HomeMy WebLinkAboutB17-0092_P-001-1_1508947713.pdfPLUMBING LEGEND
SYMBOL DESCRIPTION ABBR. DESCRIPTION
ACID RESISTANT WASTE PIPING (ABOVE FLOOR IN BUILDING)
DOMESTIC COLD WATER PIPING
DOMESTIC HOT WATER PIPING
DOMESTIC HOT WATER CIRC. PIPING
SOFTENED DOMESTIC COLD WATER PIPING
SOFTENED DOMESSTIC HOT WATER PIPING
DOMESTIC HOT WATER PIPING @ TEMPERATURE
SHOWN
SURFACE CLEANOUT
FLOOR CLEANOUT
LINE CLEANOUT
FIXTURE OR DRAIN P-TRAP
AREA DRAIN
FLOOR SINK (SQUARE GRATE)
ROOF DRAIN OR OVERFLOW DRAIN
GAS PRESSURE REDUCING VALVE
ATMOSPHERIC VACUUM BREAKER
ACID RESISTANT VENT PIPING
WASTE PIPING (ABOVE FLOOR IN BUILDING)
WASTE PIPING (BELOW FLOOR IN BUILDING)
WALL CLEANOUT
CLEANOUT TEE
ABBR.SYMBOL
VENT PIPING
FLOOR DRAIN (ROUND GRATE)
HW
HWC
C-SW
140° HW
V
H-SW
AV
W
W
AW
AW
CW
FS
RD / OD
VB
AV
W
W
AW
AW
GD
IW
S
ST
SSD
SD
SD
OD
OD
A
G G
ACID RESISTANT WASTE PIPING (BELOW FLOOR IN BUILDING)
IW
S
ST
SSD
SD
GD
SD
OD
OD
A COMPRESSED AIR
GREASE DRAIN (WASTE LINE TO GREASE INTERCEPTOR)
INDIRECT WASTE PIPING
SANITARY SEWER PIPING (OUTSIDE BUILDING)
STORM SEWER PIPING (BELOW GRADE OUTSIDE BUILDING)
SUB-SURFACE DRAIN PIPING
OVERFLOW DRAIN PIPING (ABOVE FLOOR IN
BUILDING)
STORM DRAIN PIPING (ABOVE FLOOR IN
BUILDING)
STORM DRAIN PIPING (BELOW FLOOR IN
BUILDING)
OVERFLOW DRAIN PIPING (BELOW FLOOR IN BUILDING)
FCO
WCO
COT
AD
LCO
FD
SCO
BFP
SA
GC
FC
WH
HB
YH
MH
CI
MANHOLE
DOUBLE CHECK BACKFLOW PREVENTER
SHOCK ARRESTOR W / ISOLATION VALVE
GAS SHUT-OFF VALVE
STOP AND DRAIN VALVE
HOSE BIBB
HWC BALANCING VALVE
CAST IRON
WALL HYDRANT
YARD HYDRANT
INVERT ELEVATION
CATCH BASIN
POLYVINYL CHLORIDE
VITRIFIED CLAY PIPE
VENT THRU ROOF
VCP
CB
VTR
IE
PVC
SW
SW
140°
FUEL OIL PIPING LEGEND
SYMBOL DESCRIPTION ABBR. DESCRIPTION
FUEL OIL SUPPLY PIPING
FUEL OIL RETURN PIPING
FUEL OIL FILL PIPING
FUEL OIL VENT PIPING
FUEL OIL OVERFLOW PIPING
DAY TANK PUMP OUT PIPING
PRESSURE RELIEF VALVE
VACUUM GAUGE W/ COCK VALVE
FUEL OIL HAND PUMP
GENERATOR FUEL OIL RETURN PIPING
PRESSURE GAUGE W/ COCK VALVE
FUSIBLE LINK VALVE
ABBR.SYMBOL
GENERATOR FUEL OIL SUPPLY PIPING
FOR
FOF
FOV
DPO
GFOS
FOO
GFOR
FOS
FOR
FOF
FOV
DPO
GFOS
FOO
GFOR
FOS
V
F
P
FIRE PROTECTION LEGEND
SYMBOL DESCRIPTION ABBR. DESCRIPTION
FIRE SERVICE PIPING
FIRE SPRINKLER PIPING
WET STANDPIPE
O.S.&Y. VALVE W/ TAMPER SWITCH
FLOW SWITCH
POST INDICATOR VALVE
NEW SPRINKLER HEAD
EXISTING SPRINKLER HEAD
DRY SPRINKLER HEAD (SHAFT)
FIRE HOSE CABINET
FIRE VALVE CABINET
FIRE DEPARTMENT CONNECTION
RELOCATED SPRINKLER HEAD
SIDEWALL SPRINKLER HEAD
ABBR.
F
SYMBOL
FIRE HYDRANT
AUTOMATIC FIRE SPRINKLER
FS
WSP
PIV
FH
FS
FDC
F
FS
N20
FHC
FVC
A/S
D24
LABORATORY / MEDICAL SERVICES LEGEND
SYMBOL DESCRIPTION ABBR. DESCRIPTION
LABORATORY COMPRESSED AIR PIPING
OXYGEN PIPING
VACUUM PIPING
NITROUS OXIDE PIPING
NITROGEN PIPING
MEDICAL AIR PIPING
CARBON DIOXIDE
OXYGEN SERVICE OUTLET
VACUUM SERVICE INLET
NITROGEN SERVICE OUTLET
NATURAL GAS SERVICE OUTLET
LABORATORY/MEDICAL AIR SERVICE OUTLET
ZONE VALVE BOX
MEDICAL GAS OUTLET
AREA ALARM PANEL
MASTER ALARM PANEL
DEIONIZED WATER PIPING
HYDROGEN PIPING
LIQUID NITROGEN PIPING
NATURAL GAS PIPING
WASTE ANESTHESIA GAS DISPOSAL INLET
NITROUS OXIDE SERVICE OUTLET
ABBR.
02
SYMBOL
WASTE ANESTHESIA GAS DISPOSAL
CARBON DIOXIDE SERVICE OUTLET
VAC
N2O
N
CO2
WAGD
MA
DI
H
NL
LA
G
O2
ZVB
MGO
AAP
MAP
VAC
N
WAGD
DI
H
NL
LA
G
N20
MA
CO2
GENERAL LEGEND
SYMBOL DESCRIPTION ABBR. DESCRIPTION
NEW
SECTION DESIGNATION
SECTION DRAWN ON THIS SHEET
SECTION CUT ON THIS SHEET
RISER DIAGRAM NUMBER
SHEET RISER IS DRAWN ON
EQUIPMENT UNIT IDENTIFICATION
CAP END OF PIPE
PITCH DOWN IN DIRECTION OF ARROW
UNION OR FLANGE
CONCENTRIC PIPE REDUCER
ECCENTRIC PIPE REDUCER
PRESSURE AND/OR TEMPERATURE RELIEF VALVE
PLUG VALVE
GATE VALVE
VERTICAL PIPE VALVE
DIFFUSER IDENTIFICATION
DIFFUSER NECK DIAMETER
DIFFUSER CFM
EXISTING
PIPE ANCHOR
PIPE ALIGNMENT GUIDE
ABBR. SYMBOL
EQUIPMENT UNIT NUMBER
PRESSURE REDUCING VALVE
(E)
(N)
(R)
PTRV
(F)
DIA
WAD
NIC
AFF
GC
MC
EC
RELOCATED
FUTURE
POINT OF CONNECTION, NEW TO EXISTING
DIRECTION OF FLOW IN PIPE
DUCTWORK, PIPING AND EQUIPMENT TO BE REMOVED
DIAMETER
ABOVE FINISHED FLOOR
WALL ACCESS DOOR
ELECTRICAL CONTRACTOR
NOT IN CONTRACT
GENERAL CONTRACTOR
PRV
GLV
BFV
BV
CV
P/T
STRAINER W/ BLOWDOWN
GLOBE VALVE
BUTTERFLY VALVE
BALL VALVE
CHECK VALVE
SOLENOID VALVE
PRESSURE / TEMPERATURE TAP
BUTTERFLY SOLENOID VALVE
FLEXIBLE PIPE CONNECTOR
HOSE END DRAIN VALVE
STRAINER
CEILING ACCESS PANEL
PRESSURE GAUGE
PUMP
THERMOMETER
SIGHT GLASS
C.A.P.
TB
MECHANICAL CONTRACTOR
#
UNIT
M-X
X
X.X X.X
X
GV
THRUST BLOCK
XX
P/T
DETAIL SHEETS PLAN SHEETS
XX
NATURAL GAS
PIPING
(Not all symbols listed below are used on these drawings)
(Not all symbols listed below are used on these drawings)
(Not all symbols listed below are used on these drawings)
(Not all symbols listed below are used on these drawings)
(Not all symbols listed below are used on these drawings)
NECK
CFMX
POINT OF DISCONNECTION (DEMO)2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP,
P.C.
Sheet Title:
Revisions Date
Sheet Information
Project Information
Issuance
Consultant
CENTRAL WING RENOVATION
7/10/2017 2:00:41 PM15924.00
P-001.1
PLUMBING LEGENDS &
NOTES
07/11/17PERMIT
RESUBMISSION
EAST WING
ADDITION
180 S Frontage Rd W, Vail, CO 81657PLUMBING NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
CONTRACTOR SHALL NOT SHUT-OFF/PUT OUT OF SERVICE ANY
SYSTEMS/SERVICES WITHOUT FIRST COORDINATING WITH OWNER.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTING
CONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK AND SHALL NOTIFY
THE ARCHITECT/ENGINEER OF ANY DISCREPANCIES FOR RESOLUTIONS.
THIS CONTRACTOR SHALL COORDINATE LOCATIONS OF PIPING WITH OTHER
TRADES AND ADVISE ARCHITECT/ENGINEER OF ANY POSSIBLE CONFLICTS.
VERIFY EXACT LOCATIONS, ELEVATIONS AND DIMENSIONS OF STRUCTURAL
MEMBERS AND OPENINGS.
SEE SPECIFICATIONS FOR WATER HAMMER ARRESTOR SIZING. ALL FLUSH
VALVES AND SOLENOID OPERATED EQUIPMENT SHALL HAVE A WATER
HAMMER ARRESTOR.
SEE PLUMBING FIXTURE SCHEDULE FOR PIPE SIZING TO INDIVIDUAL
PLUMBING FIXTURES.
ALL EXISTING FIXTURES AND EQUIPMENT TO BE REMOVED SHALL HAVE ALL
ASSOCIATED PIPING CONTROLS, HANGERS, SUPPORTS AND ANY
MISCELLANEOUS ASSOCIATED SERVICE OR PART REMOVED COMPLETELY.
ALL MEDICAL GAS PIPING SHALL HAVE TOP TAKE-OFFS WHENEVER POSSIBLE.
REFER TO ARCHITECTURAL DRAWINGS FOR ROOF PENETRATION DETAILS.
REFER TO ARCHITECTURAL DRAWINGS FOR FIXTURE ELEVATIONS AND
LOCATIONS.
SEE ARCHITECTURAL CONSTRUCTION DOCUMENTS FOR DIMENSIONED
LOCATION OF PLUMBING FIXTURES AND WALLS.
PROVIDE CLEANOUTS IN ACCESSIBLE LOCATIONS PER THE PROJECT
SPECIFICATIONS AND LOCAL PLUMBING CODES.
FOUNDATION PLUMBING NOTES:
1.
2.
3.
4.
CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFICATION OF ALL EXISTING
CONDITIONS PRIOR TO COMMENCEMENT OF ANY WORK.
COORDINATE WORK WITH ALL TRADES.
SEE ARCHITECTURAL CONSTRUCTION DOCUMENTS FOR EXACT LOCATION OF
PLUMBING FIXTURES AND WALLS.
PROVIDE A WALL CLEANOUT ON ALL VERTICAL VENT PIPING SERVING BELOW
GRADE HORIZONTAL WASTE PIPING.
FIRE PROTECTION PLAN NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
FURNISH ALL LABOR, MATERIALS, EQUIPMENT AND SERVICES
NECESSARY FOR THE INSTALLATION OF A COMPLETE AND PROPERLY
FUNCTIONING FIRE PROTECTION SYSTEM.
THE FIRE PROTECTION WORK INVOLVES ENGINEERING AND DESIGN BY
THE CONTRACTOR TO DETERMINE THE EXTENT OF NEW WORK AND
THE MODIFICATION AND EXTENSION OF EXISTING SYSTEMS TO
PROVIDE FULL COVERAGE TO THE PROJECT AREA SHOWN ON THESE
AND THE ARCHITECTURAL PLANS.
THE INFORMATION PRESENTED ON THESE DRAWINGS IS
DIAGRAMMATIC. IT DOES NOT NECESSARILY REPRESENT ALL ELBOWS,
OFFSETS, HANGERS, ETC., REQUIRED FOR A COMPLETE WORKING
SYSTEM.
ALL FIRE PROTECTION SYSTEMS INSTALLED SHALL BE IN ACCORDANCE
WITH NFPA-13, 14, 20, ETC. AND LOCAL BUILDING CODES AND
ORDINANCES.
FIRE PROTECTION CONTRACTOR SHALL COORDINATE THE LOCATION
OF ALL NEW FIRE PROTECTION EQUIPMENT AND PIPING WITH ALL
OTHER TRADES PRIOR TO SUBMITTAL OF SHOP DRAWINGS AND
SYSTEM INSTALLATION, SO AS NOT TO INTERFERE WITH THE ROUTING
OF NEW DUCTWORK, PLUMBING PIPING, ETC.
PROVIDE ALL FITTINGS, RISER NIPPLES, ARM-OVERS, HANGERS, ETC.
TO MAINTAIN CONFORMANCE WITH APPLICABLE STANDARDS AND TO
POSITION THE SPRINKLERS IN THE PROPER LOCATIONS.
SEAL ALL PIPE PENETRATIONS THROUGH FIRE RATED WALLS AND
CEILINGS WITH FIRE STOPPING MATERIALS AS REQUIRED.
FOR REMODEL AREAS NEW SPRINKLERS SHALL MATCH EXISTING
SPRINKLERS.
PROVIDE WORKING DRAWINGS AND HYDRAULICALLY CALCULATE THIS
FIRE SPRINKLER SYSTEM PER NFPA-13 WHERE REQUIRED BY THE
LOCAL AUTHORITY HAVING JURISDICTION.
PROVIDE FIELD COORDINATION OF PIPING AND SPRINKLER
INSTALLATIONS WITH DUCTWORK, LIGHTS, SMOKE DETECTORS,
DIFFUSERS, ETC.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
1.
2.
3.
4.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
10/25/17