HomeMy WebLinkAboutB16-0266_A003_1491490897.pdfDW
REF.
3'-10"
6'-8"
FIRE ALARM AUDIO/VISUAL DEVICES
DOORBELL DISABLE
SWITCH
FINISHED FLOOR
GUESTROOM SIDE OF DOOR
SYMBOL DEVICE REMARKS
BUTTON FOR DOOR SIGNAL
2-GANG BOX WITH
TRANSFORMER FOR DOOR BELL
DOORBELL DISABLE SWITCH
HORN STROBE (VISUAL & AUDIBLE) FOR DOOR
SIGNAL (BEDROOMS)
REMOTE VISUAL STROBE DOOR SIGNAL
(BATHROOMS)
OUTSIDE DOOR ON STRIKE SIDE, +48" AFF
FACTORY LABEL ON COVER PLATE
MOUNT IN SOFFIT OR CABINET - PROVIDE ACCESS
PROVIDE KEY SWITCH IN CORRIDOR ABOVE THE PUSH
BUTTON TO TURN ON/OFF THE REQUIRED DOORBELL
KIT. GANG WITH LIGHT SWITCH "DOORBELL DISABLE
SWITCH" PLAQUE ON WALL BESIDE EVERY ENTRY DOOR,
ROOM SIDE.
MOUNT 80" AFF
MOUNT 80" AFF
HI-CF NOTES:
PROVIDE ASSISTIVE LISTENING DEVICES IN THE REQUIRED NUMBER OF ROOMS PER BUILDING CODES AND DOJ 2010 ADA
STANDARDS FOR ACCESSIBLE DESIGN.
1. DISTRIBUTE HEARING IMPAIRED ROOMS AMONGST ALL CLASSES OF ROOMS INCLUDING SUITES.
2. PLAQUES (EXCEPT AS NOTED): PROVIDE AS INDICATED. PLAQUES SHALL BE BLACK PHENOLIC WITH 1/4" WHITE ENGRAVED LETTERS.
3. PROVIDE TELEPHONE WITH VOLUME CONTROL AND SIGNAL NOTIFICATION LIGHT.
4. LOCATE TELEPHONES WITHIN 48" OF AN ELECTRICAL OUTLET.
5. PROVIDE EDWARDS 7005-65 HOTEL ROOM ANNUNCIATOR KIT WITH ADDITIONAL VISUAL STROBE AT EACH BATHROOM AND ADDITIONAL HORN
STROBE AT EACH BEDROOM IN SUITES IN HI ROOMS.
DEVICES FOR THE HEARING IMPAIRED COMPLIANT FEATURES:
J
PB
J T
DDS
H
A A
SYMBOL DEVICE REMARKS
SMOKE DETECTOR
ELECTRICAL PANEL
SMOKE DETECTOR WITH STROBE
REMOVE EXISTING BATTERY POWERED SMOKE DETECTOR
EXISTING ELECTRICAL PANEL
PROVIDE SMOKE DETECTOR WITH STROBE
HI NOTES:
PROVIDE FIRE ALARM SYSTEM UPGRADES IN GUESTROOMS WITH HEARING IMPAIRED COMPLIANT FEATURES PER BUILDING CODES AND DOJ
2010 ADA STANDARDS FOR ACCESSIBLE DESIGN.
1. GUESTROOM FIRE ALARM (FA) ADDRESSABLE ANNUNCIATING DEVICES ARE CONNECTED TO EXISTING BUILDING FA PANEL IN THE HOTEL
LOBBY. THEY ARE ACTIVATED BY EXISTING HARD-WIRED SMOKE DETECTORS, FA PULL STATION AND OTHER EXISTING SIGNALING
DEVICES LOCATED IN GUEST BUILDING CORRIDORS AND STAIRWELLS.
2. GENERAL CONTRACTOR TO COORDINATE INSTALLATION OF NEW FA DEVICES WITH FIRE ALARM SYSTEMS VENDOR IF REQUIRED.
3. FIRE ALARM SYSTEMS VENDOR TO PROVIDE ADDITIONAL DOCUMENTATION REQUIRED BY LOCAL MUNICIPALITY / AUTHORITY HAVING
JURISDICTION (AHJ) AND SECURE REQUIRED FA PERMITS.
4. SMOKE DETECTORS (HARDWIRED WITHIN ROOM):
A - REMOVE EXISTING BATTERY POWERED SMOKE DETECTOR (SD)
B - PROVIDE SDS WITH BATTERY BACK-UP (EXISTING SYSTEM COMPATIBLE) HARD-WIRED TO 120V POWER. SDS TO HAVE 520HZ, LOW
FREQUENCY SOUNDER BASE, WHERE REQUIRED BY JURISDICTION PER NFPA 72.
C - PROVIDE ADDITIONAL SDS DEVICES PER PLAN, INTER-CONNECTED TO PROVIDE NOTIFICATION THROUGHOUT GUESTROOM UNIT.
5. IF EXISTING FIRE ALARM DEVICES OR SMOKE DETECTORS ARE NOT WITHIN VISUAL SIGHT OF BED PILLOW, FIRE ALARM DEVICES AND
SMOKE DETECTORS WILL BE RELOCATED TO BE WITHIN VISUAL SIGHT OF BED PILLOW.
6. ADDRESSABLE SMOKE DETECTORS:
A - DISCONNECT & REMOVE EXISTING ADDRESSABLE SMOKE DETECTOR DEVICES.
B - PROVIDE ADDRESSABLE SMOKE DETECTOR THAT IS COMPATIBLE WITH EXISTING BUILDING FIRE ALARM SYSTEM
C - PROVIDE REMOTE SMOKE DETECTOR STROBE DEVICE PER PLAN, CONNECTED TO BUILDING SMOKE DETECTOR SYSTEM THROUGH
ORIGINAL SMOKE DETECTOR HORN DEVICE WIRING
D - IF EXISTING SMOKE DETECTORS AND STROBES ARE ADDRESSABLE, NEW SMOKE DETECTORS WILL BE ADDRESSABLE. IF EXISTING
SMOKE DETECTORS ARE HARD WIRED WITHIN ROOMS ONLY, GC TO VERIFY WITH LOCAL FA VENDOR IF LOCAL JAA REQUIRES SMOKE
DETECTORS & STROBES TO BE MADE ADDRESSABLE OR HARD WIRED.
E - SUITE ROOMS TO HAVE REMOTE SMOKE DETECTOR STROBES IN ALL LIVING ROOM AREAS AND BEDROOMS.
DEVICES FOR HI UPGRADES:
SD
EP
SDS
SMOKE STROBE, REMOTE PROVIDE REMOTE STROBE CONNECTED TO SMOKE
DETECTOR
SS
CORRIDOR SIDE OF DOOR
3'-10"
DOORBELL
FINISHED FLOOR
DOORBELL
DISABLE KEY
SWITCH
H
A A
DDS
J T
J
PB
TRANSFORMER LOCATION
MAY VARY BY ROOM TYPE.
ALWAYS ENDEAVOR TO HIDE
FROM GUEST VIEW WHILE
PROVIDING VENTILATION AND
ACCESS FOR MAINTENANCE.
LOCATE DOORBELL DISABLE
SWITCH NEXT TO WELCOME
LIGHT SWITCH - DO NOT GANG
BOX. PROVIDE SEPARATE
LABELED COVERPLATE (TYPICAL)
A446b
H
A
A DDS
J
T
TRANSFORMER LOCATION
MAY VARY BY ROOM TYPE.
ALWAYS ENDEAVOR TO HIDE
FROM GUEST VIEW WHILE
PROVIDING VENTILATION AND
ACCESS FOR MAINTENANCE.
LOCATE DOORBELL DISABLE
SWITCH NEXT TO WELCOME
LIGHT SWITCH - DO NOT GANG
BOX. PROVIDE SEPARATE
LABELED COVERPLATE (TYPICAL)
J
PB
UP TO LOFT LEVEL
6C 2D
2D
H
A A
FROM LOWER LEVEL
A445b
2B
5B
2D
1
A 2 3 4 5 6 A B C D E
1
3 4 5 6
2
COPYRIGHT 2016 BASKERVILL. USE OF THIS WORK IN WHOLE OR
IN PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN
CONSENT.
B C D E
DRAWING NO.
P.O. BOX 400, RICHMOND, VA 23218-0400
DRAWING TITLE
ISSUE
PROJECT
OWNER
®
10/12/2016
6:08:16 PM
HEARING IMPAIRED
ROOM TYPES -
PLANS, ELEVATION &
LEGEND
THE WIDEWATERS
GROUP
2.160036.0
DOUBLETREE VAIL,
CO CONVERSION
GUESTROOMS &
PUBLIC SPACES
RENOVATION
08/25/2016 -
CONSTRUCTION
DOCUMENTS
A003
2211 N FRONTAGE
RD, VAIL, COLORADO
81657
1. DISCONNECT & REMOVE ONLY HI-CF DEVICES AND ALL ASSOCIATED WIRING.
2. PROVIDE BLANK COVER PLATES FOR REMAINING BACK BOXES.
ALTERNATE: REMOVE BACK BOX AND PATCH WALL & FINISH TO MATCH EXISTING.
3. DO NOT RE-USE ANY HEARING IMPAIRED DEVICES REMOVED FOR
DECOMMISSIONING.
HI-CF DECOMMISSIONING NOTES:
WHERE HI-CF ROOM IS DESIGNATED TO BE DECOMMISSIONED:
ABBREVIATIONS:
HI - CF: HEARING IMPAIRED - COMMUNICATION FEATURE
HI - FA: HEARING IMPAIRED - FIRE ALARM
SCALE: 3/8" = 1'-0"
2DTYP DEVICE MOUNTING HEIGHTS
PLAN SHOWS NEW DEVICES ONLY, UNLESS
OTHERWISE NOTED.
SCALE: 3/8" = 1'-0"
2ETYP DEVICE MOUNTING HEIGHTS
SCALE: 1/4" = 1'-0"
2AKING/ QUEEN QUEEN/ KING SUITE HI-CF UPGRADE PLAN (TYPICAL)
SCALE: 1/4"
= 1'-0"
4AKING CONDO LOWER LEVEL HI-CF UPGRADE PLAN (TYPICAL)
SCALE: 1/4" =
1'-0"
6AKING CONDO LOFT LEVEL HI-CF UPGRADE PLAN (TYPICAL)
PLAN SHOWS NEW DEVICES ONLY, UNLESS
OTHERWISE NOTED.
PLAN SHOWS NEW DEVICES ONLY, UNLESS OTHERWISE
NOTED.
10/17/2016
04/06/17