HomeMy WebLinkAboutB16-0266_M001_1478900256.pdfHOT WATER
FLOW METER WITH
BALANCING COCK
THERMOMETER
SUPPLY
HOT WATER
RETURN
THREE-WAY AUTOMATIC
CONTROL VALVE
TERMINAL UNIT
HOT WATER COIL
CONCEALED REGULATOR KIT
CEILING DIFFUSER
RIGID DUCTWORK
FLEXIBLE DUCTWORK
SCREWS
AND WIRE (50'-0"
RACK & PINION
FLEXIBLE CASING
MAXIMUM)
OPERATOR
ADJUSTABLE
PRIOR TO INSTALLATION.
1)
SPANNER WRENCH
ROUND DAMPER
COORDINATE EXACT LOCATION OF CEILING MOUNTED CONCEALED REGULATOR WITH ARCHITECT
COVER PLATE
NOTE:
INDOOR AIR HANDLING UNIT SCHEDULE
DESIGNATION AREA SERVED NOTES
MODEL MANUFACTURER SUPPLY
AIR FLOW
RATE
OUTDOOR
AIR FLOW
RATE
EXTERNAL
STATIC
PRESSURE
MOTOR SIZE FAN
DRIVE
SUPPLY FAN DX COOLING
°F W.B.
°F D.B. °F W.B. °F D.B.
ENTERING
AIR CONDITIONS
MAX LEAVING
AIR CONDITIONS
EER
MIN
TOTAL
CAPACITY
MIN
SENSIBLE
CAPACITY
ROWS
HOT WATER HEATING COIL
ENTERING
AIR TEMP
°F D.B.
MIN
LEAVING
AIR
TEMP
°F D.B.
MIN
TOTAL
CAPACITY
GPM MCA
VOLT/PH
ELECTRICAL
AHU-1 BACK OF HOUSE 3,800 RCC154/HCC154 ADDISON 915 CFM 2.25" 5 HP BELT 52.9 53.2 66.1 77.0 156.1 MBH 100.5 MBH 10.7 4 55 85 211 MBH 12.6 1, 2, 3, 4, 5, 6, 7
NOTES:
1. PROVIDE MICROPROCESSOR BASED BACNET CONTROLLER.
2. PROVIDE FACTORY NON-FUSED DISCONNECT.
3. COOLING CAPACITY BASED ON 95°F AMBIENT AIR AND 8,000 FEET ELEVATION.
4. HEATING CAPACITY BASED ON 180°F HEATING WATER.
5. PROVIDE 2" MERV 11 AIR FILTERS AND FILTER DIFFERENTIAL PRESSURE SWITCH.
6. PROVIDE SINGLE POINT POWER CONNECTION.
7. PROVIDE CORRESPONDING OUTDOOR CONDENSING UNIT WITH SEPARATE ELECTRICAL DISCONNECT AND PRE-CHARGED REFRIGERANT LINE KIT.
57.6 208 / 3
VOLTS/PHASE
DESIGNATION MODEL
TYPE SIZE (FEET) GPM
%EFF.
HP RPM
HEAD
MOTOR
NOTES
SERVICE IMPELLER
(INCHES)
RATE
FLOW
208/3 P-1 INLINE B & G E-90 25 6 27 1/2 1800 TERMINAL REHEAT SECONDARY LOOP 1AAB 5
NOTES:
PUMP SCHEDULE
1
1. PUMP SHALL BE ALL BRONZE CONSTRUCTION AND HAVE 316 STAINLESS STEEL SHAFT.
2. PROVIDE DISCONNECT.
2
DESIGNATION SERVICE TYPE AIR PATTERN FINISH FACE SIZE / FRAME MODEL NECK SIZE
AIR DISTRIBUTION DEVICE SCHEDULE
ACCESSORIES
1
NOTES AND ACCESSORIES:
R-1 GRILLE RETURN TITUS PAR
E-1 GRILLE EXHAUST
-
S-1 TWO WAY COLOR BY ARCH SLOT SUPPLY 48" LENGTH TITUS ML-39 1
3 PAINT VISIBLE PLENUM OR DUCTWORK
BEHIND GRILLE FLAT BLACK.
TITUS 350 RL
SEE PLAN
22x22
ADJUST PATTERN CONTROLLERS AS SHOWN.
PROVIDE OPPOSED BLADE DAMPER.
SEE PLAN -
3
S-3 HORIZONTAL SUPPLY SEE PLANS / SURFACE TITUS CT 480 LINEAR BAR SEE PLAN
4 PROVIDE MOUNTING FRAME AS
REQUIRED FOR INSTALLATION. REFER
TO ARCH REFLECTED CEILING PLANS.
3
2
2
3
4
5
4
4
S-4 SUPPLY TITUS 300 RS SEE PLAN 1 2 4
5 2 SLOT, 1 INCH SLOT WIDTH WITH
INSULATED PLENUM BOOT.
S-2 ROUND SUPPLY 24x24 / SURFACE OR LAY-IN TITUS OMNI PLAQUE FACE SEE PLAN 4
COLOR BY ARCH
COLOR BY ARCH
COLOR BY ARCH
COLOR BY ARCH
COLOR BY ARCH
SEE PLANS / SURFACE HORIZONTAL SIDE WALL
SEE PLANS / SURFACE
24x24 / SURFACE OR LAY-IN
E-2 GRILLE TITUS PAR - 22x22 COLOR BY ARCH 24x24 / SURFACE OR LAY-IN EXHAUST 3 4
ELECTRIC WALL HEATER SCHEDULE
LOCATION
EWH-1
DESIGNATION BTU/HR
CAPACITY
PHASE
VOLTS/
KW CFM °F
E.A.T.
AMPS HZ
MOTOR
MODEL NUMBER
MAKE AND
NOTES
27,400 8.0 208 / 1 F30522T2DWB VESTIBULE 400 60 38.5 40
NOTES:
1. PROVIDE WALL MOUNT BRACKET.
2. PROVIDE UNIT MOUNTED DISCONNECT SWITCH.
3. PROVIDE BUILT-IN, TAMPER-PROOF THERMOSTAT.
1 2 3
TERMINAL BOX SCHEDULE
VAV AIR VALVE
DESIGNATION
TERMINAL BOX
MIN.
CFM
MAX.
CFM
INCH DIA.
SIZE
INLET
CFM
IN. W.G.
STATIC
PRESS.
MAX.
EWT
EAT
HOT WATER HEATING COIL
GPM
MAKE MODEL
°F
NOTES / ACCESSORIES
LWT
LAT
°F
°F
°F
WPD
FT WG
MAX.
1
85 165 6
170 540 8
160 160 6
335 855 10
85 160 6
130 430 6
145 475 6
VAV-1 220 500 8 0.25 180 0.5 0.3 DESV TITUS
335 755 8
168
152
157
156
167
158
158
152
144
55.0
55.0
55.0
55.0
55.0
55.0
55.0
55.0
55.0
91.7
85.8
101.7
99.6
95.4
110.0
100.7
97.3
105.0
0.9
PERFORMANCE BASED ON ACCORDANCE WITH ASHRAE 120, AHRI 880, AND ELEVATION OF 8,000 FEET.
1
1
1
1
1
1
1
1
1
2
2
2
2
2
2
2
2
2
2
SPACE TEMPERATURES ARE BASED ON 76°F COOLING /72°F HEATING DURING OCCUPIED HOURS; 85°F COOLING / 65°F HEATING DURING
UNOCCUPIED HOURS. PROVIDE WITH WIRELESS, STAND-ALONE CONTROLLER COMPATIBLE WITH THE AHU AND USING BACNET PROTOCOL.
VAV-2
VAV-3
VAV-4
VAV-5
VAV-6
VAV-8
VAV-9
VAV-7
DESV
TITUS
DESV
TITUS
DESV
TITUS
DESV
TITUS
DESV
TITUS
DESV
TITUS
DESV
TITUS
DESV
TITUS
85
170
160
335
85
130
145
220
335 0.25
0.25
0.25
0.25
0.25
0.25
0.25
0.25
180
180
180
180
180
180
180
180
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
NEW DUCTWORK, PIPING OR EQUIPMENT (SHOWN DARK)
EXISTING DUCTWORK, PIPING OR EQUIPMENT
TO REMAIN (SHOWN LIGHT)
EXISTING DUCTWORK, PIPING OR EQUIPMENT
TO BE REMOVED
ACCESS DOOR
TURNING VANES
DUCT SECTION, SUPPLY
DUCT SECTION, RETURN/OUTSIDE AIR
MOTORIZED DAMPER
DUCT SMOKE DETECTOR
AIR FLOW MEASURING SENSOR
12x12
FIRE DAMPER
SMOKE DAMPER
DUCT SECTION, EXHAUST
12x12
12x12
M
F
S
C
CHECK VALVE
BUTTERFLY VALVE
STEAM PRESSURE REGULATING VALVE
STEAM DRIP TRAP ASSEMBLY
TEE OFF TOP
TEE OFF BOTTOM
FLOW CONTROL VALVE
DIRECTION OF FLOW
PITCH DOWN IN DIRECTION OF ARROW
MANUAL AIR VENT (SEE DETAIL)
AUTOMATIC AIR VENT (SEE DETAIL)
CONCENTRIC REDUCER
ECCENTRIC REDUCER
ELBOW, TURNING DOWN
ELBOW, TURNING UP
DIFFERENTIAL PRESSURE SWITCH
GLOBE VALVE
ISOLATION VALVE
HOSE BIBB DRAIN VALVE
BALL VALVE
UNION
PLUG VALVE
AUTOMATIC VALVE, 3-WAY, PNUEMATIC
AUTOMATIC VALVE, 3-WAY, ELECTRIC/ELECTRONIC
FLEXIBLE PIPE CONNECTOR
AUTOMATIC VALVE, 2-WAY, PNUEMATIC
AUTOMATIC VALVE, 2-WAY, ELECTRIC/ELECTRONIC
RELIEF VALVE
WATER PRESSURE REDUCING VALVE
STRAINER
PIPE GUIDE
PIPE ANCHOR
FLOW METER
PIPE CAP
CARBON DIOXIDE SENSOR (MOUNT 4'-0" A.F.F.)
CARBON MONOXIDE SENSOR (MOUNT 4'-0" A.F.F.)
POINT OF CONNECTION, NEW TO EXISTING
REMOVE TO THIS POINT
DP
CO
AAV
MAV
DUCTWORK WITH LINER
VOLUME DAMPER
TRANSITION, FLAT ON TOP
SPLITTER DAMPER
SUPPLY AIR DEVICE
COUNTERBALANCED BACKDRAFT DAMPER
TRANSITION, FLAT ON BOTTOM
FOT
FOB
FLEXIBLE DUCT CONNECTION
FLEXIBLE DUCT
12x12 S-1
300 CFM
RETURN AIR DEVICE
12x12 R-1
300 CFM
EXHAUST AIR DEVICE
12x12 E-1
300 CFM
HUMIDITY SENSOR (MOUNT 4'-0" A.F.F.)
H
THERMOSTAT (MOUNT 4'-0" A.F.F.)
T
TEMPERATURE SENSOR (MOUNT 4'-0" A.F.F.)
TS
BDD
HOT WATER FLOW DIAGRAM
SCALE: NONE
FLUE (TYP)
TO NEAREST
DRAIN (TYP)
PRV
INLET (TYP)
4" HWS
PRV
4" HWR
NOTE: EXISTING BOILERS AND MAIN PIPING SHALL CONTINUE TO BE USED TO
SUPPLY HEATING HOT WATER TO ALL INDOOR EQUIPMENT. THERE ARE NO
CHANGES TO HYDRONIC CONTROLS OR DESIGN TEMPERATURES.
EXISTING
BOILER2
EXISTING PUMP 3
TO
BASEBOARD AND
BUILDING HEATING
EXISTING AIR
SEPARATOR
EXISTING SECONDARY LOOP
TO ADDITIONAL HYDRONIC HEAT EXCHANGER
EXISTING
SECONDARY LOOP TO SNOWMELT HEAT EXCHANGER
EXISTING SECONDARY LOOP
TOSPA HEAT EXCHANGER
REMOVE EXISTING SPA
HYDRONIC SYSTEM. REUSE
MAIN TAP LOCATION FOR NEW
TERMINAL UNIT HEATING
LOOP.
REFER TO NEW LOOP DETAIL
THIS SHEET.
EXISTING
BOILER1
SINGLE DUCT VAV
TERMINAL
BOX (TYPICAL)
NEW REHEAT LOOP HOT WATER FLOW DIAGRAM
SCALE: NONE
NOTE: EXISTING BOILERS AND MAIN PIPING SHALL BE USED TO SUPPLY HEATING HOT
WATER TO ALL NEW VAV BOXES. PROVIDE NEW PIPING AND TAP EXISTING PIPING AS
INDICATED ON FLOW DIAGRAM AND ROUTE AS SHOWN ON FLOOR PLANS. NEW PUMP AND
THREE WAY VALVE SHALL BE INTEGRATED INTO THE EXISTING HEATING CONTROLS SYSTEM.
1" HWS
1" HWS
3/4" HWS AND HWR UNLESS OTHERWISE
NOTED ON FLOOR PLANS
BRANCH ISOLATION
VALVES, TYPICAL AT EACH
TAP FROM MAIN TO
TERMINAL UNIT
PROVIDE HYDRONIC BRIDGE IF NOT TIED INTO END OF RUN AS SHOWN.
1 A 2 3 4 5 6 A B C D E
1
3 4 5 6 2
COPYRIGHT 2016 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN
PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
B C D E
DRAWING
NO.
P.O. BOX 400, RICHMOND, VA 23218-0400
DRAWING TITLE
ISSUE
PROJECT
OWNER
®
TOWN OF VAIL USE
7/11/2016
11:05:07 AM
LEGEND, DETAILS &
SCHEDULES
THE WIDEWATERS
GROUP
2.160036.0
DOUBLETREE VAIL,
CO CONVERSION
GUESTROOMS &
PUBLIC SPACES
RENOVATION
07/08/16 - PERMIT SET
M001
2211 N FRONTAGE
RD, VAIL, COLORADO
81657
NOTES - GENERAL MECHANICAL LEGEND - GENERAL MECHANICAL
1. PROVIDE ALL MATERIALS AND EQUIPMENT AND PERFORM ALL LABOR REQUIRED
TO INSTALL COMPLETE AND OPERABLE MECHANICAL SYSTEMS AS INDICATED
ON THE DRAWINGS, AS SPECIFIED AND AS REQUIRED BY CODE.
2. CONTRACT DOCUMENT DRAWINGS FOR MECHANICAL WORK ARE
DIAGRAMMATIC AND ARE INTENDED TO CONVEY SCOPE AND GENERAL
ARRANGEMENT ONLY.
3. INSTALL ALL MECHANICAL EQUIPMENT AND APPURTENANCES IN ACCORDANCE
WITH MANUFACTURER'S RECOMMENDATIONS, CONTRACT DOCUMENTS AND
APPLICABLE CODES AND REGULATIONS.
4. COORDINATE ALL EQUIPMENT CONNECTIONS WITH MANUFACTURERS'
CERTIFIED DRAWINGS. COORDINATE AND PROVIDE ALL DUCT AND PIPING
TRANSITIONS REQUIRED FOR FINAL EQUIPMENT CONNECTIONS TO FURNISHED
EQUIPMENT. FIELD VERIFY AND COORDINATE ALL DUCT AND PIPING
DIMENSIONS PRIOR TO FABRICATION.
5. WORK SHALL BE ACCURATELY LAID OUT WITH REFERENCE TO THE
ARCHITECTURAL DRAWINGS AND IN COOPERATION WITH OTHER TRADES,
WHICH SHALL AFFORD MAXIMUM ACCESSIBILITY FOR OPERATION,
MAINTENANCE AND HEADROOM. FAILURE TO COORDINATE WORK WITH OTHER
TRADES SHALL NOT BE CONSIDERED AS A BASIS FOR EXTRA COST CHANGES.
6. DIMENSIONS SHOWN ON DRAWINGS FOR DUCTWORK ARE INSIDE CLEAR.
7. ALL DUCTWORK, INCLUDING FIRE DAMPERS, SHALL BE SEALED AND TESTED
FOR LEAKS PRIOR TO COVERING WORK.
8. PATCH ALL CUTTING OR DRILLING OF FINISHED WALLS, CEILINGS AND FLOORS.
9. DIFFUSER AND GRILLE LOCATIONS TO BE COORDINATED WITH ARCHITECTURAL
CEILING PLAN. ANY CEILING MOUNTED DIFFUSERS OR GRILLES WHICH DO NOT
MATCH CEILING TILE SIZES ARE TO BE MOUNTED IN CENTER OF TILE.
10. CONTRACTOR SHALL INSTALL ANY BALANCING DEVICE NECESSARY TO ACHIEVE
PROPER ADJUSTING AND BALANCING OF MECHANICAL SYSTEMS.
11. REFRIGERANT PIPING SHALL BE SIZED IN ACCORDANCE WITH MANUFACTURER'S
RECOMMENDATIONS.
ABBREVIATIONS - GENERAL MECHANICAL
AAV AUTOMATIC AIR VENT
AD ACCESS DOOR
AFMS AIRFLOW MEASURING STATION
BDD COUNTERBALANCED BACKDRAFT DAMPER
BFW BOILER FEEDWATER
CD CONDENSATE DRAIN
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CVD REMOTE CABLE CONTROL VOLUME DAMPER
CWR CONDENSER WATER RETURN
CWS CONDENSER WATER SUPPLY
DSD DUCT SMOKE DETECTOR
DV HOSE BIBB DRAIN VALVE
FD FIRE DAMPER
FM FLOW METER
FOB FLAT ON BOTTOM
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FOT FLAT ON TOP
GR GLYCOL RETURN
GS GLYCOL SUPPLY
HPS HIGH PRESSURE STEAM
HRR HEAT RECOVERY RETURN
HRS HEAT RECOVERY SUPPLY
HWR HEATING HOT WATER RETURN
HWS HEATING HOT WATER SUPPLY
LPS LOW PRESSURE STEAM
MAV MANUAL AIR VENT
MPS MEDIUM PRESSURE STEAM
PCR PUMPED CONDENSATE RETURN
PRV PRESSURE REDUCING VALVE
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID
RS REFRIGERANT SUCTION
RV RELIEF VALVE
SD SMOKE DAMPER OR SPLITTER DAMPER
VD VOLUME DAMPER
NOT TO SCALE
6AHOT WATER FLOW DIAGRAM
NOT TO SCALE
4ANEW REHEAT LOOP HOT WATER FLOW
DIAGRAM
NOT TO SCALE 5BHOT WATER COIL DETAIL
SCALE: 12" = 1'-0" 4BREMOTE CABLE OPERATOR DETAIL
07/11/2016
P.O. BOX 400, RICHMOND, VA 23218-0400
®
08/16/16