HomeMy WebLinkAboutB17-0092_E-401-1_1508947650.pdfSINGLE GANG PLASTER RING WITH
GROUND SCREW AND PIGTAIL TO MATCH
DRYWALL THICKNESS
4" SQ COMBO BOX
NO SCALE
16135.3
RECEPTACLE BOX SUPPORT DETAIL
TOP OF CABINET
TOP OF CABINET 80" (6'-8") OR 6" BELOW
CEILING
WHICHEVER IS LOWER
84" (7'-0") UON96" (8'-0") UON72" (6'-0") UON78" (6'-6") UON48" (4'-0") UON64" (5'-4") UONTYPICAL 9'-0" CEILING OR HIGHER
TOP OF CABINET
TYPICAL 8'-0" CEILING
2.
3.
NOTES:
1.
FINISHED FLOOR
18" (1'-6") UONNOTE: ALL DEVICES INDICATED TO BE
INSTALLED AT DIFFERENT MOUNTING
HEIGHTS AND LOCATED WITHIN ONE
STUD SPACE FROM EACH OTHER
SHALL ALIGN VERTICALLY, ON THE
SAME SIDE OF THE STUD. WHERE WALL
MOUNTED TELEPHONES OCCUR OVER
LIGHT SWITCHES, VOLUME CONTROLS,
ETC. OFFSET ONE STUD SPACE.
HEIGHTS SHOWN ARE TYPICAL TO CENTERLINE OF BOX UNLESS NOTED OTHERWISE.
WHERE EVER DEVICES ARE INDICATED TO BE ABOVE DOORS, DEVICE SHALL BE CENTERED BETWEEN TOP
OF DOOR TRIM AND CEILING LINE.
MOUNTING HEIGHTS SHOWN ON ARCHITECTURAL ELEVATIONS SHALL GOVERN OVER THOSE SHOWN ABOVE.
BOTTOM OF DEVICE
W
GFI
GZM
PB P P
CONTROL PANELS
TOP
S
TOP
S
PC
C
C
B
B
FAA
C
C
MDC
C
E
MD
C
C
FACP
SCR D CB E 1 2 S V
T TC
S SM I
M
NO SCALE
16143.1
F
TYPICAL DEVICE MOUNTING HEIGHTS
NOTE:
TRAPEZE SHALL BE PROVIDED
WHEREVER TWO OR MORE
RACEWAYS ARE RUN ADJACENT.
FUTURE STRUT TO BE
ATTACHED TO EXISTING
STRUT
NOTE: SEE SPECIFICATIONS FOR ADDITIONAL
SUPPORT, SEISMIC AND OTHER REQUIREMENTS.
U-CHANNEL STRUT
SPACE FOR FUTURE
RACEWAYS
1/2 W
MIN.
W
RACEWAYS INSTALLED AS
PART OF THIS CONTRACT
SHALL BE ATTACHED TO TOP
OF STRUT WITH APPROVED
U-CHANNEL STRUT
FASTENER
STEEL ALL
THREADPER SPECS
ATTACHED TO STRUCTURE
AS REQUIRED
NO SCALE
16190.2
TRAPEZE DETAIL
1/2"
1/4"
1/4"
3/16"
1/4"
3/16"
13/16"
WIDTH AS REQUIRED
2 1/2"
NOTES:
1. SEE SPECIFICATIONS FOR ADDITIONAL NAMEPLATE INFORMATION.
2. REWORD NAMEPLATE FOR FIELD CONDITIONS.
3. HP SHALL INDICATE HORSEPOWER.
UTILIZATION EQUIPMENT
NAMEPLATE DETAIL
EXHAUST FAN #1
480V 3Ø HP
FED FROM H1A
SCALE: FULL
16195.3
AIRFLOW
DIRECTION
INSERT RUBBER PLUG
THIS END OF INLET TUBE.
INLET TUBE HOLES FACE
UPSTREAM OF AIRFLOW.
TUBE SUPPORT HOLE ONLY FOR
DUCTS MORE THAN 3' WIDE
EXPECTED AIRFLOW DIRECTION
RETURN TUBE SLANT CUT FACE
ORIENTED DOWN-STREAM OF
AIRFLOW. DO NOT INSERT
RUBBER PLUG.
DUCT WIDTH
NO SCALE
16721.2
DUCT DETECTOR DETAIL NOTES:
2 1/2"
WIDTH AS REQUIRED
1. SEE SPECIFICATIONS FOR ADDITIONAL NAMEPLATE INFORMATION.
2. REWORD NAMEPLATE FOR FIELD CONDITIONS.
3. AMP RATING SHALL INDICATE BUS RATING.
SCALE: FULL
16195.2
PANEL L1A
22,000 AIC
120/208V 3Ø, 4W, 225A
FED FROM MDC 3/16"
1/4"
1/4"
1/4"
3/16"
3/16"
1/4"
3/16"
3/32"
1/4"
SUB-DISTRIBUTION CENTER
AND BRANCH PANELBOARD
NAMEPLATE DETAIL
PH A - BLACK; PH B - RED; PH C - BLUE
NEUTRAL - WHITE; GROUND - GREEN
3/16"
3/32"3/32"
4. CONTRACTOR TO COORDINATE DEIVCE MOUNTING HEIGHTS WITH WALL SURFACE SO THAT DEVICES DO NOT OVERLAP
TWO SURFACES. FOR EXAMPLE, LIGHT SWTICHES SHALL BE MOUNTED AT 44" WHERE WALL PROTECTION IS INSTALLED UP
TO 48"
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
CENTRAL WING RENOVATION
7/10/2017 1:48:04 PM15924.00
E-401.1
ELECTRICAL DETAILS
07/11/17PERMIT
RESUBMISSION
EAST WING
ADDITION
180 S Frontage Rd W, Vail, CO 8165710/25/17