LS201A.1
A1
LS201D.1
A1
LS201B.1
A3
LEGEND
EXISTING TO
REMAIN
NEW WALL
KEY PLAN
GENERAL NOTES
1. SPRINKLER SYSTEM PROTECTION WILL REMAIN
OPERATIONAL EXCEPT FOR ANY SPRINKLER MODIFICATION
REQUIRED TO ACCOMMODATE THE REMODEL. SPRINKLER
SYSTEM WILL BE OFF LINE FOR NOT MORE THAN 4 HOURS
FOR THE RESPECTIVE SMOKE COMPARTMENT WHILE
SPRINKLER REMODEL IS TAKING PLACE. UNLESS FIRE
WATCH IS IN PLACE.
2. SPRINKLER SYSTEM SHOP DRAWINGS WILL BE SUBMITTED
FOR REVIEW.
3. EXISTING SMOKE DETECTORS WILL BE COVERED DURING
THE REMODEL WITHIN THESE SUITES.
TEMPORARY PARTION
PER NFPA 241. PLASTIC
CURTAINS ARE NOT
ACCEPTABLE
REGION INDICATES AREA
NOT IN SCOPE
REMOVE AND REPLACE
CEILING
KEYNOTES
CONSTRUCTION SEQUENCE LEGEND
AREA NOT IN SCOPE
AREA OF SEQUENCE #2 - NUCLEAR MEDICINE SUITE
PLANNED TIMELINE: 05/08/17 - 9/13/17
NOTE: SPACE IS NON-OCCUPIED DURING
CONSTRUCTION BUT ILSM IS REQUIRED FOR
OCCUPANT SAFETY.
AREA OF SEQUENCE #2 - CLINIC (MSA)
PLANNED TIMELINE: 06/15/17 - 9/01/17
NOTE: SPACE IS NON-OCCUPIED DURING
CONSTRUCTION AND DOES NOT IMPACT BUILDING
OCCUPANT EGRESS.
REDUCED CORRIDOR WIDTH - MIN 4' - 0"4'-0" MINEXIT DISCHARGE
EXIT ACCESS
TEMPORARY PARTITION - COMPLIANT WITH NFPA
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
CENTRAL WING RENOVATION
7/11/2017 10:29:59 AM15924.00
LS201.1
OVERALL INTERIM LIFE
SAFETY PLAN - LEVEL 1
2017
07/11/17PERMIT
RESUBMISSION
VAIL VALLEY
MEDICAL
CENTER
180 S. Frontage
Road West, Vail, CO 816571
1/16" = 1'-0"A1 OVERALL INTERIM LIFE SAFETY PLAN & SEQUENCE PLAN - LEVEL 1
NORTH
A
B
C
D
E
2
ADDENDUM 1 05/23/17 1
ADDENDUM 3 06/27/17 2
10/25/17