HomeMy WebLinkAboutB17-0092_E-302-1_1498849080.pdf2901 Blake Street, Suite 100 Denver, CO 80205 303.861.8555 Denver 1 A B C D E 2 3 4 5 6 A B C D E 1 2 3 4 5 6 DPA Project: Sheet Number: COPYRIGHT - DAVIS PARTNERSHIP, P.C. Sheet Title: Revisions Date Sheet Information Project Information Issuance Consultant CENTRAL WING RENOVATION 3/10/2017 6:58:12 AM 15924.00 E-302.1 ELECTRICAL PANEL SCHEDULES 2017 03/10/17 PERMIT VAIL VALLEY MEDICAL CENTER 180 S. Frontage Road West, Vail, CO 81657 O Other 0 VA 0.00% 0 VA E Existing 0 VA 0.00% 0 VA Total Demand Current: 206 A K Kitchen 3000 VA 100.00% 3000 VA Total Demand Load: 74177 VA G General 35277 VA 100.00% 35277 VA C Continuous 0 VA 0.00% 0 VA Total Connected Current: 277 A M Motor 0 VA 0.00% 0 VA Total Connected Load: 99789 VA R Receptacle 61320 VA 58.15% 35660 VA L Lighting 192 VA 125.00% 240 VA Power Factor: 1 Load Type Connected Load Demand Factor Demand Load Panel Totals Phase Balance: 27 % A-B 9 % B-C 17 % C-A Total Amps: 245 A 312 A 286 A Total Load: 29373 VA 36751 VA 33665 VA 119 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 120 117 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 118 115 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 116 113 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 114 111 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 112 109 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 110 107 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 108 105 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 106 103 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 104 101 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 102 2 99 R-PHARMACY FAX G 20 A 1 1000 VA 900 VA 1 20 A R R-PHARMACY DESK 100 2 2 97 R-PHARMACY DESK R 20 A 1 900 VA 720 VA 1 20 A R R-PHARMACY DESK 98 2 2 95 R-PHARMACY R; G 20 A 1 920 VA 500 VA 1 20 A G R-PHARMACY UC REF 96 2 2 93 R-PHARMACY COFFEE G 20 A 1 1400 VA 360 VA 1 20 A R R-PHARMACY DESK 94 2 2 91 R-PHARMACY DESK R 20 A 1 900 VA 1200 VA 1 20 A G R-PHARMACY MICRO 92 2 89 1664 VA 4803 VA 90 1 87 TREADMILL G 20 A 2 1664 VA 4803 VA 88 1 85 R-WAITING/CORRIDOR R 20 A 1 720 VA 4803 VA 3 40 A G TREADMILL 86 1 1 83 R-HUARDS OFFICE R 20 A 1 900 VA 360 VA 1 20 A R R-BIOMOTION PITS 84 1 1 81 TREADMILL G 20 A 1 1500 VA 360 VA 1 20 A R R-BIOMOTION FLR BOX 82 1 1 79 CONF RM FLOOR BOX R 20 A 1 180 VA 1250 VA 80 77 Spare -- 20 A 1 0 VA 1250 VA 2 20 A G SERVER 78 1 1 75 R-NORTH OFFICES R 20 A 1 1620 VA 64 VA 1 20 A L L-UC & NICHE LIGHTS 76 1 1 73 R-BIOMOTION XRAY G 20 A 1 1000 VA 1000 VA 1 20 A G PT - WATER COOLER 74 1 1 71 R-BIOMOTION XRAY G 20 A 1 1000 VA 720 VA 1 20 A R R-VALET/EXTERIOR 72 1 1 69 R-BIOMOTION R 20 A 1 720 VA 1000 VA 1 20 A G BIOMOTION SHADES 70 1 1 67 R-MAIL/PLOT ROOM R 20 A 1 720 VA 720 VA 1 20 A R R-BIOMOTION CNTL 68 1 1 65 R-LOBBY GREETER R; L 20 A 1 848 VA 560 VA 1 20 A R; G R-BIOMOTION 66 1 1 63 R-LOBBY R 20 A 1 1080 VA 1080 VA 1 20 A R R-BIOMOTION 64 1 1 61 R-HUARDS LAB PRINT G 20 A 1 200 VA 540 VA 1 20 A R R-INCUBATOR/HOOD 62 1 1 59 LAB SERVICE PANELS R 20 A 1 720 VA 720 VA 1 20 A R LAB SERVICE PANELS 60 1 1 57 LAB SERVICE PANELS R 20 A 1 720 VA 720 VA 1 20 A R LAB SERVICE PANELS 58 1 1 55 R-HUARDS LAB R 20 A 1 1080 VA 1080 VA 1 20 A R R-HUARDS LAB 56 1 1 53 R-LOCKERS/TLT R 20 A 1 900 VA 720 VA 1 20 A R LAB SERVICE PANELS 54 1 1 51 R-SF RM - OFFICE/ELEC R 20 A 1 1080 VA 1080 VA 1 20 A R R-HUARDS LAB 52 1 49 Spare -- 20 A 1 0 VA 360 VA 1 20 A R R-MICROSCOPY 50 1 1 47 R-STAFF RM - MICRO R 20 A 1 1500 VA 1080 VA 1 20 A R R-HUARDS LAB 48 1 1 45 R-STAFF RM - COFFEE R 20 A 1 1500 VA 1500 VA 1 20 A K R-KITCHEN - DISPOSAL 46 1 1 43 R-STAFF ROOM R; G 20 A 1 740 VA 0 VA 1 20 A -- Spare 44 1 41 R-MAIL/PLOT ROOM R 20 A 1 1080 VA 1500 VA 1 20 A K R-KITCHEN - COFFEE 42 1 1 39 R-ICE MACHINE R 20 A 1 1500 VA 600 VA 1 20 A G R-CONF ROOM - TVS 40 1 1 37 R-CORRIDORS R 20 A 1 360 VA 720 VA 1 20 A R R-CONFERENCE ROOM 38 1 1 35 R-FRONT DESK - PRINT R; G 20 A 1 560 VA 1440 VA 1 20 A R R-OFFICES 36 1 1 33 R-FRONT DESK R 20 A 1 1080 VA 1000 VA 1 20 A G R-MAIL - COPIER 34 1 1 31 R-FRONT DSK - COPIER R 20 A 1 1000 VA 1260 VA 1 20 A R R-CORRIDOR 32 1 1 29 R-THERP. WORKSTAT R 20 A 1 740 VA 1260 VA 1 20 A R R-OFFICES 30 1 1 27 R-THERP. WORKSTAT R 20 A 1 720 VA 1080 VA 1 20 A R R-OFFICES 28 1 1 25 R-THERP. WORKSTAT R 20 A 1 720 VA 1080 VA 1 20 A R R-OFFICES 26 1 1 23 R-PHY. THER. - WAITING R 20 A 1 540 VA 1000 VA 1 20 A G R-MED REC - COPIER 24 1 1 21 R-PRIV. TREATMENT R 20 A 1 720 VA 1080 VA 1 20 A R R-MEDICAL RECORDS 22 1 1 19 R-OCCUP. THERAPY R 20 A 1 540 VA 900 VA 1 20 A R R-MEDICAL RECORDS 20 1 1 17 R-OCCUP. THER- TABLE R; G 20 A 1 1100 VA 900 VA 1 20 A R R-MEDICAL RECORDS 18 1 1 15 R-THERAPY FLR BX R 20 A 1 180 VA 980 VA 1 20 A R; G R-HUARDS LAB - TVS 16 1 1 13 R-THERAPY FLR BX R 20 A 1 180 VA 900 VA 1 20 A R R-HUARDS LAB OFFICES 14 1 1 11 R-PHY. THER. - BEDS R 20 A 1 1080 VA 900 VA 1 20 A R R-HUARDS MICROSCO. 12 1 1 9 R-PHY. THER. - BEDS R 20 A 1 1080 VA 1080 VA 1 20 A R R-HUARDS MICROSCO. 10 1 1 7 R-PHY. THER. - BEDS R 20 A 1 900 VA 900 VA 1 20 A R R-HUARDS LAB CONF. 8 1 1 5 R-PHY. THER. - BEDS R 20 A 1 900 VA 1500 VA 1 20 A G R-HUARDS LAB - ICE 6 1 1 3 R-PHY. THER - TVS G 20 A 1 600 VA 900 VA 1 20 A R R-HUARDS LAB OFFICES 4 1 1 1 R-PHYSICAL THERAPY R 20 A 1 900 VA 900 VA 1 20 A R R-HUARDS LAB OFFICES 2 1 Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note 1. EXISTING LOAD 2. NEW LOAD Circuit Notes: Enclosure: Type 1 MCB Rating: 250 A Mounting: Surface Wire: 4 Bus Rating: 250 A Supply From: T75 Phase: 3 Mains Type: MCB Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000 Panel NL1A EXISTING General Notes: O Other 0 VA 0.00% 0 VA E Existing 0 VA 0.00% 0 VA Total Demand Current: 29 A K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 10375 VA G General 10375 VA 100.00% 10375 VA C Continuous 0 VA 0.00% 0 VA Total Connected Current: 29 A M Motor 0 VA 0.00% 0 VA Total Connected Load: 10375 VA R Receptacle 0 VA 0.00% 0 VA L Lighting 0 VA 0.00% 0 VA Power Factor: 1 Load Type Connected Load Demand Factor Demand Load Panel Totals Phase Balance: 46 % A-B 16 % B-C 26 % C-A Total Amps: 35 A 24 A 28 A Total Load: 4175 VA 2900 VA 3300 VA 41 0 VA 0 VA 1 20 A -- Spare 42 39 0 VA 0 VA 1 20 A -- Spare 40 37 SPD -- 30 A 3 0 VA 0 VA 1 20 A -- Spare 38 35 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 36 33 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 34 31 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 32 29 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 30 27 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 28 25 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 26 23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24 21 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 22 19 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 20 2 17 PHARMACY ADO G 20 A 1 400 VA 18 1 15 LWR LVL - DOOR PWR G 20 A 1 600 VA 500 VA 1 20 A G 1ST FLR LAB - AAP 16 1 1 13 2ND FLR - DOOR PWR G 20 A 1 400 VA 700 VA 1 20 A G 2ND FLR - CARD READR 14 1 1 11 AREA ALARM PANEL G 20 A 1 500 VA 400 VA 1 20 A G LWR LVL - DOOR PWR 12 1 1 9 AREA ALARM PANEL G 20 A 1 500 VA 300 VA 1 20 A G LWR LVL - ELEV SMOKE 10 1 1 7 AREA ALARM PANEL G 20 A 1 1000 VA 1375 VA 1 20 A G 1ST FLR EGRESS DRS 8 1 1 5 1ST FLR - FA PWR SUPP G 20 A 1 500 VA 1500 VA 1 20 A G 1ST FLR EGRESS DRS 6 1 1 3 1ST FLR - DOOR CNTL G 20 A 1 500 VA 500 VA 1 20 A G 2ND FLR - FA PWR SUPP 4 1 1 1 2ND FLR - DOOR PWR G 20 A 1 200 VA 500 VA 1 20 A G 2ND FLR - DOOR PWR 2 1 Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note 1. EXISTING LOAD 2. NEW LOAD Circuit Notes: Enclosure: Type 1 Mounting: Surface Wire: 4 Bus Rating: 100 A Supply From: T15 Phase: 3 Mains Type: MCB Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000 Panel SL1A EXISTING O Other 0 VA 0.00% 0 VA E Existing 0 VA 0.00% 0 VA Total Demand Current: 86 A K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 31050 VA G General 15404 VA 100.00% 15404 VA C Continuous 0 VA 0.00% 0 VA Total Connected Current: 83 A M Motor 14554 VA 107.50% 15646 VA Total Connected Load: 29958 VA R Receptacle 0 VA 0.00% 0 VA L Lighting 0 VA 0.00% 0 VA Power Factor: 1 Load Type Connected Load Demand Factor Demand Load Panel Totals Phase Balance: 9 % A-B 44 % B-C 56 % C-A Total Amps: 100 A 92 A 64 A Total Load: 11597 VA 10647 VA 7713 VA 41 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 42 39 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 40 37 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 38 35 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 36 33 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 34 2 31 FIRE/SMOKE DAMPER M 20 A 1 50 VA 0 VA 1 20 A -- Spare 32 29 797 VA 797 VA 30 27 797 VA 797 VA 28 25 EF-16 M 20 A 3 797 VA 797 VA 3 20 A M EF-17 26 23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24 1 21 R-FUME HOOD G 20 A 1 1200 VA 150 VA 1 20 A M DI-2 22 1 1 19 R-FUME HOOD G 20 A 1 1200 VA 996 VA 1 20 A G R-TRI-GAS INCUBATOR 20 1 1 17 WASHER DISINFECTOR G 20 A 1 1500 VA 840 VA 1 20 A G STEAM STER. CNTRL 18 1 15 2028 VA 2184 VA 16 1 13 HAC-1 M 20 A 2 2028 VA 2184 VA 2 20 A M CU-ELEV2 14 1 1 11 R-LAB HOOD G 20 A 1 1200 VA 180 VA 1 20 A G R-BIO-REACTOR 12 1 1 9 R-LAB HOOD G 20 A 1 996 VA 996 VA 1 20 A G R-INCUBATOR 10 1 1 7 R-LAB HOOD G 20 A 1 1200 VA 996 VA 1 20 A G R-LAB HOOD 8 1 1 5 R-LAB HOOD G 20 A 1 1200 VA 1200 VA 1 20 A G R-LAB HOOD 6 1 1 3 FIRE/SMOKE DAMPERS M 20 A 1 300 VA 1200 VA 1 20 A G R-INCUBATOR 4 1 1 1 FIRE/SMOKE DAMPERS M 20 A 1 850 VA 500 VA 1 20 A G MECHANICAL CNTRLS 2 1 Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note 1. EXISTING LOAD 2. NEW LOAD Circuit Notes: Enclosure: Type 1 MCB Rating: 100 A Mounting: Surface Wire: 4 Bus Rating: 100 A Supply From: Phase: 3 Mains Type: MCB Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000 Panel QL1A EXISTING General Notes: O Other 0 VA 0.00% 0 VA E Existing 0 VA 0.00% 0 VA Total Demand Current: 39 A K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 32020 VA G General 10375 VA 100.00% 10375 VA C Continuous 0 VA 0.00% 0 VA Total Connected Current: 33 A M Motor 0 VA 0.00% 0 VA Total Connected Load: 27691 VA R Receptacle 0 VA 0.00% 0 VA L Lighting 17316 VA 125.00% 21645 VA Power Factor: 1 Load Type Connected Load Demand Factor Demand Load Panel Totals Phase Balance: 4 % A-B 19 % B-C 25 % C-A Total Amps: 37 A 35 A 30 A Total Load: 9968 VA 9548 VA 8174 VA 41 3300 VA 4260 VA 42 39 2900 VA 4260 VA 40 1 37 PANEL 'SL1A' VIA XFMR G 25 A 3 4175 VA 4260 VA 3 25 A L PANEL 'SH3A' 38 1 35 0 VA 0 VA 1 20 A -- Spare 36 33 0 VA 0 VA 1 20 A -- Spare 34 1 31 SPD -- 30 A 3 0 VA 0 VA 1 20 A -- Spare 32 29 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 30 27 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 28 25 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 26 23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24 21 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 22 19 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 20 17 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 18 15 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 16 13 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 14 11 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 12 9 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 10 7 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 8 1 5 L-BASEMENT EGRESS L 20 A 1 424 VA 190 VA 1 20 A L L 6 1 3 L-1ST FLOOR EGRESS L 20 A 1 1916 VA 472 VA 1 20 A L L-ADMIN/NUC MED 4 2 1 1 L-2ND FLOOR EGRESS L 20 A 1 839 VA 694 VA 1 20 A L L-EXTERIOR 2 1 Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note 1. EXISTING LOAD 2. NEW LOAD Circuit Notes: Enclosure: Type 1 Mounting: Surface Wire: 4 Bus Rating: 100 A Supply From: Phase: 3 Mains Type: MLO Location: Voltage: 480/277 Wye A.I.C. Rating: 10,000 Panel SH1A EXISTING O Other 0 VA 0.00% 0 VA E Existing 0 VA 0.00% 0 VA Total Demand Current: 44 A K Kitchen 1800 VA 90.00% 1620 VA Total Demand Load: 15864 VA G General 13524 VA 100.00% 13524 VA C Continuous 0 VA 0.00% 0 VA Total Connected Current: 45 A M Motor 0 VA 0.00% 0 VA Total Connected Load: 16044 VA R Receptacle 720 VA 100.00% 720 VA L Lighting 0 VA 0.00% 0 VA Power Factor: 1 Load Type Connected Load Demand Factor Demand Load Panel Totals Phase Balance: 51 % A-B 22 % B-C 24 % C-A Total Amps: 36 A 55 A 45 A Total Load: 4356 VA 6432 VA 5256 VA -- 41 Space -- -- -- 0 VA 0 VA -- -- -- Space 42 -- -- 39 Space -- -- -- 0 VA 0 VA -- -- -- Space 40 -- -- 37 Space -- -- -- 0 VA 0 VA -- -- -- Space 38 -- -- 35 Space -- -- -- 0 VA 0 VA -- -- -- Space 36 -- -- 33 Space -- -- -- 0 VA 0 VA -- -- -- Space 34 -- -- 31 Space -- -- -- 0 VA 0 VA -- -- -- Space 32 -- 29 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 30 27 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 28 25 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 26 23 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 24 21 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 22 19 Spare -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 20 17 2496 VA 0 VA 1 20 A -- Spare 18 2 15 R-NUC. MED CAMERA G 30 A 2 2496 VA 0 VA 1 20 A -- Spare 16 1 13 LAB EQUIPMENT -- 20 A 1 0 VA 0 VA 1 20 A -- Spare 14 2 11 R-NUC. MED - UREF G 20 A 1 600 VA 720 VA 1 20 A R R-NUC. MED - CONTROL 12 2 9 1248 VA 1248 VA 10 1 7 LAB FREEZER G 20 A 2 1248 VA 1248 VA 2 20 A G LAB FREEZER 8 1 1 5 R-CONF. - UC REF K 20 A 1 600 VA 840 VA 1 20 A G LAB FREEZER 6 1 1 3 R-KITCHEN - REF K 20 A 1 600 VA 840 VA 1 20 A G LAB FREEZER 4 1 1 1 R-STAFF ROOM - REF K 20 A 1 600 VA 1260 VA 1 20 A G LAB FREEZER 2 1 Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note 1. EXISTING LOAD 2. NEW LOAD Circuit Notes: Enclosure: Type 1 MCB Rating: 100 A Mounting: Surface Wire: 4 Bus Rating: 100 A Supply From: T30 Phase: 3 Mains Type: MCB Location: Voltage: 120/208 Wye A.I.C. Rating: 10,000 Panel CL1A EXISTING O Other 0 VA 0.00% 0 VA E Existing 0 VA 0.00% 0 VA Total Demand Current: 0 A K Kitchen 0 VA 0.00% 0 VA Total Demand Load: 265 VA G General 0 VA 0.00% 0 VA C Continuous 0 VA 0.00% 0 VA Total Connected Current: 0 A M Motor 0 VA 0.00% 0 VA Total Connected Load: 212 VA R Receptacle 0 VA 0.00% 0 VA L Lighting 212 VA 125.00% 265 VA Power Factor: 1 Load Type Connected Load Demand Factor Demand Load Panel Totals Phase Balance: % A-B % B-C % C-A Total Amps: 1 A 0 A 0 A Total Load: 212 VA 0 VA 0 VA 41 0 VA 0 VA 42 39 0 VA 0 VA 40 1 37 PANEL 'EH3A' -- 100 A 3 0 VA 0 VA 3 70 A -- PANEL 'EL2A' 38 1 35 0 VA 0 VA 36 33 0 VA 0 VA 2 20 A -- OR #4 34 1 1 31 PANEL 'CL2LAB' -- 70 A 3 0 VA 0 VA 32 -- 29 Space -- -- -- 0 VA 0 VA 2 20 A -- OR #3 30 1 -- 27 Space -- -- -- 0 VA 0 VA 28 -- 25 Space -- -- -- 0 VA 0 VA 2 20 A -- OR #2 'B' 26 1 -- 23 Space -- -- -- 0 VA 0 VA 24 -- 21 Space -- -- -- 0 VA 0 VA 2 20 A -- OR #1 'A' 22 1 -- 19 Space -- -- -- 0 VA 0 VA 20 -- 17 Space -- -- -- 0 VA 0 VA 2 20 A -- C-SECTION OR 18 1 -- 15 Space -- -- -- 0 VA 0 VA 16 -- 13 Space -- -- -- 0 VA 0 VA 2 20 A -- OR #4 14 1 -- 11 Space -- -- -- 0 VA 0 VA 12 -- 9 Space -- -- -- 0 VA 0 VA 2 20 A -- OR #3 10 1 1 7 L-LAB -- 20 A 1 0 VA 0 VA 8 1 5 L-LDRP & NURSERY -- 20 A 1 0 VA 0 VA 2 20 A -- OR #2 'A' 6 1 1 3 L-POSTPARTUM/C-SECT -- 20 A 1 0 VA 0 VA 4 2 1 L-MSA LARGE EXAM/TLT L 20 A 1 212 VA 0 VA 2 20 A -- OR #1 'B' 2 1 Note Circuit Load Type Trip Pol... A B C Pol... Trip Type Load Circuit Note 1. EXISTING LOAD 2. NEW LOAD Circuit Notes: Enclosure: Type 1 MCB Rating: 250 A Mounting: Surface Wire: 4 Bus Rating: 250 A Supply From: Phase: 3 Mains Type: MCB Location: Voltage: 480/277 Wye A.I.C. Rating: 35,000 Panel EH2C 06/30/17