HomeMy WebLinkAboutB16-0222_E101 Lower Level_1478902144.pdfFD
TD
MT
M
D
DT
M
M
M
MT
M
D
D
DF
D
D
M
TD
DD
TV
TV
TV
D
D
D
D
D
1/4"=1'-0"
E101
LOWER
LEVEL
Sheet
Scale
04.08.2016
1414
Project
Date
1414 Moraine Drive
Lot 7 Filing 1
Dauphinais Moseley
Vail, Colorado
1414
Moraine
Drive
Revision/Issue
Project Name and Address
General Contractor
GILLETTE LLC
CONSTRUCTION
POST OFFICE BOX 5821 888.719.1123
VAIL COLORADO 81658 gillettellc.com
05.31.2016 Permit Submittal
06.09 2016 Load Calculations
LOWER NORTH BED
GUEST ENTRY
GARAGE
POWDER
KITCHEN
DINING
LIVING
MAIN ENTRY
MASTER
PANTRY
1
2
Switch All
Bedroom Outlets
1
2
Switch All
Bedroom Outlets
FAMILY
Switch with Guest Living
Locate Sub Panels Here
600 Amp Service
System: 120/240V
Square Feet: 4752
1 Steam Shower: 20160 VA (Line-Line)
3 Dishwasher: 5400 VA (Line-Line)
3 Disposal: 5400 VA (Line-Line)
2 Microwave: 3600 VA (Line-Line)
5 Fridge: 8625 VA (Line-Line)
1 Coffee: 1800 VA (Line-Line)
1 Hood: 1725 VA (Line-Line)
3 Clothes Washers: 5400 VA (Line-Line)
2 Spas: 13800 VA (Line-Line)
Dryer: 21600 VA
COOKING APPLIANCES:
Range: 7200 VA
: 4800 VA
Heat (Line-Line): 48000 VA
Cool (Line-Line): 2300 VA
HVAC (Line-Neutral): 0 VA
Other Motors (Line-Line): 0 VA
Other Motors (Line-Neutral): 0 VA
Largest Motor (Line-Neutral): 0 VA
Optional Calculation Details-BETA:
General Load (Lights, SABCs, Laundry, Appliances, Ranges,
Dryers, Water Heaters, other Motors) Total: 124266 VA
General Load Net: + 55706 VA+
General Neutral Net: ->31195 VA<-
HVACLoad: +31200 VA+
Total Load: 86906 VA / 240 = 362 Amps
Neutral Load: 31195 VA / 240 = 130 Amps
OPTIONAL CALCULATION:
Demand Load: 86906 VA
Minimum Current: 362 Amps
Standard or Minimum Breaker (240.6): 400 Amps
Copper Service Conductor (T310.15(B)(6/7)): 400 kcmil
Aluminum Service Conductor (T310.15(B)(6/7)): 600 kcmil
Copper GEC-Service (250.66): 1/0 AWG
Aluminum GEC-Service (250.66): 3/0 AWG
Neutral Load (220.61): 31195 VA
Neutral Current: 130 Amps
Copper Neutral Conductor (250.24(C)(1)): 3/0 AWG
Aluminum Neutral Conductor (T310.15(B)(6/7)): 2/0 AWG
Copper EGC-Feeder (250.122): 3 AWG
Aluminum EGC=Feeder (250.122): 1 AWG
Switch with Upper Hall