LPC
LPS
T
810-06
SCALE: NONE
AIR FLOW
6"
24" TO 36"
MIN 54"
PITCH
HIGH LIMIT HUMIDISTAT
F&T
PITCH
F&T
ALUMINUM DUCTWORK SEALED
WATERTIGHT WITH SEAMS ON TOP OR AT
LEAST 2" ABOVE BOTTOM OF DUCT
ACCES
S
DOOR
MIN 2"
DDC
COMPATIBLE
MODULATING
VALVE
MINIMUM
DISTANCE TO
FIRST FITTING
NOTES:
1.
2.
INSULATE STEAM PIPING AND CONTROL VALVE.
PROVIDE HUMIDIFIER WITH INSULATED TUBES.
AIR FLOW
SAIL
SWITCH
36"
6"
EQUAL TO DUCT
STATIC PRESSURE
CLASS (INCHES)
TEMPERATURE SWITCH
TO PREVENT VALVE
OPERATION IF HEAT
EXCHANGER IS NOT
HOT
DUCT FLANGE
CONNECTION, SEAL
WATERTIGHT (TYP.)
TO NEARBY
FLOOR DRAIN
TO BUILDING STEAM
CONDENSATE RETURN
SYSTEM
FROM
BUILDING
STEAM
SYSTEM
INSULATION TO FULLY
COVER HUMIDIFER CASING
AND HEAT EXCHANGER
DUCT DRAIN
SUMP
4" DRIP
DUCT HUMIDIFIER (WITH CONDENSATE LIFT FEATURE) PIPING DETAIL
830-12
HOT WATER REHEAT
COIL PIPING DETAIL
NOTE: INSTALL HWS
PIPING ON LEAVING
AIR SIDE OF COIL.
SCALE: NONE
HOT
COIL
WATER
FLOW
AIR
P/T
UNION OR FLANGE
FOR STEEL PIPE
ONLY. NOT
REQUIRED FOR
COPPER (TYP.)
P/T
MANUAL
VENT VALVE
DRAIN VALVE WITH HOSE END
CONNECTION AND CAP
NOTE:
ARRANGE PIPING TO
ALLOW COIL REMOVAL.
3/4"
HWS
HWS MAIN
HWR
CALIBRATED
BALANCING
VALVE
HWR MAIN HWS
~ ~
830-30
RADIANT HEATING CEILING
PANEL PIPING DETAIL
SCALE: NONE
CALIBRATED
BALANCE VALVE
HWR
P/T
SOFT COPPER PIPING
CONNECTIONS BETWEEN
PANELS (TYP.)
2-WAY TCV
HWS
P/T
UNION OR FLANGE FOR
STEEL PIPE ONLY. NOT
REQUIRED FOR COPPER
(TYP.)
RADIANT CEILING PANEL
PROVIDE 2" RIGID WITH
FOIL FACE FIBERGLASS
BATT INSULATION
ABOVE RADIANT PANELS
850-12
EF-16 ROOF EXHAUST FAN DETAIL
SEAL DUCT
PENETRATION
PREFABRICATED
ROOF CURB
SCALE: NONE
PROVIDE DRAIN
AT BOTTOM OF
FAN SCROLL
A"Ø
15'-0" TOTAL
STACK HEIGHT
ISOLATION
PER SPECS.
EXHAUST FAN
APPROX. OUTLET
SIZE: C"XD"
B"Ø
PROVIDE 3-POINT
GUY WIRE
SUPPORT AT 8'-0"
& 13'-0" ABOVE
ROOF BRACKET UPPER
STACK TO DISCHARGE
DUCT
FLEXIBLE CONNECTION
DUCT SUPPORT
36"
SEE ARCH.
FOR ROOF
DETAILS
1" GAP ALL
AROUND
891-1
DUCT ROOF PENETRATION DETAIL
SCALE: NONE
PREFABRICATED
INSULATED CURB
DUCT
ROOF
COUNTERFLASHING
ROOFING SYSTEM.
SEE ARCH.
EXTERIOR DUCT JOINT PER SMACNA
891-5
ROOF DUCT SUPPORT DETAIL, ROUND
3/16" WELDED SOLE
PLATE AND
ATTACHMENT
BOLTS
SCALE: NONE
DIAGONAL BRACING
DUCT INSULATION AND
JACKETING PER
SPECIFICATIONS
16 GA. SHEET
METAL HOLD DOWN
STRAP SECURED
W/SHEET METAL
SCREW
FASTENER
ANCHOR BOLTS, LOCATE
IN DECK AS REQUIRED BY
STRUCTURAL ENGINEER
CHANNEL STRUT.
HOT DIPPED
GALVANIZED AFTER
FABRICATION
PRE-FABRICATED
EQUIPMENT RAIL
SUPPORT ANCHOR TO
STRUCTURE PER
MFR'S INSTRUCTIONS
RE: ARCH. FOR
ROOFING DETAIL AND
WATER PROOFING
REPAIR ALL FIELD CUTS AND
WELDS WITH ZINC RICH
PAINT, FINISH WITH TWO
COATS OF OUTDOOR FINISH
PAINT AS SELECTED BY
ARCHITECT
891-11
DUCT PASSING UNDER BEAM
SCALE: NONE
RADIUS
BEAM
FLOOR
910-1
FIRE DAMPER
INSTALLATION DETAIL
SCALE: NONE
MOUNTING/RETAINING ANGLES
INSTALLED PER MFR'S
INSTALLATION INSTRUCTIONS
NOTE:
VERTICAL TYPE FIRE DAMPER SHOWN. FOR
HORIZONTAL TYPE, TURN ASSEMBLY 90° AND
PROVIDE W/NEGATOR CLOSURE SPRING.
AIR FLOW
PROVIDE SLEEVE GAUGE
STEEL FIRE DAMPER
SLEEVE, THICKNESS PER
MFR'S INSTALLATION
INSTRUCTIONS
FOR HORIZONTAL FIRE DAMPERS
LOCATE DUCT ACCESS DOOR
FROM ABOVE TO ACCESS
NEGATOR CLOSURE SPRING
BREAKAWAY
JOINTS, BOTH
SIDES OF DAMPER
SLEEVE
PROVIDE MULTIPLE
ACCESS DOORS FOR
DUCTWORK 60" OR WIDER
OR ON SIDE OF DUCT
WHEN REQUIRED TO
PROVIDE ADEQUATE
ACCESS TO FIRE DAMPER
FIRE DAMPER
INSTALLATION NOTE:
M.C. SHALL PROVIDE & INSTALL
ADDITIONAL STEEL MULLIONS PER
MFR INSTALLATION INSTRUCTIONS
FOR MULTIPLE FIRE DAMPER
ASSEMBLIES.
MAINTAIN EXPANSION CLEARANCE
PER MFR'S INSTALLATION
INSTRUCTIONS
910-2
DUCT TAKE-OFF DETAIL
RETURN OR
EXHAUST AIR
FLOW
SCALE: NONE
SUPPLY AIR FLOW
RETURN OR
EXHAUST AIR
FLOW
SUPPLY AIR FLOW
BRANCH DUCT
45° MAXIMUM
A
MAIN DUCT
910-7
SPLITTER DUCT DETAIL
C/D (AS SHOWN ON PLAN)
E/F (AS SHOWN ON PLAN)
TURNING VANES (TYP.)
SCALE: NONE
SEE PLAN FOR SIZES.
NOTE:
TRANSITION IF
REQUIRED
E/B
C/B
E C
TRANSITION IF REQUIRED
A/B (AS SHOWN ON PLAN)
TRANSITION TO E+C/B
910-9
MEDIUM PRESSURE
MVD DETAIL
GROUND END TO 1/2"
SQUARE FOR WRENCH
ADJUSTMENT
3/4" THREADED ROD
SCALE: NONE
12 GA. PLATE
D
GASKET (NEOPRENE)
NUT
WASHER
LOCKNUT
D-1"
LOCATE DUCT ACCESS
DOOR TO SERVICE INTERNAL
LINKAGE, ACTUATOR,
AND/OR CONTROLS AS
REQUIRED.
WHERE APPLICABLE,
DUCT SMOKE DETECTOR.
LOCATE ON SAME SIDE
OF DAMPER AS ACCESS
DOOR.
910-11
FIRE/SMOKE DAMPER
INSTALLATION DETAIL
NOTES:
1. INSTALL ASSEMBLY IN STRICT ACCORDANCE WITH MANUFACTURER'S
INSTRUCTIONS.
2. PROVIDE AND INSTALL ADDITIONAL STEEL MULLIONS FOR MULTIPLE FIRE/SMOKE
DAMPER ASSEMBLIES.
3. PROVIDE APPROPRIATE DUCT TRANSITIONS BETWEEN SCHEDULED DAMPER SIZE
AND INDICATED DUCT SIZE.
4. PROVIDE RED IDENTIFICATION PAINT ON EXTERIOR OF DAMPER SLEEVE.
SCALE: NONE
MOUNTING/RETAINING ANGLES
INSTALLED PER MFR'S INSTALLATION
INSTRUCTIONS
ACTUATOR OUT
OF AIRSTREAM
MANUAL RESET
THERMAL
SWITCH
FIRE/SMOKE
DAMPER
PROVIDE MULTIPLE ACCESS DOORS FOR
DUCTWORK 60" OR WIDER OR ON SIDE
OF DUCT WHEN REQUIRED TO PROVIDE
ADEQUATE ACCESS TO FIRE DAMPER
BREAKAWAY JOINTS, BOTH
SIDES OF DAMPER SLEEVE
MAINTAIN EXPANSION
CLEARANCE PER
MFR'S INSTALLATION
INSTRUCTIONS
932-11
AIR DEVICE WITH
RECTANGULAR NECK &
ROUND RUNOUT BOOT DETAIL
SCALE: NONE
CEILING
NOTE:
REGISTERS AND GRILLES SIMILAR.
SHEET METAL
DUCTWORK,
INSULATED
PER
SPECIFICATIONS
BELLMOUTH TYPE SPIN-IN
WITH BUTTERFLY TYPE MVD,
EXTEND QUADRANT HANDLE
THRU INSULATION AND SEAL
AROUND INSULATION.
INSULATE RUN-OUT PER
SPECIFICATIONS
STAINLESS STEEL WORM
GEAR CLAMP ON BOTH
THE FLEX DUCT JACKET
AND INNER CORE.
T-BAR OR LAY-IN
FRAME FOR
HARD
CEILING.
LAY-IN AIR
DEVICE
FLEXIBLE DUCT (MAX. 6'-0")
SUPPORT @ 3'-0" O.C.,
INSULATED PER SPECIFICATIONS
SUPPORT FROM OVERHEAD
STRUCTURE
EXTERNALLY
INSULATED
SHEET METAL
PLENUM BOX OVER
GRILLE PER
SPECIFICATIONS
ALTERNATE
OPTIONAL
CONNECTION
METHOD AT TOP OF
PLENUM
SHEET METAL
DUCT WHERE
INDICATED ON
PLANS
932-12B
ROUND NECK
AIR DEVICE DETAIL
SCALE: NONE
LONG RADIUS
FLEXIBLE DUCT (MAX. 6'-0")
SUPPORT @ 3'-0" O.C.
INSTALLED PER
SPECIFICATIONS
NOTE:
CEILING DIFFUSER SHOWN;
REGISTERS AND GRILLES
SIMILAR.
CEILING
LAY-IN AIR DEVICE
SHEET METAL
DUCTWORK,
INSULATED PER
SPECIFICATIONS.
BELLMOUTH TYPE SPIN-
IN WITH BUTTERFLY
TYPE MVD, EXTEND
QUADRANT HANDLE
THRU INSULATION AND
SEAL AROUND
INSULATION.
T-BAR OR LAY-IN
FRAME FOR HARD
CEILING.
SUPPORT FROM
OVERHEAD
STRUCTURE
INSTALL RUN-OUT
PER
SPECIFICATIONS
STAINLESS STEEL WORM
GEAR CLAMP ON BOTH
THE FLEX DUCT JACKET
AND INNER CORE.
HARD CEILING INSTALLATIONS:
1.
2.
PROVIDE LAY-IN FRAME TO ALLOW AIR DEVICE TO BE
REMOVED.
LOCATE MVD TO BE ACCESSIBLE. IF SPIN-IN IS NOT
ACCESSIBLE PROVIDE A REMOTE OPERATED MVD.
HARD CEILING INSTALLATIONS:
1.
2.
PROVIDE LAY-IN FRAME TO ALLOW AIR DEVICE TO BE
REMOVED.
LOCATE MVD TO BE ACCESSIBLE. IF SPIN-IN IS NOT
ACCESSIBLE PROVIDE A REMOTE OPERATED MVD.
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP, P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
CENTRAL
WING
RENOVATION
3/10/2017
9:34:01 AM
180 S. Frontage
Road
West,
Vail, CO 81657
15924.00
M-401.1
MECHANICAL DETAILS
2017
03/10/17
PERMIT VAIL
VALLEY
MEDICAL
CENTER
06/30/17