HomeMy WebLinkAboutB17-0092_S-200_1503950595.pdf3/16 2-12
1/4 2-12
4" EXISTING
SPANDREL BEAM
1'-0"
SAW CUT OFF BOTTOM OF EXISTING
BEAM AFTER COMPLETE
INSTALLATION OF
STEEL CHANNEL AND EPOXY BOLTS
ABOVE. INSTALL COVER PLATE
AFTER SAW CUT OF EXISTING BEAM.
SEE PLAN FOR LENGTH OF SAW CUT.
1'-1" 2"
(2)-C15x33.9x23'-0
CENTER CHANNEL
BETWEEN EXISTING
COLUMNS
PL 1/4" CONT BELOW OPENING
4 1/2"
1'-0"
1'-4 1/2"
4"
3/4" DIA EPOXY ANCHORS @ 20" OC
(HILTI HIT-HY 200 WITH 4 3/4" EMBED)
STAGGER ANCHORS ON OPPOSITE END OF
EXISTING SPANDREL BEAM
LEVEL 2 FFE
PLATE WASHER 1/4"x4x4. FIELD WELD
BOLT HEAD TO PLATE WASHER WITH
3/16" WELD ALL AROUND
3/16 1"
WELD ALL
FOUR SIDES
APPROXIMATE LINE LOCATION
2'-8"
1'-0"
3'-8" 8" 2" NOTCH
EXISTING CONCRETE BEAM
12x64 WITH (3) #8 T&B AND
#3 TIES AT 10" OC. FIELD
VERIFY ALL LOCATIONS OF
EXISTING REINFORCING
CEILING
NEW 5" DIA HOLE. CORE THROUGH EXISTING BEAM. PRIOR TO
CORING OF EXISTING BEAM, GPR (GROUND PENETRATING
RADAR) EXISTING BEAM TO LOCATED REINFORCING STEEL. FIELD
LOCATED HOLE AROUND EXISTING REINFORCING STEEL. DO NOT
DAMAGE EXISTING REINFORCING STEEL
F.V.
3'-1 1/2"
FFE = 61'-4" 2'-8"
1'-0"
10" 8" CEILING
5" DIA HOLE
APPROXIMATE LINE LOCATION
HDG PL 3/16x3
PIPE CLAMP AND CONNECTION
TO FRAME BY OTHERS
HDG HSS 3/16x3x3
WITH 1/4" CAP PLATE
DUCT
SEE MECHANICAL
HDG L4x4x3/16x2'-0
T&B
1
1
1/8
1
1/8 1
TYP. ANGLE
TO
EXISTING
METAL
STUD
1/8 2
1/8 2
1/4
EXTERIOR VENEER
PROVIDE ONE FRAME
EACH SIDE OF DUCT
FIELD VERIFY EXISTING METAL STUD SPACING
2901 Blake Street, Suite
100
Denver, CO 80205
303.861.8555
Denver
1
A
B
C
D
E
2 3 4 5 6
A
B
C
D
E
1 2 3 4 5 6
DPA Project:
Sheet Number:
COPYRIGHT - DAVIS PARTNERSHIP, P.C.
Sheet Title:
Revisions Date No.
Sheet Information
Project Information
Issuance Date
Consultant
CENTRAL
WING
RENOVATION
PERMIT
RESUBMISSION
07/11/17
MM JOB #: PRINCIPAL:
EOR: PROJECT
MANAGER:
DESIGNERS:
DATE
PRINTED:
FILE PATH:
7/10/2017
10:27:14 AM
C:\Proj\16.0188 - VVMC
CENTRAL
ENABLING - RS17_jschmidt.rvt
C:\Proj\16.0188 - VVMC
CENTRAL
ENABLING -RS17_jschmidt.rvt
16.0188.S.01
S-200
VAIL
VALLEY
MEDICAL
CENTER
180 S. Frontage
Road
West,
Vail, CO 81657
FRAMING DETAILS
Michael
Renes
Michael
Renes
Shane
McCormick
16.0188.S.01
Shane
McCormick 3/4" = 1'-0" 1 SAW CUT THROUGH EXSITING BEAM
1/2" = 1'-0" 2 FRAMING DETAIL
1/2" = 1'-0" 3 FRAMING DETAIL
3/4" = 1'-0" 4 DUCT SUPPORT DETAIL
1
1
1
1
ADDENDUM 2 06.12.2017 1
7/11/17
08/28/17