ZONE 1
ZONE 2
26.31
ZONE 3
26.45 26.31
LTG-403
LTG-403
LTG-403
LTG-403
26.58
LLF
MOTORIZED
SCREEN SWITCH
+42" +42" +42"
PR
PR
PR
BALLROOM/
MEETING
ROOM
104
MEETING
STORAGE
153
26.54
26.45
B- 2
B- 4
B- 6
MOUNT RECEPTACLES HORIZONTAL
B- 23
26.31 BD
26.45
26.59
26.107
LLF
1 A 2 3 4 5 6 A B C D E
1
3 4 5 6 2
COPYRIGHT 2016 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN
PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
B C D E
DRAWING NO.
P.O. BOX 400, RICHMOND, VA 23218-0400
DRAWING TITLE
ISSUE
PROJECT
OWNER
®
7/31/2017
9:14:10 AM
ENLARGED PLANS -
BALLROOM
THE WIDEWATERS
GROUP
2.160036.0
DOUBLETREE VAIL,
CO CONVERSION
GUESTROOMS &
PUBLIC SPACES
RENOVATION
08/25/16 -
CONSTRUCTION
DOCUMENTS
E405
2211 N FRONTAGE
RD, VAIL, COLORADO
81657
SCALE: 1/4" = 1'-0" DRAWING REF: E111
3ALIGHTING PLAN - BALLROOM
SCALE: 1/4" = 1'-0" DRAWING REF: E121
6APOWER AND COMMUNICATIONS PLAN - BALLROOM
KEYNOTES
26.31 PROVIDE NEW LIGHTING CONTROLS / PANEL EQUAL TO LUTRON GRAFIK EYE QS.
26.45 CONNECT TO AVAILABLE 20A 1P 120V CIRCUIT MADE AVAILABLE DURING
DEMOLITION OR PROVIDE MATCHING AIC 20A 1P CIRCUIT BREAKER IN AVAILABLE
SPACE OF EXISTING PANELBOARD AS NEEDED. FIELD VERIFY PANEL
DESIGNATIONS AND CIRCUIT AVAILABILITY.
26.54 SAWCUT / TRENCH AND REPAIR FLOOR AS REQUIRED. PROVIDE RECESSED
FLOORBOX WITH RECEPTACLES. CONNECT TO EXISTING RECEPTACLE CIRCUIT
OR AVAILABLE 20A 1P 120V BREAKER.
26.58 PROVIDE JUNCTION BOXES AND LIGHTING CIRCUIT THRU NEW LIGHTING
CONTROLS. INSTALL PENDANT LIGHTING SUPPLIED BY OTHERS AND MAKE ALL
FINAL CONNECTIONS.
26.59 PROVIDE POWER TO RECESSED MOTORIZED SCREEN AS ADD / ALTERNATE.
26.107 PROVIDE 400A, 3วพ, 42P PANEL. EXTEND AND CONNECT TO 3P BREAKER IN
SWITCHGEAR WITH (4)#500KCMIL, (1)#2GND - 3 1/2"C. CONTRACTOR TO FIELD
COORDINATE PANEL LOCATION SO THAT PANEL CAN BE USED FOR FUTURE
DEVELOPMENT OF UPSTAIRS LODGING.
1 8/25/2016 FOR CONSTRUCTION SET
4 11/07/2016 ASI #2
9 7/21/17 CCD-05
Notes:
Total Est. Demand... 69 A
Total Conn. Current: 69 A
Total Est. Demand: 24800 VA
Total Conn. Load: 24800 VA
Power 20000 VA 100.00% 20000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 79 A 79 A 55 A
Total Load: 9100 VA 9100 VA 6600 VA
41 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 42
39 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 40
37 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 38
35 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 36
33 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 34
31 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 32
29 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 30
27 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 28
25 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 26
23 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 24
21 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 22
19 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 20
17 SPARE 20 A 1 0 VA 0 VA -- -- SPACE ONLY 18
15 250... 0 VA -- -- SPACE ONLY 16
13
OUTDOOR PATIO INFRARED HEATER 35 A 2
250... 0 VA -- -- SPACE ONLY 14
11 250... 0 VA -- -- SPACE ONLY 12
9
OUTDOOR PATIO INFRARED HEATER 35 A 2
250... 0 VA -- -- SPACE ONLY 10
7 250... 0 VA -- -- SPACE ONLY 8
5
OUTDOOR PATIO INFRARED HEATER 35 A 2
250... 160... 6
3 250... 160...
4
1
OUTDOOR PATIO INFRARED HEATER 35 A 2
250... 160...
3 40 A
PANEL 'T LOCATED IN DUMPSTER
SHED
2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating:
Mounting: Surface Wires: 4 Mains Rating: 400 A
Supply From: Phases: 3 Mains Type:
Location: MEETING STORAGE 153 Volts: 120/208 Wye A.I.C. Rating: VERIFY
Branch Panel: LLF
07/31/2017