HomeMy WebLinkAboutB16-0266_E001_1491490849.pdfSYMBOL DESCRIPTION
DUPLEX RECEPTACLE, NEMA 5-20R, MOUNT +18" AFF,
SUBSCRIPT 'S' INDICATES CONTROLLED RECEPTACLE,
REFER TO LIGHTING CONTROL SYSTEM DIAGRAM,
SUBSCRIPT 'H' INDICATES HORIZONTAL MOUNT
DUPLEX RECEPTACLE, SPLIT WIRED, NEMA 5-20R, MOUNT
+18" AFF, SUBSCRIPT 'S' INDICATES CONTROLLED RECEPTACLE,
REFER TO LIGHTING CONTROL SYSTEM DIAGRAM, SUBSCRIPT
'H' INDICATES HORIZONTAL MOUNT
SINGLE RECEPTACLE, NEMA 5-20R, MOUNT +18" AFF,
SUBSCRIPT 'S' INDICATES CONTROLLED RECEPTACLE,
REFER TO LIGHTING CONTROL SYSTEM DIAGRAM,
SUBSCRIPT 'H' INDICATES HORIZONTAL MOUNT
GFCI
RECEPTACLE, NEMA 5-20R, MOUNT +18" AFF,
SUBSCRIPT 'S' INDICATES CONTROLLED RECEPTACLE,
REFER TO LIGHTING CONTROL SYSTEM DIAGRAM,
SUBSCRIPT 'H' INDICATES HORIZONTAL MOUNT
QUADRAPLEX RECEPTACLE, NEMA 5-20R, MOUNT +18" AFF,
SUBSCRIPT 'S' INDICATES CONTROLLED RECEPTACLE, REFER TO
LIGHTING CONTROL SYSTEM DIAGRAM
GFCI QUADRAPLEX RECEPTACLE, NEMA 5-20R, MOUNT +18" AFF,
SUBSCRIPT 'S' INDICATES CONTROLLED RECEPTACLE, REFER TO
LIGHTING CONTROL SYSTEM DIAGRAM
SPECIAL PURPOSE RECEPTACLE, NEMA CONFIGURATION AND
MOUNTING AS INDICATED
BRANCH CIRCUIT HOMERUN, HATCH MARKS INDICATE TYPE AND
NUMBER OF CONDUCTORS, DASHED LINES INDICATE UNDER
FLOOR/GROUND ROUTING, PROVIDE 3#12 IN 3/4" CONDUIT
UNLESS OTHERWISE INDICATED.
INDICATES PHASE CONDUCTOR
INDICATES NEUTRAL CONDUCTOR
INDICATES GROUNDING CONDUCTOR
NON-FUSED DISCONNECT SWITCH
FUSED DISCONNECT SWITCH
MANUAL MOTOR STARTER
MAGNETIC MOTOR STARTER
COMBINATION STARTER/DISCONNECT
MOTOR
DUPLEX RECEPTACLE, NEMA 5-20R, FLUSH FLOOR MOUNT
QUADRAPLEX RECEPTACLE, NEMA 5-20R, FLUSH FLOOR MOUNT
FLOOR BOX, FLUSH FLOOR, WITH (2) DUPLEX RECEPTACLES AND
SPACE FOR (2) SINGLE GANG TELECOMMUNICATION OUTLETS
FLOOR BOX, POKE-THRU TYPE WITH (2) DUPLEX RECEPTACLES
AND SPACE FOR TELECOMMUNICATION OUTLETS
JUNCTION BOX
SYSTEM FURNITURE CONNECTION, WALL AND FLOOR MOUNT
PANELBOARD, SURFACE MOUNT
PANELBOARD, RECESS MOUNT
TRANSFORMER, DRY TYPE
PLUG LOAD CONTROLLER, MOUNT IN ACCESSIBLE ABOVE
CEILING SPACE, REFER TO LIGHTING CONTROL SYSTEM
DIAGRAM
DUPLEX RECEPTACLE, NEMA 5-20R, CEILING MOUNT, SUBSCRIPT
'S' INDICATES CONTROLLED RECEPTACLE, REFER TO LIGHTING
CONTROL SYSTEM DIAGRAM
SURFACE RACEWAY, DEVICES AS INDICATED
PLUGMOLD, OUTLET EVERY 12" ON CENTER, ALTERNATE NEMA
5-15R RECEPTACLE WITH USB CHARGING PORT
POWER LEGEND
GENERAL DEMOLITION NOTES
DEMOLITION DRAWINGS ARE PROVIDED AS REFERENCE ONLY. DEMOLITION
DRAWINGS ARE BASED ON NON-DESTRUCTIVE FIELD INVESTIGATION AND
EXISTING DRAWINGS.
VISIT THE PROJECT SITE AND BECOME FAMILIAR WITH EXISTING FIELD
CONDITIONS PRIOR TO PROCEEDING WITH THE WORK.
CLEAN AND REPAIR ALL EQUIPMENT INDICATED FOR REUSE OR SALVAGE.
DISPOSE OF, IN A LEGAL MANNER, ALL MATERIALS INDICATED FOR REMOVAL AND
NOT INDICATED FOR REUSE OR SALVAGE.
MAINTAIN CONTINUITY OF EXISTING BRANCH CIRCUITS AND FEEDERS NOT
INDICATED FOR REMOVAL BUT MAY BE DISTURBED BY THE WORK. REROUTE
CIRCUITS AS REQUIRED DUE TO THE WORK.
EXISTING CONDUIT MAY BE ABANDONED IN THE WALLS, FLOOR SLAB, AND BELOW
GRADE ONLY. REMOVE CONDUITS TO THE SURFACE OF THE WALL/FLOOR AND
PATCH.
REMOVE UNUSED CABLING AND CONDUCTORS ALL THE WAY BACK TO THE
SOURCE.
1.
2.
3.
4.
5.
6.
7.
LIGHTING LEGEND
SYMBOL DESCRIPTION
LIGHT FIXTURE
LIGHT FIXTURE ON EMERGENCY/NON-SWITCHED POWER
LIGHT FIXTURE, WALL MOUNT
LIGHT FIXTURE, WALL MOUNT, ON EMERGENCY/NON-SWITCHED
POWER
LIGHT FIXTURE, POLE MOUNT
EXIT SIGN, WALL MOUNT +90" AFF AND CEILING MOUNT, SHADED
SIDE INDICATES FACE(S) OF SIGN, DIRECTIONAL CHEVRONS AS
INDICATED
EGRESS LIGHT WITH BATTERY PACK, WALL MOUNT +90" AFF
OCCUPANCY SENSOR, DUAL TECHNOLOGY, CEILING MOUNT,
OMNI-DIRECTIONAL AND DIRECTIONAL
PHOTO CELL
LIGHT SWITCH, 120/277-VOLT, 1HP RATED, MOUNT +46" AFF,
SUBSCRIPT INDICATES TYPE OF SWITCH:
3 - 3-WAY
4 - 4-WAY
D - DIMMING
K - KEY OPERATED
M - OCCUPANCY SENSOR
P - PILOT LIGHT
LIGHT SWITCH, LOW VOLTAGE, MOUNT +46" AFF, REFER TO
LIGHTING CONTROL SYSTEM DIAGRAM, SUBSCRIPT INDICATES
TYPE OF SWITCH:
3 - 3-WAY
4 - 4-WAY
D - DIMMING
K - KEY OPERATED
M - OCCUPANCY SENSOR
P - PILOT LIGHT
ROOM CONTROLLER, MOUNT IN ACCESSIBLE ABOVE CEILING
SPACE, REFER TO LIGHTING CONTROL SYSTEM DIAGRAM
LOW VOLTAGE CABLING FOR LIGHTING CONTROL SYSTEM,
REFER TO LIGHTING CONTROL SYSTEM DIAGRAM
SYMBOL DESCRIPTION
CCTV CAMERA
KEYPAD, MOUNT +46" AFF, PROVIDE 3/4" EMPTY CONDUIT TO
ACCESSIBLE ABOVE CEILING SPACE
CARD READER, MOUNT +46" AFF, PROVIDE 3/4" EMPTY CONDUIT
TO ACCESSIBLE ABOVE CEILING SPACE
CARD READER WITH KEYPAD, MOUNT +46" AFF, PROVIDE 3/4"
EMPTY CONDUIT TO ACCESSIBLE ABOVE CEILING SPACE
MAGNETIC LOCK
ELECTRIC STRIKE
ELECTRIC LOCK
GLASS BREAK SENSOR
SECURITY LEGEND
SYMBOL DESCRIPTION
TELECOMMUNICATIONS OUTLET, MOUNT +18" AFF, PROVIDE 1"
EMPTY CONDUIT WITH BUSHING TO ACCESSIBLE ABOVE CEILING
SPACE
TELECOMMUNICATIONS OUTLET, FLUSH FLOOR MOUNT, PROVIDE
1" EMPTY CONDUIT WITH BUSHING TO ACCESSIBLE ABOVE
CEILING SPACE
SOUND SYSTEM SPEAKER, CEILING AND WALL MOUNT
COAXIAL CABLE TELEVISION OUTLET, MOUNT +18" AFF
INTERCOM STATION, MOUNT +46" AFF
19" EQUIPMENT RACK
TELECOMMUNICATIONS OUTLET, CEILING MOUNT, PROVIDE 1"
EMPTY CONDUIT TO ACCESSIBLE ABOVE CEILING SPACE
TELECOMMUNICATIONS LEGEND
GENERAL NOTES
PROVIDE WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE,
LOCAL ORDINANCES, AND AS APPROVED BY THE LOCAL AUTHORITY HAVING
JURISDICTION.
OBTAIN PERMITS AND PAY SUCH FEES AS MAY BE NECESSARY FOR
INSPECTIONS, TESTS, AND OTHER SERVICES NECESSARY FOR THE
COMPLETION OF THE WORK.
PROVIDE LABOR, MATERIAL, AND OTHER SERVICES AS MAY BE NECESSARY TO
PROVIDE A COMPLETE AND FUNCTIONING SYSTEM.
NOTIFY THE ARCHITECT/ENGINEER AND RESOLVE ANY ISSUES EXPERIENCED
DURING THE COURSE OF THE WORK PRIOR TO EXECUTION OF THE WORK.
SUBMIT SHOP DRAWINGS FOR THE FOLLOWING ITEMS:
A. LIGHT FIXTURES
B. PANELBOARDS / CIRCUIT BREAKERS
C. SAFETY SWITCHES
D. TRANSFORMERS
E. WIRING DEVICES
F. CONDUCTORS
G. CONDUIT
H. ALL OTHER ITEMS SPECIFIED BY MODEL NUMBER ON
DRAWINGS
SHOP DRAWINGS MUST BE APPROVED BY ENGINEER PRIOR TO PURCHASE. IF A
SUBSTITUTION IS PROPOSED, BE PREPARED TO PROVIDE SAMPLES FOR
EVALUATION.
PROVIDE MATERIAL WITHIN ONE YEAR OF MANUFACTURE, BEARING A U.L.
LABEL, AND LISTED FOR ITS INSTALLED APPLICATION.
PROVIDE MAJOR COMPONENTS OF THE ELECTRICAL SYSTEM BY THE SAME
MANUFACTURER.
USE MOUNTING HEIGHTS INDICATED ON THE LEGEND EXCEPT WHERE
INDICATED ON THE DRAWINGS. MOUNTING HEIGHTS ARE MEASURED FROM
THE MIDDLE OF WALL MOUNTED DEVICES AND FROM THE BOTTOM OF
PENDENT MOUNTED DEVICES.
ASSEMBLE, HANG, AND CONNECT LIGHTING FIXTURES FURNISHED COMPLETE
WITH SOCKETS, TRIM HANGERS, SUPPORTS, ETC, AS REQUIRED FOR A
COMPLETE INSTALLATION. MOUNT LIGHT FIXTURES SUPPORTED
INDEPENDENTLY OF SUSPENDED CEILING COMPONENTS.
PROVIDE "LOCKING" TYPE DEVICES ON CIRCUIT BREAKERS CONNECTED TO
EMERGENCY LIGHTING, NIGHT LIGHTING, FIRE ALARM, AND SECURITY
SYSTEMS.
IN FINISHED SPACES: FLUSH MOUNT LIGHT SWITCHES, RECEPTACLES, AND
TELECOMMUNICATIONS OUTLETS, ROUTE RACEWAYS CONCEALED.
PROVIDE MOTOR OVERLOAD DEVICES IN STARTERS BASED ON NAMEPLATE
RATING ON THE MOTORS BEING INSTALLED.
PROVIDE "HACR" TYPE CIRCUIT BREAKERS FOR CIRCUITS THAT SERVE
HEATING, AIR CONDITIONING, OR REFRIGERATION EQUIPMENT.
PROVIDE MINIMUM #10 NEUTRAL CONDUCTOR FOR MULTI-WIRE RECEPTACLE
BRANCH CIRCUITS.
PROVIDE SPLICES IN OUTLET OR JUNCTION BOXES ONLY.
PROVIDE UPDATED TYPE WRITTEN CIRCUIT DIRECTORY IN PLASTIC SLEEVE
FOR EACH PANELBOARD AFFECTED BY THE WORK.
PROVIDE U.L. APPROVED FIRE STOP SYSTEMS FOR PENETRATIONS THROUGH
FIRE AND SMOKE PARTITIONS TO MAINTAIN THE RATING OF THE PARTITION.
BOX-IN DEVICES ON FIRE/SMOKE PARTITIONS WITH FIRE RATED MATERIAL.
PROVIDE "AS-BUILT" DRAWINGS TO THE OWNER AT CONTRACT CLOSEOUT.
GUARANTEE WORK AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER
OWNER ACCEPTANCE.
PERFORM ALLWORK IN ACCORDANCE WITH NATIONAL ELECTRIC CODE (2011),
VIRGINIA UNIFORM STATEWIDE BUILDING CODE (2012), ADA STANDARDS FOR
ACCESSIBLE DESIGN (2010), AND CONSTRUCTION AND PROFESSIONAL
SERVICES MANUAL, REV 0 (2013).
CONTRACTOR SHALL COMPLY WITH AND MAINTAIN A COPY OF VIRGINIA STATE
FIRE PROTECTION CODE (2012) AND NFPA 241-2000 "STANDARD FOR
SAFEGUARDING CONSTRUCTION, ALTERATION, AND DEMOLITION OPERATIONS"
ON SITE.
NOTIFY CONSTRUCTION MANAGER, OWNER , FIRE DEPARTMENT, AND
AUTHORITY HAVING JURISDICTION A MINIMUM OF SEVEN DAYS PRIOR TO ANY
FIRE ALARM OR SPRINKLER SYSTEM SERVICE INTERRUPTION. PROVIDE FIRE
WATCH IN ACCORDANCE WITH VIRGINIA STATEWIDE FIRE PREVENTION CODE
(2012), PARAGRAPH 901.7. SERVICE INTERRUPTIONS SHALL BE CONFINED TO
TIMES WHEN THE BUILDING IS NORMALLY UNOCCUPIED.
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
SYMBOL DESCRIPTION
FIRE ALARM VISIBLE NOTIFICATION APPLIANCE, MOUNT STROBE
LENS NOT LESS THAN +80" AFF AND NOT MORE THAN +96" AFF.
STROBE CANDELA RATING AS INDICATED
FIRE ALARM VISIBLE/AUDIBLE NOTIFICATION APPLIANCE, MOUNT
STROBE LENS NOT LESS THAN +80" AFF AND NOT MORE THAN +
96" AFF. STROBE CANDELA RATING AS INDICATED
FIRE ALARM MANUAL PULL STATION, MOUNT +46" AFF
FIRE ALARM SMOKE DETECTOR, CEILING MOUNT
FIRE ALARM HEAT DETECTOR, CEILING MOUNT
FIRE ALARM DUCT SMOKE DETECTOR
FIRE ALARM TAMPER SWITCH
FIRE ALARM FLOW SWITCH
FIRE ALARM PRESSURE SWITCH
FIRE ALARM MONITOR MODULE
FIRE ALARM CONTROL MODULE
FIRE ALARM VISIBLE NOTIFICATION APPLIANCE, CEILING MOUNT,
STROBE CANDELA RATING AS INDICATED
FIRE ALARM VISIBLE/AUDIBLE NOTIFICATION APPLIANCE,
CEILING MOUNT, STROBE CANDELA RATING AS INDICATED
MAGNETIC DOOR HOLD OPEN DEVICE
FIRE ALARM LEGEND
SPECIFICATIONS
RELATED DOCUMENTS
DRAWINGS AND GENERAL PROVISIONS OF THE CONTRACT, INCLUDINGGENERAL
AND SUPPLEMENTARY CONDITIONS AND DIVISION 01 SPECIFICATIONS, APPLY.
260513 - CONDUCTORS AND CABLES
1. PROVIDE COPPER CONDUCTORS, NEMA WC/ICEA S-95-658 TYPE
THHN/THWN-2, TYPE UF, AND TYPE SO.
2. PROVIDE SOLID CONDUCTORS FOR #10 AWG AND SMALLER, STRANDED
FOR #8 AWG AND LARGER.
3. COLOR CODE ALL CONDUCTORS.
260526 - GROUNDING AND BONDING
1. PROVIDE 3/4" DIA X 10'-0" COPPER CLAD GROUND RODS.
2. PROVIDE INSULATED GROUNDING CONDUCTORS WITH ALL FEEDER AND
BRANCH CIRCUITS.
260529 - HANGERS AND SUPPORTS
1. PROVIDE HOT DIP GALVANIZED STEEL SLOTTED SUPPORT SYSTEMS WITH
MFMA-4 FACTORY FABRICATED COMPONENTS FOR FIELD ASSEMBLY.
2. PROVIDE STEEL HANGERS, CLAMPS, AND ASSOCIATED FITTINGS FOR CONDUIT
AND CABLE SUPPORT.
3. ATTACHMENTS
3.1 WOOD - LAG SCREWS.
3.2 CONCRETE - EXPANSION ANCHORS.
3.3 MASONRY - TOGGLE TYPE BOLTS.
3.4 STEEL - BEAM CLAMPS.
3.5 LIGHT STEEL - SHEET METAL SCREWS.
260533 - RACEWAYS AND BOXES
1. METAL CONDUIT
1.1 GRC - COMPLY WITH ANSI C80 AND UL 6.
1.2 EMT - COMPLY WITH ANSI C80.3 AND UL 797.
1.3 FMC - COMPLY WITH UL 1; ZINC-COATED STEEL.
1.4 LFMC - FLEXIBLE STEEL CONDUIT WITH PVC JACKET, COMPLY WITH
UL 360.
1.5 FITTINGS - COMPLY WITH FB 1 AND UL 514B.
1.6 FITTING FOR EMT - STEEL SETSCREW.
2. NON-METALLIC CONDUIT
2.1 PVC, SCHEDULE 40 - COMPLY WITH NEMA TC 2 AND UL 651.
3. APPLICATIONS
3.1 OUTDOORS EXPOSED US GRC, UNDERGROUND USE PVC.
3.2 INDOORS EXPOSED USE GRC, CONCEALED US EMT.
3.3 CONNECTION TO VIBRATING EQUIPMENT US LFMC OR FMC.
3.4 PROVIDE MINIMUM 3/4" RACEWAYS.
3.5 PROVIDE PULL STRING IN ALL EMPTY CONDUITS.
260553 - IDENTIFICATION
1. PROVIDE LAMINATED ACRYLIC PLASTIC SIGNS FOR ALL EQUIPMENT,
ENGRAVED LEGEND WITH BLACK LETTERS ON WHITE FACE, PUNCHED OR
DRILLED FOR MECHANICAL FASTENERS.
2. PROVIDE SIGNS DESIGNATING EQUIPMENT IDENTIFICATIONS, SYSTEM VOLTAGE
AND PHASE, AND PPE WARNING.
3. FOR EXTERIOR APPLICATIONS PROVIDE UV STABILIZED SIGNS.
262200 - LOW VOLTAGE TRANSFORMERS
1. DRY TYPE, COPPER COIL, 115 DEGREE RISE, VENTILATED TRANSFORMERS
WITH GRAY FINISH.
2. MOUNT WITH VIBRATION DAMPENING SUPPORTS.
262416 - PANELBOARDS
1. COMPLY WITH NEMA PB 1 AND NFPA 70.
2. ENCLOSURE - FLUSH AND SURFACE MOUNT GALVANIZED STEEL DEAD FRONT
CABINETS RATED FOR ENVIRONMENTAL CONDITIONS AT INSTALLED
LOCATION.
3. HARD DRAWN COPPER, 98 PERCENT CONDUCTIVITY PHASE, NEUTRAL, AND
GROUND BUSES.
4. MECHANICAL TYPE LUGS.
5. PROVIDE MOUNTING BRACKETS, BUS CONNECTIONS, FILLER PLATES AND
NECESSARY APPURTENANCES REQUIRED FOR FUTURE DEVICE.
6. ASSEMBLY FULLY RATED AND NRTL LISTED FOR 100 PERCENT INTERRUPTING
CAPACITY.
7. PROVIDE THERMAL MAGNETIC CIRCUIT BREAKERS WITH STANDARD TRIP
RATINGS AND NUMBER OF POLES, MECHANICAL LUGS AND LISTED FOR
INTERRUPTING CAPACITY TO MATCH PANELBOARD.
8. PROVIDE TYPE WRITTEN CIRCUIT DIRECTORY CARD INSIDE DOOR,
TRANSPARENT CARD HOLDER, IDENTIFYING SPECIFIC PURPOSE WITH
SUFFICIENT DETAIL TO DISTINGUISH IT FROM ALL OTHER CIRCUITS, USE
OWNER'S FINAL SPACE DESIGNATIONS.
9. MOUNT TOP OF TRIM AT +90" AFF.
262726 - WIRING DEVICES
1. RECEPTACLES - COMPLY WITH NEMA WD 1 AND WD 6, AND UL 498, 125V,
20A RATED.
2. TOGGLE SWITCHES - COMPLY WITH NEMA WD 1, UL 20, AND FS W-S-896.
3. PROVIDE WHITE DEVICES WITH .035" THICK SATIN FINISHED TYPE 302
STAINLESS STEEL COVERPLATES IN FINISHED SPACES. PROVIDE CASEALUMINUM
COVERPLATES IN WET AND DAMP LOCATIONS.
262816 - ENCLOSED SWITCHES AND CIRCUIT BREAKERS
1. FUSIBLE SWITCHES - TYPE HD, SINGLE THROW, LOCKABLE HANDLE,
MECHANICAL TYPE LUGS.
2. NON-FUSIBLE SWITCHES - TYPE HD, SINGLE THROW, LOCKABLE HANDLE,
MECHANICAL TYPE LUGS.
3. MCCB - PROVIDE THERMAL MAGNETIC CIRCUIT BREAKER WITH STANDARD
TRIP RATINGS AND NUMBER OF POLES, MECHANICAL LUGS AND LISTED
FOR INTERRUPTING CAPACITY TO COMPLY WITH AVAILABLE FAULT CURRENT.
4. ENCLOSURE - COMPLY WITH NEMA AB 1, NEMA KS 1, NEMA 250, AND UL 50.
4.1 INDOOR DRY AND CLEAN LOCATIONS - NEMA 250 TYPE 1.
4.2 OUTDOOR LOCATIONS - NEMA 250 TYPE 3R.
4.3 OTHER WET OR DAMP LOCATIONS - NEMA 250 TYPE 4.
265116 - FLUORESCENT INTERIOR LIGHTING
1. COMPLY WITH UL 1598 AND ANSI C81.61.
2. PROVIDE ELECTRONIC BALLASTS, UL 935, ANSI C82.11, CLASS A SOUND
RATING, 10% THD, 42KHz OPERATING FREQUENCY, BALLAST FACTOR: 0.88
OR HIGHER, 0.95 POWER FACTOR OR HIGHER.
3. EMERGENCY FLUORESCENT POWER UNIT - INTERNAL TYPE, MODULAR BATTERY-
INVERTER TO OPERATED ONE LAMP AT 1100 LUMEN OUTPUT, SEALED NI-CAD
BATTERY.
4. LAMPS - 3500 DEGREE K, 20,000 HOURS AVERAGE LIFE, CRI: 85 OR HIGHER.
265119 - LED INTERIOR LIGHTING
1. COMPLY WITH NEMA LE 4 AND ANSI C79.1 AND C81.61.
2. MINIMUM CRI: 80, CCT: 3000 DEGREES K, L70 LAMP LIFE: 50,000 HOURS.
265617 - FLUORESCENT EXTERIOR LIGHTING
1. COMPLY WITH UL 1598 AND ANSI C81.61.
2. PROVIDE ELECTRONIC BALLASTS, UL 935, ANSI C82.11, CLASS A SOUND
RATING, 10% THD, 42KHz OPERATING FREQUENCY, BALLAST FACTOR: 0.88
OR HIGHER, 0.95 POWER FACTOR OR HIGHER.
265619 - LED EXTERIOR LIGHTING
1. COMPLY WITH NEMA LE 4 AND ANSI C79.1 AND C81.61.
2. MINIMUM CRI: 80, CCT: 3000 DEGREES K, L70 LAMP LIFE: 50,000 HOURS.
283111 - FIRE ALARM
1. SYSTEM DESCRIPTION
1.1 PROVIDE ALL COMPONENTS COMPATIBLE WITH AN OPERATE AS AN
EXTENSION OF EXISTING SYSTEM. PROVIDE MANUFACTURER'S
CERTIFICATION THAT ALL COMPONENTS
PROVIDED HAVE BEEN TESTED AS, AND WILL OPERATE
AS, A SYSTEM.
1.2 NON-CODED UL-CERTIFIED ADDRESSABLE SYSTEM WITH
MULTIPLEXED SIGNAL TRANSMISSION AND VOICE HORN/STROBE
EVACUATION.
1.3 ALL COMPONENTS LISTED FOR USE WITH SELECTED SYSTEM,
LISTED AND LABELED AS DEFINED IN NFPA 70 BY QUALIFIED
TESTING AGENCY.
2. FIRE ALARM CONTROL UNIT
2.1 FIELD PROGRAMMABLE, MICROPROCESSOR BASED, MODULAR,
POWER LIMITED DESIGN WITH ELECTRONIC MODULES, COMPLY
WITH UL 864.
2.2 ADDRESSABLE INITIATION DEVICE CIRCUITS.
2.3 ADDRESSABLE CONTROL CIRCUITS.
2.4 ALPHANUMERIC DISPLAY AND SYSTEM CONTROLS: DISPLAY ALARM,
SUPERVISORY, AND COMPONENT STATUS MESSAGES AND
THE PROGRAMMING AND CONTROL MENU.
2.5 PRIMARY POWER: 24VDC OBTAINED FROM 120V AC SERVICE AND
POWER SUPPLY MODULE.
2.6 SECONDARY POWER: 24VDC SUPPLY SYSTEM WITH SEALED LEAD
CALCIUM BATTERIES, AUTOMATIC BATTERY CHARGER, AND
AUTOMATIC TRANSFER SWITCH.
3. MANUAL FIRE ALARM BOXES
3.1 COMPLY WITH UL 38, FINISH IN RED WITH MOLDED RAISED LETTER
OPERATING INSTRUCTIONS IN CONTRASTING COLOR.
3.2 DOUBLE ACTION MECHANISM, PULL LEVER TYPE WITH INTEGRAL
ADDRESSABLE MODULE.
3.3 STATION RESET: KEY OR WRENCH OPERATED SWITCH.
4. SYSTEM SMOKE DETECTORS
4.1 COMPLY WITH UL 268, OPERATING AT 24V DC NOMINAL WITH
INTEGRAL ADDRESSABLE MODULE.
5. HEAT DETECTORS
5.1 COMPLY WITH UL 521.
5.2 ACTUATED BY EITHER FIXED TEMPERATURE OF 135 DEGREES F OR
RATE OF RISE THAT EXCEEDS 15 DEGREES F PER MINUTE.
6. NOTIFICATION APPLIANCES
6.1 INDIVIDUALLY ADDRESSED AND CONNECTED TO A SIGNALING LINE
CIRCUIT.
6.2 HORNS: COMPLY WITH UL 464, PRODUCE SOUND PRESSURE LEVEL
OF 90dBA MEASURED 10 FEET FROM HORN, USING CODED
SIGNAL PRESCRIBED IN UL 464 TEST PROTOCOL.
6.3 VISIBLE NOTIFICATION APPLIANCES: XENON STROBE LIGHTS
COMPLY WITH UL 1971 WITH CLEAR NOMINAL WHITE
POLYCARBONATE LENS.
6.3.1 LIGHT OUTPUT: 15/30/75/110 DC SELECTABLE IN THE FIELD.
6.3.2 FLASHING IN TEMPORAL PATTERN, SYNCHRONIZED WITH
OTHER UNITS.
6.4 VOICE/TONE NOTIFICATION APPLIANCES
6.4.1 COMPLY WITH UL 1480.
6.4.2 HIGH RANGE UNITS: RATED 2 TO 15 W.
6.4.3 LOW RANGE UNITS: RATED 1 TO 2 W.
7. MAGNETIC DOOR HOLDERS
7.1 ELECTROMAGNETS REQUIRE MAXIMUM 3W TO DEVELOP 25 LBF
HOLDING FORCE.
8. REMOTE ANNUNCIATOR
8.1 MATCH FUNCTIONS TO FIRE ALARM CONTROL UNIT FOR ALARM,
SUPERVISORY, AND TROUBLE INDICATIONS, AND MANUAL
SWITCHING FUNCTIONS.
8.2 ALPHANUMERIC DISPLAY AND LED INDICATING LIGHTS.
9. SUBMITTAL REQUIREMENTS
9.1 SUBMIT SHOP DRAWINGS AND PRODUCT DATA TO THE AUTHORITY
HAVING JURISDICTION FOR APPROVAL. SUBMIT APPROVED
DRAWINGS AND DATA TO ARCHITECT.
9.2 SHOP DRAWINGS AND PRODUCT DATA SHALL BE PREPARED BY PERSONS
TRAINED AND CERTIFIED BY MANUFACTURER IN FIRE ALARM SYSTEM
DESIGN AND LICENSED OR CERTIFIED BY AUTHORITIES HAVING
JURISDICTION.
9.3 PRODUCT DATA SHALL INCLUDE:
9.3.1 CONSTRUCTION DETAIL, MATERIAL DESCRIPTIONS, DIMENSIONS,
PROFILES, AND FINISHES.
9.3.1 RATED CAPACIEITES, OPERATING CHARACTERISTICS, AND
ELECTRICAL CHARACTERISTICS.
9.4 SHOP DRAWINGS SHALL INCLUDE:
9.4.1 PLANS, ELEVATIONS, SECTIONS, DETAILS, AND ATTACHEMENTS
TO OTHER WORK.
9.4.2 DETAILS OF EQUIPMENT ASSEMBLIES AND SUPPORT
REQUIREMENTS.
9.4.3 VOLTAGE DROP CALCULATIONS FOR NOTIFICATION APPLIANCE
CIRCUITS.
9.4.4 BATTERY SIZE CALCULATIONS
9.4.5 STATEMENT FROM MANUFACTURER THAT ALL EQUIPMENT AND
COMPONENTS HAVE BEEN TESTED AS A SYSTEM AND
COMPLY WITH NFPA 72.
PROJECT INFORMATION
PROJECT DESCRIPTION:
[ KEEP IT VERY BRIEF ]
APPLICABLE CODES:
VIRGINIA UNIFORM STATEWIDE BUILDING CODE, 2012 EDITION
NATIONAL ELECTRICAL DOCE, 2011 EDITION
INTERNATIONAL ENERGY CONSERVATION CODE, 2012 EDITION
YEAR CONSTRUCTED: [ YYYY ]
EXISTING USE GROUP: [ USE GROUP ]
CONSTRUCTION CLASSIFICATION: [ CLASSIFICATION ]
NUMBER OF STORIES: [ # ]
BUILDING HEIGHT" [ __'-__" ]
PROJECT AREA: [ ____ SQFT ]
TOTAL BUILDING AREA" [ ____ SQFT ]
PROJECT: [ NOT IN A FLOOD PLAIN ]
FIRE RESISTANCE RATING: [ NO FIRE PENETRATIONS ]
OCCUPANCY: [ # ]
CHANGE OF USE: [ YES ] [ NO ]
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
DRAWING NUMBER
E001
E101
E102
E111
E112
E121
E122
E131
E132
E401
E501
E601
DRAWING TITLE
LEGEND AND SPECIFICATIONS
FIRST FLOOR PLAN DEMOLITION
SECOND FLOOR PLAN DEMOLITION
FIRST FLOOR PLAN LIGHTING
SECOND FLOOR PLAN LIGHTING
FIRST FLOOR PLAN POWER
SECOND FLOOR PLAN POWER
FIRST FLOOR PLAN FIRE ALARM
SECOND FLOOR PLAN FIRE ALARM
LARGE SCALE PLANS
DETAILS
SCHEDULES AND DIAGRAMS
ELECTRICAL DRAWING LIST
1P SINGLE POLE
2P DOUBLE POLE
3P THREE POLE
1PH SINGLE PHASE
3PH THREE PHASE
A AMPERES
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
AMP AMPERE
AUTO AUTOMATIC
A/V AUDIO / VISUAL
AWG AMERICAN WIRE GAUGE
BFC BELOW FINISHED CEILING
BFG BELOW FINISHED GRADE
C CONDUIT
CATV CABLE TELEVISION
CB CIRCUIT BREAKER
CCTV CLOSED CIRCUIT TELEVISION
CF COMPACT FLUORESCENT
CKT CIRCUIT
C/T CURRENT TRANSFORMER
CU COPPER
DEMO DEMOLITION
DISC DISCONNECT
ELEC ELECTRICAL
ELTG EXTERIOR LIGHTING
EM EMERGENCY
EQ EQUIPMENT
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FT FEET
FVNR FULL VOLTAGE NON-REVERSING
G GROUND
GFCI GROUND FAULT CIRCUIT INTERRUPTING
GFI GROUND FAULT INTERRUPTING
GND GROUND
HP HORSE POWER
IAW IN ACCORDANCE WITH
ILTG INTERIOR LIGHTING
IN INCHES
KCMIL KILO CIRCULAR MILLS
KVA KILO VOLT AMPS
KW KILO WATTS
KWH KILO WATT HOURS
LED LIGHT EMITTING DIODE
LTG LIGHTING
LTS LIGHTS
MCC MOTOR CONTROL CENTER
MISC MISCELLANEOUS
MTD MOUNTED
MTR MOTOR
N NEUTRAL
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NO. NUMBER
P/BD PANELBOARD
PR PRESENT TO REMAIN
PRI PRIMARY
PVC POLYVINYL CHLORIDE
PWR POWER
RCPT RECEPTACLE
RL RELOCATED
SEC SECURITY
SW SWITCH
SWBD SWITCH BOARD
TELECOM TELECOMMUNICATIONS
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSOR
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTIBLE POWER SUPPLY
V VOLTS
W/ WITH
XFER TRANSFER
XFMR TRANSFORMER
ABBREVIATIONS
S S
J
SF SF
T
C
C
S
SD
H
TS
FS
PS
M
C
F
F
F
KP
CR
M
PC
M M
G
S
H
S
H
S
H
PC
I
I
I
S
H
RATED WALL LEGEND
SYMBOL DESCRIPTION
NON-RATED PARTITION
NON-RATED SMOKE RESISTIVE PARTITION
1 HOUR FIRE BARRIER
1 HOUR SMOKE COMPARTMENT BARRIER
2 HOUR FIRE BARRIER
2 HOUR SMOKE COMPARTMENT BARRIER
2 HOUR FIRE BARRIER
3 HOUR SMOKE COMPARTMENT BARRIER
CK
ML
ES
EL
1
A 2 3 4 5 6 A B C D E
1
3 4 5 6
2
COPYRIGHT 2016 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN
PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
B C D E
DRAWING
NO.
P.O. BOX 400, RICHMOND, VA 23218-0400
DRAWING TITLE
ISSUE
PROJECT
OWNER
®
TOWN OF VAIL USE
7/11/2016
11:08:58 AM
LEGEND, SPECS,
FIXTURE SCHEDULE
& UL DETAILS
THE WIDEWATERS
GROUP
2.160036.0
DOUBLETREE VAIL,
CO CONVERSION
GUESTROOMS &
PUBLIC SPACES
RENOVATION
07/08/16 - PERMIT SET
E001
2211 N FRONTAGE
RD, VAIL, COLORADO
81657
07/11/2016