HomeMy WebLinkAboutB17-0092_S-200_1498849140.pdf4 1/2"
1'-0"
3'-10" 1'-4 1/2"
5'-2 1/2"
1'-1" 1'-0" 6"
2"
7 1/2" EXISTING
CONCRETE BEAM
SAW CUT OFF BOTTOM OF
EXISTING BEAM AFTER
COMPLETE INSTALLATION OF
STEEL ABOVE. SEE PLAN FOR
LENGTH OF SAW CUT.
(2)-C15x33.9x23'-0
CENTER CHANNEL
BETWEEN EXSITING
COLUMNS
3/4" DIA. THROUGH
BOLT AT 12" O.C. WITH
1/4"x3"x3" PLATE
WASHER EACH SIDE
1 1/2" DIA. OVER SIZED
HOLE. PRESURE
GROUT SOILD AFTER
INSTALLATION OF
THROUGH BOLT
1/4
NUT TO
WASHER
1/4 1.5
EA. SIDE OF
WASHER TO
C15
LEVEL 2 FFE
LEVEL 1 PHARMACY
CEILING
2901 Blake Street, Suite 100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP, P.C.
Sheet Title:
Revisions Date No.
Sheet Information
Project Information
Issuance Date
Consultant
CENTRAL
WING
RENOVATION
PERMIT 03/10/17
MM JOB #: PRINCIPAL:
EOR: PROJECT
MANAGER:
DESIGNERS:
DATE
PRINTED:
FILE PATH:
3/9/2017
3:59:57 PM
C:\Proj\16.0188 - VVMC
CENTRAL
ENABLING - RS16_mrenes.rvt
C:\Proj\16.0188 - VVMC
CENTRAL
ENABLING -RS16_mrenes.rvt
16.0188.S.01
S-200
VAIL
VALLEY
MEDICAL
CENTER
180 S. Frontage
Road W. Vail, CO 81656
FRAMING DETAILS
Michael
Renes
Michael
Renes
Shane
McCormick
16.0188.S.01
Shane
McCormick 3/4" = 1'-0" 1 SAW CUT THROUGH EXSITING BEAM
06/30/17