 A -- OR #4
14
1
-- 11 Space -- -- -- 0 VA 0 VA 12
-- 9 Space -- -- -- 0 VA 0 VA
2 20 A -- OR #3
10
1
1 7 L-LAB -- 20 A 1 0 VA 0 VA 8
1 5 L-LDRP & NURSERY -- 20 A 1 0 VA 0 VA
2 20 A -- OR #2 'A'
6
1
1 3 L-POSTPARTUM/C-SECT -- 20 A 1 0 VA 0 VA 4
2 1 L-MSA LARGE EXAM/TLT L 20 A 1 212 VA 0 VA
2 20 A -- OR #1 'B' 2
1
Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note
1. EXISTING LOAD
2. NEW LOAD
Circuit Notes:
Enclosure: Type 1 MCB Rating: 250 A
Mounting: Surface Wire: 4 Bus Rating: 250 A
Supply From: Phase: 3 Mains Type: MCB
Location: Voltage: 480/277 Wye A.I.C. Rating: 35,000
Panel EH2C