Chamonix Development - Building 6, Unit 28
Air Infiltration Report
Lit
Test Date: March , 2018
BNI uilder: RA Nelson
.° Contact: Jason Kiefer
IiiSite
u Address: 2373 Chamonix Road, Vail, CO 81657
LI Aon Site Visit By: Jason Weingast
Ail t, / ,, . E W.- _.
>a
s
P'ckground
The project goal is to undergo testing at the final point in construction to determine if the unit
meets the 2015 IECC requirements for infiltration. Active Energies was contracted to perform a
final blower door test to determine total air infiltration. The home is permitted under the Town
of Vail and requires blower door testing per the IECC. The blower door testing must show a
tested value of 3 ACH50 or lower in order to comply with the IECC.
Site Observations
Construction of the building envelope was complete. All exterior openings were shut and locked
and interior doors were open. The ERV serves the unit continuously, so it was covered over per
ICC guidelines to eliminate this infiltration. The blower door test was performed in the back
patio door to the unit. The pressure probe was placed outside.
Blower Door Test
The unit was depressurized, utilizing blower door testing equipment to a pressure of-50 Pa. At
the test pressure, the CFM50 was recorded, in order to determine the ACH5o.
The blower door air leakage resulted in the following measurements: 3.0ACHso
Please call with any questions or concerns.
\*A\
Jason Weingast
LEED for Homes Green Rater, HERS Rater
Page 1 of 2 3/8/2018
P.O.Box 1434,Edwards,CO 81632 1 P: 970.306.4237
NORTPENFRGY
NORTH 39 ENERGY/Active Energies, Inc. ACTIVE
Expert Energy Consulting, Training &Verification Services ENERGIES.
Page 2 of 2 3/8/2018
P.O.Box 1434,Edwards,CO 81632 P: 970.306.4237