Loading...
HomeMy WebLinkAboutB16-0266_M202_1498075792.pdfT T K L M N M1 K 206 KA 204 KA 203 K 202 QQMR 205 QQ 207 KMR 208 LAUNDRY 200 CORRIDOR 240 JANITOR 200B KS 201 23.8 6ø CU-5 EF-8 EF-7 LIQUID REFRIGERANT LINE DOWN SUCTION REFRIGERANT LINE DOWN 18x4 S-3 240 CFM (TYP. OF 4) 18x4 S-3 200 CFM (TYP. OF 10) 12x6 12x6 10x8 10x8 16x12 16x12 336" x 4" S-3 BAR DIFFUSER WITH PREMIUM FINISH AS SELECTED BY ARCHITECT. TEN ACTIVE SECTIONS, EACH 18" LONG EXISTING AIR HANDLER AHU-2 TO PROVIDE: 120 MBH HEATING 5 TONS COOLING 2000 CFM SUPPLY AIR 430 CFM OUTSIDE AIR EXISTING AIR HANDLER AHU-1 TO PROVIDE: 120 MBH HEATING 5 TONS COOLING 2010 CFM SUPPLY AIR 430 CFM OUTSIDE AIR CONNECT OA DUCT TO EXISTING INTAKES ON LOW ROOF (TYP. OF 2). CONTRACTOR TO CONFIRM EXISTING LOUVERS HAVE MINIMUM OF 0.75 SQFT OF FREE AREA. 8ø S-1 100 CFM 8ø S-1 100 CFM 4'-0" S-1 100 CFM 4'-0" S-1 100 CFM 4'-0"S-1 100 CFM 4'-0" S-1 100 CFM 8ø S-2 200 CFM 8ø S-2 200 CFM 8ø S-2 200 CFM 8ø S-2 200 CFM 8ø S-2 200 CFM 8ø S-2 200 CFM R-1 785 CFM LOBBY LOUNGE WITH CONNECTIVITY ZONE 102 VESTIBULE 101 SKI BOOT REMOVAL AREA 110 8ø S-2 200 CFM 16x12 8ø 8ø 8ø 10x8 8ø 8ø 8ø 8ø 18x20 24x14 24x14 12x10 12x10 6ø 6ø 8x8 8ø 14x14 8ø 8ø 18x4 18x4 18x4 23.16 23.16 45 DEGREE ELBOWS 18x4 18x4 18x4 18x4 18x4 18x4 18x4 18x4 18x4 18x4 18x4 255" x 4" S-3 BAR DIFFUSER WITH PREMIUM FINISH AS SELECTED BY ARCHITECT. FOUR ACTIVE SECTIONS, EACH 18" LONG 18x12 SEE SHEET A401d IN ARCHITECTURAL PLANS 4'-0" S-1 105 CFM 4'-0" S-1 105 CFM (TYP. OF 2) 4'-0" S-1 105 CFM 8x4 E-1 95 CFM TYP. OF 4 10x6 E-1 95 CFM TYP. OF 4 EF-5 8ø S-2 170 CFM AHU-5, DISCHARGE CONDENSATE TO FLOOR DRAIN IN MECAHNICAL ROOM 10x6 6x6 6x6 20x12 20x8 10x8 6x6 6x6 6x6 10x6 12x10 6x6 6x6 6x10 12x8 8x10 10x10 6ø 14x10 14x10 10ø 8ø 8ø 6x6 8ø 32x12 VAV-9 VAV-6 24x30 24x32 MOTORIZED DAMPERS FOR ECONOMIZER FUNCTIONALITY. SEE CONTROLS NARRATIVE. 23.14 M EMPLOYEE LOCKER ROOM 138 W EMPLOYEE LOCKER ROOM 137 WOMEN'S BATHROOM 139 MEN'S BATHROOM 141 90.00° VAV-9 VAV-6 23.19 23.18 8ø 8ø 8ø 6x10 8ø 6x8 8ø 8ø 4'-0" S-1 105 CFM 8ø VAV-5 10x6 10ø 1 A 2 3 4 5 6 A B C D E 1 3 4 5 6 2 COPYRIGHT 2016 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT. B C D E DRAWING NO. P.O. BOX 400, RICHMOND, VA 23218-0400 DRAWING TITLE ISSUE PROJECT OWNER ® 8/29/2016 4:46:13 PM 1ST FLOOR LOBBY, BATHROOM, AND 2ND FLOOR DUCTWORK PLAN THE WIDEWATERS GROUP 2.160036.0 DOUBLETREE VAIL, CO CONVERSION GUESTROOMS & PUBLIC SPACES RENOVATION 08/25/16 - CONSTRUCTION DOCUMENTS M202 2211 N FRONTAGE RD, VAIL, COLORADO 81657 SCALE: 1/8" = 1'-0" DRAWING REF: E401a 2A2ND FLOOR EQUIPMENT AND DUCTWORK PLAN KEYNOTES GENERAL NOTES 1. REPLACE ALL PTAC UNITS IN GUEST ROOMS (SECOND, THIRD, AND FOURTH FLOORS) WITH EQUIVALENT PTAC UNITS. THE NEW PTAC UNITS MUST SUPPLY 50 CFM OF OUTSIDE AIR. 23.8 PROVIDE NEW EXHAUST FAN TO MATCH EXISTING FANS IN GUEST ROOMS. CONNECT TO EXISTING EXHAUST DUCT IN CHASE. 23.14 CONNECT TO EXISTING LOUVER IN PRECAST WALL. CONTRACTOR TO LOCATE ACTUAL LOCATION IN FIELD. 23.16 COORDINATE DUCT INSTALLATION WITH EXISTING TRUSSES IN LOBBY AREA. 23.18 CONTRACTOR TO VERIFY 24X32" DUCT WILL FIT IN EXISTING PRECAST CONCRETE WALL OPENING. IF OPENING NEEDS TO BE ENLARGED, CONTRACTOR TO VERIFY STRUCTURAL REQUIREMENTS. 23.19 CONTRACTOR TO VERIFY THAT EXISTING LOUVER HAS MINIMUM 8.5 SQFT OF FREE AREA. OTHERWISE, COORDINATE LOUVER SIZE WITH ENGINEER. SCALE: 1/4" = 1'-0" DRAWING REF: M201 5ALOBBY DUCT LAYOUT SCALE: 1/4" = 1'-0" DRAWING REF: M201 5DBACK OF HOUSE BATHROOM DUCT LAYOUT 1 8/25/2016 Revision 1 08/29/2016 06/21/17