HomeMy WebLinkAboutB16-0266_P001_1478900267.pdfCEILING CLEANOUT
CO
FLOOR CLEANOUT
FCO
WALL CLEANOUT
WCO
EXTERIOR CLEANOUT
TEE OFF TOP
TEE OFF BOTTOM
CONCENTRIC REDUCER
ECCENTRIC REDUCER
ELBOW, TURNING DOWN
ELBOW, TURNING UP
GATE VALVE SCREWED OR SOLDERED
GATE VALVE FLANGED
BALL VALVE
UNION
MIXING VALVE
P-TRAP
PIPE CAP
HOSE BIBB
ECO
DIRECTION OF FLOW
PITCH DOWN IN DIRECTION OF ARROW
POINT OF CONNECTION, NEW TO EXISTING
REMOVE TO THIS POINT
NEW PIPING OR EQUIPMENT (SHOWN DARK)
EXISTING PIPING OR EQUIPMENT TO REMAIN (SHOWN LIGHT)
EXISTING PIPING OR EQUIPMENT TO BE REMOVED
MOUNT TO INSIDE
OF CHASE WALL
DISTRIBUTION UNIT
ROUTE 1/2" UNDER FLOOR
TO FLOOR DRAINS
MIFAB MODEL M2-500 TRAP
PRIMER MOUNTED IN
ACCESSIBLE LOCATION
STRAINER
DOMESTIC COLD WATER
BALL VALVE
OFFSET DRAIN TO REUSE
EXISTING SLAB PENETRATION
2" SAN
SHOWER PAN
NEW SHOWER
VALVE
1
A 2 3 4 5 6 A B C D E
1
3 4 5 6
2
COPYRIGHT 2016 BASKERVILL. USE OF THIS WORK IN WHOLE OR IN
PART IS FORBIDDEN WITHOUT EXPRESSED WRITTEN CONSENT.
B C D E
DRAWING NO.
P.O. BOX 400, RICHMOND, VA 23218-0400
DRAWING TITLE
ISSUE
PROJECT
OWNER
®
TOWN OF VAIL USE
7/11/2016
10:40:15 AM
SCHEDULES, LEGEND
& DETAILS
THE WIDEWATERS
GROUP
2.160036.0
DOUBLETREE VAIL,
CO CONVERSION
GUESTROOMS &
PUBLIC SPACES
RENOVATION
07/08/16 - PERMIT SET
P001
2211 N FRONTAGE
RD, VAIL, COLORADO
81657
LEGEND - PLUMBING
ABBREVIATIONS - PLUMBING
WCO WALL CLEANOUT
CO CLEANOUT
CW DOMESTIC COLD WATER
FCO FLOOR CLEANOUT
G NATURAL GAS PIPING
HW DOMESTIC HOT WATER
HWR DOMESTIC HOT WATER RETURN
SAN SANITARY WASTE
V VENT PIPING
NOT TO SCALE
2ATRAP PRIMER DETAIL
PLUMBING FIXTURE CONNECTION SCHEDULE
DESIGNATION ITEM CW HW WASTE VENT REMARKS
PF-1 WATER CLOSET - ADA 1/2" - 4" 2"
PF-2 GUESTROOM FAUCET - ADA 3/8" 3/8" - -
PF-3 GUESTROOM SINK - ADA - - 1 1/2" 1 1/2"
PF-4 SHOWER PAN - - 2" 2"
PF-5 SHOWER CONTROLS/SHOWERHEAD 1/2" 1/2" - -
PF-6
PF-7 BATHTUB - ADA 1/2" 1/2" 2" 2"
PF-8 PUBLIC RESTROOM FAUCET - ADA 3/8" 3/8" - -
PF-9 PUBLIC RESTROOM SINK - ADA - - 1 1/2" 1 1/2"
PF-10 URINAL - ADA 3/4" - 2" 2" WALL-HUNG URINAL - PROVIDE FIXTURE CARRIER
PF-11 PUBLIC RESTROOM WATER CLOSET - ADA 1" - 4" 2" WALL-HUNG WATER CLOSET - PROVIDE FIXTURE
CARRIER
PF-12 PUBLIC RESTROOM ROLL-IN SHOWER - ADA 1/2" 1/2" 2" 2"
PF-13 BREAKROOM SINK 3/8" 3/8" 1 1/2" 1 1/2"
SANITARY WASTE AND VENT PIPING:
MATCH EXISTING WASTE AND VENT PIPING IN ALL RESPECTS
DOMESTIC WATER PIPING:
BELOW FLOOR - TYPE "K" COPPER, SOFT DRAWN (FEDERAL SPECIFICATION WW-T-799). NO FITTINGS BELOW FLOOR.
ABOVE FLOOR - TYPE "L" COPPER, HARD DRAWN (FEDERAL SPECIFICATION WW-T-799). ASSEMBLED WITH WROGHT COPPER TYPE FITTINGS AND 95-5 LEAD-FREE SOLDER.
DOMESTIC WATER BALL VAVLE:
NIBCO NO. 585-70-66-NS, FULL PORT BRONZE BODY, STAINLESS STEEL, NIB-SEAL, INSULATED HANDLE, AND SOLDER ENDS.
NATURAL GAS PIPING
BLACK IRON SCH 40 GAS PIPING
HANGERS AND SUPPORTS:
IN GENERAL, HORIZONTAL PIPING HUNG FROM EXISTING CONSTRUCTION SHALL BE SUPPORTED BY MEANS OF PHILLIPS RED HEAD SELF DRILLING ANCHORS.
GENERALLY, HORIZONTAL PIPING SHALL BE HUNG WITH CLEVIS, SPLIT RING, OR SPLIT STEEL HANGERS, GRINNEL FIGURES NOS. 260, 108, AND 212 RESPECTIVELY. HANGERS SHALL BE
LARGE ENOUGH TO RECIEVE PIPE AND INSULATION. HANGER ROD SIZES SHALL BE AS CATALOG LISTED FOR A SPECIFIED HANGER.
HANGER SPACING SHALL BE AS FOLLOWS:
6' O.C. FOR COPPER PIPE 1 1/4" AND SMALLER
4' O.C. FOR PVC SOIL PIPE
IN ADDITION, HANGERS SHALL BE INSTALLED WITHIN 2' OF EACH CHANGE IN DIRECTION HANGERS SHALL BE LOCATED WITH RESPECT TO BEND SO AS NOT TO HAMPER EXPANSION OR
CONTRACTION.
OTHER FORMS AND ARRANGEMENTS OF HANGERS AND SUPPORTS SHALL BE USED TO ACCOMODATE SPECIAL OR UNUSUAL CONDITIONS OR CONDITIONS NOT COVERED HEREIN,
SUBJECT TO THE APPROVAL OF THE ARCHITECTS AND ENGINEERS.
PIPING INSULATION:
DOMESTIC COLD WATER AND DOMESTIC HOT WATER SHALL BE INSULATED WITH 1" THICK FIBERGLASS SSL-11-2 HEAVY DENSITY SECTIONAL PIPE INSULATION JACKETED WITH
REINFORCED ALL SERVICE VAPOR RETARDER JACKET. JACKET SHALL HAVE A FACTORY-APPLIED DOUBLE PRESSURE SEALING ADHESIVE THAT PROVIDES POSITIVE CLOSURE AND
VAPOR SEALING OF LONGITUDINAL JOINT. JOINTS BETWEEN SECTIONS SHALL BE SEALED WITH BUTT STRIPS. LONGITUDINAL SEAMS IN ALL SERVICE JACKETS SHALL OVERLAP AND
SHALL BE VAPOR SEALED. BUTT JOINTS IN STRAIGHT RUNS SHALL BE VAPOR SEALED AND THE JOINT SHALL BE SEALED WITH A JOINT SEALING STRIP. THE SHEET METAL OVERLAP OF
THE HANGER INSERT SHALL ALSO BE SEALED JOINT SEALING STRIP (COLD PIPE ONLY).
PIPE TESTING:
TEST ALL SOIL, WASTE, AND VENT PIPING IN ACCORDANCE WITH APPLICABLE CODE.
TEST ALL WATER PIPING AT 125 PSI WITH NO LOSS IN PRESSURE FOR 2 HOURS.
PLUMBING SPECIFICATIONS
GENERAL NOTES
1. ALL WORK SHALL BE DONE IN STRICT ACCORDANCE WITH THE REQUIREMENTS OF
ALL LOCAL PLUMBING, HEALTH DEPARTMENT, AND BUILDING CODES, REGULATIONS
AND ORDINANCES.
2. EVERY FIXTURE, DEVICE, APPARATUS, AND PIECE OF EQUIPMENT WHICH CONVEYS,
USES, OR IS ACTIVATED BY WATER SHALL BE OF SUCH DESIGN AND BE INSTALLED
IN SUCH A MANNER THAT THE DOMESTIC WATER SYSTEM IS PROTECTED AGAINST
CONTAMINATION.
3. ALL PLUMBING PIPING SHALL BE COORDINATED WITH OTHER DISCIPLINES,
INCLUDING MECHANICAL DUCTWORK, LIGHT FIXTURES, CONDUITS, AND STRUCTURE,
PRIOR TO PIPING INSTALLATION.
4. PLUMBING CONTRACTOR SHALL FLUSH OUT ALL WATER AND WASTE LINES PRIOR
TO FINAL CONNECTION TO FOODSERVICE EQUIPMENT.
5. PLUMBING CONTRACTOR SHALL INSTALL ALL ACCESSORIES AND FITTINGS
PROVIDED LOOSE WITH FOODSERVICE EQUIPMENT AND MAKE FINAL CONNECTIONS
TO EQUIPMENT.
6. CONTRACTOR SHALL COMPLY WITH CONTRACT DOCUMENTS, INCLUDING
INCORPORATION OF LATEST BRAND STANDARDS.
7. DRAWINGS ARE DIAGRAMMATIC ONLY AND REPRESENT THE GENERAL SCOPE OF
WORK. PLUMBING CONTRACTOR SHALL VERIFY EXISTING CONDITIONS.
8. CLEANOUTS SHALL BE INSTALLED AS INDICATED ON DRAWINGS AND AS PER
APPLICABLE PLUMBING CODE.
NOT TO SCALE
3ATUB TO SHOWER DEMOLITION DETAIL
NOT TO SCALE
4ATUB TO SHWOER NEW WORK DETAIL
FLOOR RECEPTOR SCHEDULE
ITEM BODY MATERIAL
FLASHING AND
ANCHOR FLANGE
SEDIMENT
BUCKET STRAINER HEAD
STRAINER
MATERIAL TOP SHAPE BASIS OF DESIGN
FLD-01 CAST IRON REQUIRED REQUIRED ADJUSTABLE NICKEL-BRONZE ROUND JAY R SMITH SERIES 2050
FSK-01 CAST IRON REQUIRED REQUIRED NON-ADJUSTABL
E
NICKEL-BRONZE SQUARE WITH
1/2 GRATE
JAY R SMITH SERIES 3100