HomeMy WebLinkAboutB16-0266_M701_1491490975.pdfGENERAL
WHEN THE UNIT IS NOT SUPPLYING AIR, THE UNIT ISOLATION DAMPERS SHALL
BE CLOSED.
THE SEQUENCE DESCRIBED BELOW CONSISTS OF THREE MODES: SHUTDOWN,
OCCUPIED COOLING OR HEATING, AND ECONOMIZER.
SHUTDOWN MODE IS INTENDED TO DESCRIBE STOPPING RTU FANS IN AN
ORDERLY MANNER, CLOSING DAMPERS AND INDICATE SHUTDOWN INFORMATION
AT THE CONTROLLER.
OCCUPIED COOLING OR HEATING MODE IS DETERMINED BASED ON THE OCCUPANCY
SCHEDULE AND ADJUSTED BY THE OPTIMAL START PROGRAM FROM THE
CONTROLLER. INITIAL OCCUPANCY SCHEDULE SHALL BE RUNNING 24 HOURS PER
DAY.
SHUTDOWN MODE:
WHEN THE RTU IS INDEXED FOR SHUTDOWN MODE, THE UNITS SUPPLY AND
EXHAUST FANS SHALL STOP. THE RTU EXHAUST AIR DAMPER SHALL OPEN FULLY,
RELIEF AIR, OUTSIDE AIR AND ISOLATION DAMPERS SHALL CLOSE.
COOLING AND HEATING SHALL BE DISABLED DURING SHUTDOWN.
THE SYSTEM SHALL BE INDEXED TO SHUTDOWN MODE IF ANY ONE OR MORE OF
THE FOLLOWING CONDITIONS ARE MET:
● A SHUTDOWN SIGNAL FROM THE CONTROLLER CONSOLE.
● AN ALARM CONDITION FROM THE RTU SUPPLY AND EXHAUST DUCT
SMOKE DETECTOR.
● UPON ALARM CONDITION FROM THE RTU FREEZESTAT.
OCCUPIED MODE:
HEATING OR COOLING:
● AT THE PREDETERMINED OPTIMUM START TIME, AS DETERMINED BY THE OCCUPANCY
SCHEDULE, THE RTU WILL BE ENABLED.
● THE BAS SHALL NEXT COMMAND THE RTU TO RUN AND OPEN THE ISOLATION
DAMPERS.
● SPACE TEMPERATURE AND HUMIDITY SETPOINTS SHALL BE LOCATED IN TWO FLOORS
IN THE CORRIDORS. TEMPERATURE AND HUMIDITY SHALL BE "WORST CASE" SELECTED
AS THE CRITICAL CONTROL POINT.
● WITH BOTH FANS RUNNING, THE OVERALL AIRFLOWS AT CONSTANT VOLUME SHALL
PROVIDE POSITIVE PRESSURE TO THE BUILDING. A BUILDING PRESSURE SENSOR
SHALL BE PROVIDED AS AN AUXILIARY INPUT TO EACH UNIT. THE SENSOR SHALL
MEASURE FROM AN UPPER LEVEL CORRIDOR TO OUTSIDE AMBIENT TO ENSURE A
POSITIVE READING. EACH UNIT'S CONTROLLER SHALL THEN INDICATE WITH A DIGITAL
INDICATION, WHETHER OR NOT THE ASSOCIATED SENSOR IS POSITIVE OR NEGATIVE.
● (MECHANICAL COOLING) ON A RISE IN SPACE AIR TEMPERATURE ABOVE SETPOINT
AND THE HEATING COIL IS DISABLED, COOLING SHALL BE STAGED TO MAINTAIN
TEMPERATURE SETPOINT (ADJ, INITIAL SETPOINT 74 F RESET THE SPACE
TEMPERATURE SET POINT TO 70 F WHENEVER OAT < 35 F, BOTH ADJ.).
● ON A FALL BELOW SPACE AIR TEMPERATURE SETPOINT, AND COOLING IS DISABLED,
THE ELECTRIC HEATING COIL SHALL MODULATE (SCR CONTROL) TO MAINTAIN SPACE
TEMPERATURE SETPOINT.
● HIGH HUMIDITY DISCHARGE CONTROL SHALL BE ACCOMPLISHED VIA THE SPACE
HUMIDITY SENSOR TO MAINTAIN A MAXIMUM HUMIDITY OF 55 PERCENT (ADJ.) AND
ACCOMPLISHED BY COOLING AND HOT GAS REHEAT.
SMOKE SHUTDOWN:
IN THE EVENT THAT SMOKE IS PRESENT IN THE RTU EXHAUST OR SUPPLY AIR DUCT:
● AN AUXILIARY CONTACT IN THE EXHAUST OR SUPPLY AIR DUCT SMOKE DETECTOR
SHALL OPEN DE-ENERGIZING THE AUTO-MAINTAINED POWER SUPPLY TO THE FAN'S
STARTER OR AFD OF THE RTU CAUSING THE FANS TO SHUT OFF.
● THE BAS SHALL SHUT DOWN THE EXHAUST AIR FANS UPON SHUTDOWN OF THE
SUPPLY AIR FANS IN THE UNIT.
● SMOKE DETECTOR CONTACTS SHALL BE WIRED IN SERIES IN THE FAN MOTOR
STARTER CIRCUIT.
● THE MECHANICAL CONTRACTOR SHALL PROVIDE AND TERMINATE THE HARD-WIRED
CONNECTIONS FROM ANY DETECTOR RELAY (PROVIDED BY FIRE ALARM CONTRACTOR
AND INSTALLED BY MECHANICAL CONTRACTOR) TO THE ASSOCIATED FAN TO BE SHUT
DOWN, UNLESS OTHERWISE COORDINATED WITH THE UNIT MANUFACTURER.
● DURING MORNING COOL DOWN THE CHW VALVE SHALL MODULATE OPEN OR CLOSED
TO MAINTAIN DISCHARGE AIR TEMPERATURE AT DISCHARGE TEMPERATURE SETPOINT
(ADJUSTABLE, STARTUP SETPOINT 58 F). THE AHU CONTROLLER SHALL RESET THE
SUPPLY AIR TEMPERATURE SETPOINT 1 F COLDER EVERY 10 MINUTES (ADJUSTABLE)
UNTIL THE SUPPLY TEMPERATURE IS AT THE OPERATING SETPOINT TEMPERATURE
(ADJUSTABLE, INITIAL
SETPOINT 55 F). IF THE RETURN AIR RELATIVE HUMIDITY RISES ABOVE 50%, THE 10
MINUTE CYCLE SHALL REPEAT AT THE SAME TEMPERATURE.
● DURING MORNING WARM-UP THE BAS SHALL MODULATE THE PREHEAT COIL VALVE TO
ACHIEVE DISCHARGE SETPOINT. AFTER THAT DISCHARGE SETPOINT IS ACHIEVED AND
RETURN AIR FROM THE TERMINAL ZONES REACHES THE PREDETERMINED ROOM
SETPOINT (68° F, ADJ), THE BAS SHALL COMMAND THE TWO-POSITION, MINIMUM OA
DAMPER OPEN.
GENERAL NOTE:
1.) TERMINAL UNIT LOOP BRANCH PUMP/LOOP SHALL BE ENABLED WHEN BOILER LOOP IS
ENABLED AND RUNNING.
HOT WATER PUMP:
1.) THE HOT WATER LOOP CONSISTS OF A CONSTANT VOLUME DEDICATED PUMP THAT
SHALL INCORPORATE THREE-WAY MIXING VALVES AT THE TERMINAL UNIT HOT WATER
COILS TO MAINTAIN FLOW AND DISCHARGE TEMPERATURE.
2.) WHEN ENABLED, THE PUMP SHALL RUN CONTINUOUSLY.
3.) THE THREE-WAY MIXING VALVES SHALL BE CONTROLLED TO MAINTAIN SPACE
TEMPERATURE PER ZONE THROUGH THE TERMINAL UNIT CONTROLLER. VALVES SHALL BE
SIZED TO ALLOW CONSTANT FLOW AT THE PUMP.
ECONOMIZER MODE:
● SYSTEM SHALL MONITOR ENTHALPY DIFFERENTIAL BETWEEN RETURN AIR AND
OUTDOOR AIR. WHEN OUTDOOR ENTHALPY IS LESS THAN RETURN AIR ENTHALPY,
ECONOMIZER MODE SHALL BE ENABLED.
● WHEN ECONOMIZER MODE IS ENABLED, OPEN OUTDOOR AIR DAMPER TO 100%
SETTING AND CLOSE THE RETURN AIR TO THE 0% SETTING. COOLING AND HEATING
SHALL BE DISABLED WHEN ECONOMIZER MODE IS ENABLED.
1
A 2 3 4 5 6 A B C D E
1
3 4 5 6
2
COPYRIGHT 2016 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN
PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
B C D E
DRAWING NO.
P.O. BOX 400, RICHMOND, VA 23218-0400
DRAWING TITLE
ISSUE
PROJECT
OWNER
®
8/29/2016
4:46:14 PM
UNIT CONTROLS
THE WIDEWATERS
GROUP
2.160036.0
DOUBLETREE VAIL,
CO CONVERSION
GUESTROOMS &
PUBLIC SPACES
RENOVATION
08/25/16 -
CONSTRUCTION
DOCUMENTS
M701
2211 N FRONTAGE
RD, VAIL, COLORADO
81657
SEQUENCE OF OPERATIONS AHU
VARIABLE AIR VOLUME AIR HANDLER UNIT
SEQUENCE OF OPERATIONS
TERMINAL UNIT HYDRONIC CONTROLS
1 8/25/2016 Revision 1
08/29/2016
04/06/17