HomeMy WebLinkAboutB17-0092_LS201D.1_1508947567.pdfLEGEND
EXISTING TO
REMAIN
NEW WALL
KEY PLAN
GENERAL NOTES
1. SPRINKLER SYSTEM PROTECTION WILL REMAIN
OPERATIONAL EXCEPT FOR ANY SPRINKLER MODIFICATION
REQUIRED TO ACCOMMODATE THE REMODEL. SPRINKLER
SYSTEM WILL BE OFF LINE FOR NOT MORE THAN 4 HOURS
FOR THE RESPECTIVE SMOKE COMPARTMENT WHILE
SPRINKLER REMODEL IS TAKING PLACE. UNLESS FIRE
WATCH IS IN PLACE.
2. SPRINKLER SYSTEM SHOP DRAWINGS WILL BE SUBMITTED
FOR REVIEW.
3. EXISTING SMOKE DETECTORS WILL BE COVERED DURING
THE REMODEL WITHIN THESE SUITES.
TEMPORARY PARTION
PER NFPA 241. PLASTIC
CURTAINS ARE NOT
ACCEPTABLE
REGION INDICATES AREA
NOT IN SCOPE
REMOVE AND REPLACE
CEILING
KEYNOTES
PASSAGE THROUGH EXISTING CORRIDOR TO BE
MAINTAINED AT ALL TIMES.
PROVIDE TEMPORARY PARTITION SUCH
THAT EXISTING EGRESS CAN BE
MAINTAINED WHILE DEMOLISHING CEILING
THIS AREA WOULD NOT BE OCCUPIED
DURING CONSTRUCTION
PASSAGE THROUGH EXISTING CORRIDORTO BE
MAINTAINED AT ALL TIMES.
PROVIDE TEMPORARY PARTITION SUCH
THAT EXISTING EGRESS CAN BE
MAINTAINED WHILE DEMOLISHING CEILINGS
NOTE: WORK TO BE PERFORMED DURING OFF-HOURS OR IN A MANNER THAT DOES
NOT IMPACT THE OPERATIONS OF THE CARDIO PULMONARY SUITE
EXISTING DOOR AND EXIT LIGHT
TO BE MAINTAINED
DURATION: FIRST HALF OF SEQUENCE #2 - SEE G-010.2 FOR MORE INFORMATION.
F102
F102
RECEPTION
102
PASSAGE THROUGH EXISTING
CORRIDOR TO BE MAINTAINED AT
ALL TIMES.
THIS AREA WOULD NOT BE OCCUPIED
DURING CONSTRUCTION
PASSAGE THROUGH EXISTING
CORRIDOR TO BE MAINTAINED AT
ALL TIMES.
NOTE: WORK TO BE PERFORMED DURING OFF-HOURS OR IN A MANNER THAT DOES
NOT IMPACT THE OPERATIONS OF THE CARDIO PULMONARY SUITE
DURATION: SECOND HALF OF SEQUENCE #2 - SEE G-010.2 FOR MORE INFORMATION.
F102
F102
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
CENTRAL WING RENOVATION
7/11/2017 10:30:12 AM15924.00
LS201D.1
INTERIM LIFE LAFETY PLAN
- AREA D
2017
07/11/17PERMIT
RESUBMISSION
VAIL VALLEY
MEDICAL
CENTER
180 S. Frontage
Road West, Vail, CO 81657A
B
C
D
E
1
1/4" = 1'-0"A1 ENLARGED ILSM FLOOR PLAN - AREA A
NORTH
1/4" = 1'-0"C1 ENLARGED ILSM FLOOR PLAN - AREA A
NORTH
F10 EXISTING UPPER MILLWORK TO REMAIN, REPLACE LOWER
CABINETS WITH ADA COMPLIANT 32" BASE CABINETS.
F102 PER 2012 NFPA 101, SECTION 4.6.10.1, "BUILDINGS OR PORTIONS
OF BUILDINGS SHALL BE PERMITTED TO BE OCCUPIED DURING
CONSTRUCTION ONLY WHERE REQUIRED MEANS OF EGRESS
AND REQUIRED FIRE PROTECTION FEATURES ARE IN PLACE
AND CONTINUOUSLY MAINTAINED"
ADDENDUM 1 05/23/17 1
10/25/17