HomeMy WebLinkAboutB17-0074_A9-04_1495579920.pdf(2) 2X6 SILL PLATE
2X6 SILL PLATE
1" X 4" BASE TRIM, RE: FINISH SCHEDULE
5/8" GYP BD
7/16" FIRE RATED OSB SHEATHING
RE: SYSTEMS BUILT MFR
2" AIR GAP
5/8" GYP BD
(2) 2X12 RIM JOISTS
SPRAY FOAM INSULATION R-21 MIN.
7/8" T&G PLYWOOD SHEATHING
RE: SYSTEMS BUILT MFR
FINISH FLOOR, RE: FINISH SCHEDULE
5/8" GYP BD
7/16" FIRE RATED OSB SHEATHING,
RE: SYSTEMS BUILT MFR
2"
BATT INSULATION FOR FIREBLOCK
BETWEEN MODULES
1-HR WALL
1-HR WALL
2-HR WALL
1-HR WALL
(2) LAYERS 5/8" GYP BD.
7/16" FIRE RATED OSB SHEATHING,
RE: SYSTEMS BUILT MFR
1 3/8" AIR GAP
(2) 2X6 SILL PLATE
5/8" GYP BD.
(2) 2X12 RIM JOISTS
SPRAY FOAM INSULATION, R-21 MIN.
2X10 RIM JOIST
2X4 SILL PLATE
SPRAY FOAM INSULATION, R-21 MIN.
R-11 BLANKET INSULATION W/ NET REST
FOR FIRE BLOCKING BETWEEN JOISTS
7/16" OSB SHEATHING, RE;
SYSTEMS BUILT MFR
1"x4" BASE TRIM, RE: FINISH SCHEDULE
FINISH FLOOR, RE: FINISH SCHEDULE
7/8" T&G PLYWOOD SHEATHING,
RE: SYSTEMS BUILT MFR.
2X6 SILL PLATE
7/16" FIRE RATED OSB SHEATHING,
RE: SYSTEMS BUILT MFR
BATT INSULATION FOR FIREBLOCK
BETWEEN MODULES
(1) LAYER 5/8" GYP BD.
(2) LAYERS 5/8" GYP BD.
7/16" OSB SHEATHING, RE;
SYSTEMS BUILT MFR
2X4 PERIMETER BLOCKING FOR
TRUSS BEARING
TRUSS W/ CONTINUOUS 7/16" FIRE
RATED SHEATHING AIR SPACE SIDE
AND 5/8" GYP. BD. ATTIC SIDE. ALL
JOINTS TO BE TAPED AND ALL
PENETRATIONS TO BE FULLY FIRE
CAULKED
TRUSSED ROOF, RE: STRUCT.
R-49 BATT INSULATION
THROUGHOUT ENTIRE ATTIC SPACE
VENTED
ROOF
2"
2"
BATT INSULATION FOR FIREBLOCK
BETWEEN MODULES
5/8" GYP BD.
7/16" FIRE RATED OSB SHEATHING,
RE: SYSTEMS BUILT MFR
2" AIR GAP
(2) 2X6 SILL PLATE
5/8" GYP BD.
(2) 2X12 RIM JOISTS
SPRAY FOAM INSULATION, R-21 MIN.
2X10 RIM JOIST
2X4 SILL PLATE
SPRAY FOAM INSULATION, R-21 MIN.
R-11 BLANKET INSULATION W/ NET REST
FOR FIRE BLOCKING BETWEEN JOISTS
7/16" OSB SHEATHING, RE;
SYSTEMS BUILT MFR
1"x4" BASE TRIM, RE: FINISH SCHEDULE
FINISH FLOOR, RE: FINISH SCHEDULE
7/8" T&G PLYWOOD SHEATHING,
RE: SYSTEMS BUILT MFR.
2X6 SILL PLATE
2"
7/16" FIRE RATED OSB SHEATHING,
RE: SYSTEMS BUILT MFR
BATT INSULATION FOR FIREBLOCK
BETWEEN MODULES
1-HR WALL 1-HR WALL
2"
5/8" GYP BD.
7/16" FIRE RATED OSB SHEATHING,
RE: SYSTEMS BUILT MFR
2" AIR GAP
(2) 2X6 SILL PLATE
5/8" GYP BD.
2X10 RIM JOIST
7/16" OSB SHEATHING, RE;
SYSTEMS BUILT MFR
2X4 PERIMETER BLOCKING FOR
TRUSS BEARING
GIRDER TRUSS W/ CONTINUOUS
7/16" FIRE RATED SHEATHING AIR
SPACE SIDE AND 5/8" GYP. BD. ATTIC
SIDE. ALL JOINTS TO BE TAPED AND
ALL PENETRATIONS TO BE FULLY
FIRE CAULKED
TRUSSED ROOF, RE: STRUCT.
7/16" FIRE RATED SHEATHING AND
5/8" GYP. BD. HELD TIGHT TO BOTTOM
OF ROOF SHEATHING, FULLY FIRE
CAULK ALL JOINTS
PREMIUM ASHPHALT SHINGLES OVER
ICE AND WATER SHIELD OVER ENTIRE
ROOF OVER ROOF SHEATHING, RE:
STRUCT.
2"
BATT INSULATION FOR FIREBLOCK
BETWEEN MODULES
PROPERTY
LINE
4'-0" 1-HR RATEDSHEATHIN
G
4'-0"1-HR RATEDSHEATHING
1-HR RATED ROOF SHEATHING 4'-0"
EITHER SIDE OF PROPERTY LINE
R-49 BATT INSULATION
THROUGHOUT ENTIRE ATTIC SPACE
UNVENTED
ROOF
VENTED
ROOF
ROOF SHEATHING OVER R-5
CONTINUOUS RIGID INSULATION (VERT
AND HORZ JOINTS OFFSET FROM ROOF
SHEATHING) OVER ROOF SHEATHING
R-19 BATT INSULATION INSTALLED W/
WIRE STAYS OR NETTED CELLULOSE
CEMENT BOARD SOFFIT OVER 7/16"
FIRE RATED SHEATHING ATTACHED
TO BOTTOM OF TRUSS
LAP ICE AND WATER SHIELD OVER
PREFINISHED MTL FLASHING
CONTINUOUS SUB-FASCIA,
RE: STRUCTURAL
CONTINUOUS 2X FASCIA
CONTINUOUS 2X10 FASCIA TRIM
ROOF TRUSS RE: STRUCT
2' - 0"
PROPERTY
LINE
4'-0" 1-HR RATED
SHEATHING
1-HR RATED
SHEATHING
UNVENTED
ROOF
TRUSS W/ CONTINUOUS 7/16" FIRE
RATED SHEATHING AIR SPACE SIDE
AND 5/8" GYP. BD. ATTIC SIDE. ALL
JOINTS TO BE TAPED AND ALL
PENETRATIONS TO BE FULLY FIRE
CAULKED
TRUSSED ROOF, RE: STRUCT.
RAINSCREEN SYSTEM LAP DN
OVER DRIP FLASHING, RE: SPEC.
MIN.
2"
PREMIUM ASHPHALT SHINGLES OVER
ICE AND WATER SHIELD OVER ENTIRE
ROOF OVER OSB SHEATHING, RE:
STRUCT.
1-HR RATED ROOF SHEATHING
4'-0" OF PROPERTY LINE
DRIP FLASHING OVER SIDEWALL
STEP FLASHING
EXTEND ICE & WATER SHIELD MIN.
1'-0" UP WALL
1" R-5 MIN. FOIL FACED
POLYSTYRENE INSULATION OVER
5/8" EXT. GYP BD OVER 7/16" FIRE
RATED SHEATHING, RE: SPEC.
HORZ. STAINED CEDAR SHIP
LAP SIDING, RE: SPEC
PREFINISHED METAL FLASHING
1"
FULLY BLOCK BETWEEN TRUSSES,
7/16" FIRE RATED SHEATHING AND
5/8" GYP. BD. HELD TIGHT TO
BOTTOM OF ROOF SHEATHING,
FULLY FIRE CAULK ALL JOINTS
ROOF SHEATHING OVER R-5
CONTINUOUS RIGID INSULATION (VERT
AND HORZ JOINTS OFFSET FROM ROOF
SHEATHING) OVER ROOF SHEATHING
PREMIUM ASHPHALT SHINGLES
OVER ICE AND WATER SHIELD OVER
ENTIRE ROOF
(2) LAYERS 5/8" GYP BD.
SPRAY FOAM INSULATION, R-21 MIN.
R-19 BATT INSULATION INSTALLED W/
WIRE STAYS OR NETTED CELLULOSE
R-19 BATT INSULATION INSTALLED W/
WIRE STAYS OR NETTED CELLULOSE
RIGID INSULATION HELD TIGHT TO
BOTTOM OF ROOF SHEATHING
(2) 2X6 SILL PLATE
5/8" GYP BD.
2X10 RIM JOIST
(2) 2X6 SILL PLATE
2X6 SILL PLATE
1" X 4" BASE TRIM, RE: FINISH SCHEDULE
(2) LAYERS 5/8" GYP BD
7/16" FIRE RATED OSB SHEATHING
RE: SYSTEMS BUILT MFR
1 3/8" AIR GAP
(1) LAYER 5/8" GYP BD
(2) 2X12 RIM JOISTS
SPRAY FOAM INSULATION R-21 MIN.
7/8" T&G PLYWOOD SHEATHING
RE: SYSTEMS BUILT MFR
FINISH FLOOR, RE: FINISH SCHEDULE
5/8" GYP BD
7/16" FIRE RATED OSB SHEATHING,
RE: SYSTEMS BUILT MFR
2"
BATT INSULATION FOR FIREBLOCK
BETWEEN MODULES
2-HR WALL 1-HR WALL
(2) LAYERS 5/8" GYP BD
PROJECT NUMBER
ISSUE DATE
REVISION
SHEET TITLE
ISSUE
SHEET NO.
KEY PLAN
TOWN STAMP
DISCIPLINE STAMP
FOR REFERENCE
ONLY
4/26/2017
11:06:12 AM C:\Users\lfrazier\Documents\CHAMONIX_Building
Models_lfrazier.rvt
A9.04
DEMISING WALL
DETAILS
14054.1
CHAMONIX - VAIL
FOUNDATION PERMIT
APRIL 26, 2017
1 1/2" = 1'-0"
3 1-HR DEMISING WALL @ LEVEL 2
1 1/2" = 1'-0"
5 2-HR DEMISING WALL @ LEVEL 3
1 1/2" = 1'-0"
2 1-HR DEMISING WALL @ FLOOR LEVEL 3
1 1/2" = 1'-0"
1 1-HR DEMISING WALL @ ROOF
1 1/2"
= 1'-0"
4 2-HR DEMISING WALL @ LOWER/UPPER ROOF
1 1/2" = 1'-0"
9 2-HR DEMISING WALL @ LEVEL 2
No. Description Date
05/23/17