ISSUE LOG KEY:
# DATE
ISSUE LOG
ELECTRICAL SHEET INDEX
TITLE
ELECTRICAL COVER SHEET
E-000
PER MIT SET
08.02.2017
ISSUED AS PART OF A SET
' ' NOT PART OF SET
' ' ISSUED FOR INFORMATION ONLY
*
√
√
√
ELECTRICAL SPECIFICATIONS
E-001
GFCI DUPLEX RECEPTACLE
DUPLEX RECEPTACLE; HALF SWITCHED
ISOLATED GROUND DUPLEX RECEPTACLE
WALL MOUNTED SPECIAL OUTLET AS NOTED
SPECIAL OUTLET AS NOTED
JUNCTION BOX
WALL MOUNTED JUNCTION BOX
FLOOR MOUNTED JUNCTION BOX
DUPLEX RECEPTACLE MOUNTED ABOVE COUNTER
C
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE
FLUSH FLOOR MOUNTED DOUBLE DUPLEX RECEPTACLE
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE; HALF SWITCHED
FLUSH FLOOR MOUNTED DUPLEX RECEPTACLE AND TELECOM
DIVISION 15 EQUIPMENT POWER CONNECTION
FUSED DISCONNECT
NON FUSED DISCONNECT
MOTOR STARTER
ENCLOSED CIRCUIT BREAKER
PULL BOX
PUSH BUTTON
TRANSFORMER
PANELBOARD OR LOADCENTER
CONTACTOR
ELECTRIC MOTOR
METER
THERMOSTAT
ATS
AUTOMATIC TRANSFER SWITCH
ONE-LINE DIAGRAM SYMBOLS
CIRCUIT HOMERUN
CONDUIT RUN
CONDUIT RUN BELOW GRADE
CONDUIT UP
CONDUIT DOWN
DISCONNECT SWITCH
FUSE
CIRCUIT BREAKER
CURRENT TRANSFORMER
POTENTIAL TRANSFORMER
METER
SURGE SUPPRESSION DEVICE
VOLT-METER
SELECTOR SWITCH
GROUND
GF
GROUND FAULT PROTECTION
AMP-METER
ST
SHUNT TRIP
NORMALLY OPEN CONTACT
NORMALLY CLOSED CONTACT
COLD WATER GROUND CONNECTION
BUILDING STEEL GROUND CONNECTION
TIMER SWITCH
MULTI-OUTLET PLUG STRIP
TIME CLOCK
PHOTO-CELL
SWITCH
THERMAL OVERLOAD SWITCH
VARIABLE SPEED SWITCH
KEY SWITCH
LIGHTING FIXTURE SYMBOLS
RECESSED LIGHTING FIXTURE
WALL MOUNTED LIGHT
WALL MOUNTED UP-LIGHT
PENDANT MOUNTED LIGHT
SURFACE MOUNTED LIGHT
DIRECTIONAL/ADJUSTABLE RECESSED LIGHTING FIXTURE
MONO-POINT LIGHTING FIXTURE
RECESSED STEP LIGHT
FLUORESCENT STRIP LIGHT
WALL MOUNTED LINEAR FLUORESCENT LIGHT
RECESSED OR SURFACE MOUNTED FLUORESCENT TROFFER
FIXTURE WITH EMERGENCY BACKUP OR ON EM CIRCUIT
WALL MOUNTED EXIT SIGN W/ FACES & ARROWS AS SHOWN
EMERGENCY LIGHTS
CEILING MOUNTED EXIT SIGN W/ FACES & ARROWS AS SHOWN
SWITCH
THREE-WAY SWITCH
FOUR-WAY SWITCH
DOOR JAMB SWITCH
LIGHTING CONTROL SYMBOLS
EXTERIOR POLE MOUNTED LIGHT
EXTERIOR POST (BOLLARD) MOUNTED LIGHT
DAYLIGHT PHOTO SENSOR
DL
KEY SWITCH
LV
VARIABLE SPEED SWITCH
DIMMER
THREE-WAY DIMMER
LOW VOLTAGE SWITCH
WALL OCCUPANCY SENSOR/SWITCH
THERMAL OVERLOAD SWITCH
OCCUPANCY SENSOR - WALL MOUNTED
OCCUPANCY SENSOR - CORRIDOR CEILING MOUNTED
S
S3
ST
SO
D
3
D
SV
SK
SJ
S4
SK
SV
ST
S
PC
TC
TS
A
V
SS
M
T
C
T
PB
CB
N
--
J
J
J
ABBREVIATIONS
POWER SYMBOLS
SINGLE RECEPTACLE
DUPLEX RECEPTACLE
DOUBLE DUPLEX RECEPTACLE
NOTE:
ALL SYMBOLS SHOWN ON LEGEND ARE
NOT NECESSARILY USED.
OS
OS
OCCUPANCY SENSOR - CEILING MOUNTED
OS
NOTES:
·
LIGHT LINEWEIGHT INDICATES EXISTING.
·
HATCHED AREAS INDICATE DEMOLITION.
· 'C' ADJACENT TO A DEVICE INDICATES
MOUNTING ABOVE COUNTERTOP.
AFC
AFF
AFG
AHJ
- ABOVE FINISHED CEILING
- ABOVE FINISHED FLOOR
- ABOVE FINISHED GRADE
- AUTHORITY HAVING JURISDICTION
AL - ALUMINUM
AWG
AP - ACCESS POINT
- AMERICAN WIRE GAUGE
BFG
BMS
BAS - BUILDING AUTOMATION SYSTEM
- BELOW FINISH GRADE
- BUILDING MANAGEMENT SYSTEM
C
CATV
CCTV
- CONDUIT
- COMMUNITY (CABLE) ANTENNA TELEVISION SYSTEM
- CLOSED CIRCUIT TELEVISION
CKT - CIRCUIT
CPU - CENTRAL PROCESSING UNIT
CT - CURRENT TRANSFORMER
DISP - GARBAGE DISPOSAL
DW - DISHWASHER
(E) - EXISTING
EM - EMERGENCY
EWC - ELECTRIC WATER COOLER
FBO
GFI
FA
FACP
GRD
GC
- FIRE ALARM
- FIRE ALARM CONTROL PANEL
- FURNISHED BY OTHERS
- GENERAL CONTRACTOR
- GROUND FAULT CIRCUIT INTERRUPTER
- GROUND
IAW IN ACCORDANCE WITH
-
IC
IDF
IG
IR
LAN
- INTERMEDIATE CROSS-CONNECT
- INTERMEDIATE DISTRIBUTION FRAME
- ISOLATED GROUND
- INFRARED
- LOCAL AREA NETWORK
NIC
MDF
(N)
MAIN DISTRIBUTION FRAME
-
NEW
-
NOT IN CONTRACT
-
NL
NIGHT LIGHT
-
NTS
NOT TO SCALE
-
OC
PA
ON CENTER
-
PUBLIC ADDRESS
-
REF
REFRIGERATOR
-
TVSS
TTB
TELECOMMUNICATIONS TERMINAL BOARD
-
TRANSIENT VOLTAGE SURGE SUPPRESSOR
-
TVTB
TELEVISION TERMINAL BOARD
-
UG
UNO
W
V
UNDERGROUND
-
UNLESS NOTED OTHERWISE
-
VOLT
-
WATT
-
WP
XP
WAN
WLAN
WAP
WIDE AREA NETWORK
-
WIRELESS ACCESS POINT
-
WIRELESS LOCAL AREA NETWORK
-
WEATHERPROOF
-
EXPLOSIONPROOF
-
+18"
DEVICE ABOVE FINISH FLOOR (VERIFY W/ ARCH ELEVS)
MOUNTING HEIGHT TO CENTERLINE OF
-
ELECTRICAL SYSTEMS LEGEND
L
ELECTRONIC SAFETY & SECURITY SYMBOLS
CEILING MOUNTED CAMERA
WALL MOUNTED CAMERA
MAGNETIC DOOR CONTACT SWITCH
INTRUSION MOTION SENSOR
LIGHTING CONTROL KEYPAD - LOW VOLTAGE
MON
CCTV MONITOR
NVR
NETWROK VIDEO RECORDER
APS
AUXILIARY POWER SUPPLY
ACCESS CONTROL MAIN PANEL
ACP
EXIT PANIC/CRASH BAR SENSOR
REX
SECURITY CENTRAL PROCESSING UNIT
CPU
SECURITY/ACCESS CONTROL WORKSTATION
WS
ADA ACCESS CONTROL MAIN PANEL
ADA
CR
P
CARD READER
S
ELECTRIC LOCK
L
R
ELECTRIC LATCH / ROD RETRACTOR
S
M
MAGNETIC DOOR CONTACT SWITCH
K
I
PANIC BUTTON
P
(S = STRIKE, M = MAGNETIC)
(P = PROXIMITY, S = SWIPE)
TELEVISION OUTLET - FLOORBOX
AUDIOVISUAL OUTLET - CEILING MOUNTED
AUDIOVISUAL OUTLET - WALL MOUNTED
AUDIOVISUAL OUTLET - FLOORBOX
AV
AV
TELEVISON OUTLET - CEILING MOUNTED
TELEVISION OUTLET - WALL MOUNTED
LOUDSPEAKER - CEILING MOUNTED
LOUDSPEAKER - WALL MOUNTED
AUDIOVISUAL SYMBOLS
SPEAKER ZONE HOMERUN
VIDEO PROJECTOR
TV
AV
PROJECTION SCREEN, TELEVISION, OR OTHER DISPLAY EQPT
S
S
TV
TV
LOUDSPEAKER BAR - LEFT/CENTER/RIGHT
LOUDSPEAKER BAR - STEREO
LOUDSPEAKER - POWERED SUBWOOFER
LOUDSPEAKER BAR - CENTER CHANNEL
CTR
LR
LCR
S
VOICE/DATA SYMBOLS
COMBO PHONE/DATA OUTLET
TELEPHONE WALL OUTLET
DATA WALL OUTLET
TELEPHONE FLOOR OUTLET
DATA FLOOR OUTLET
COMBO PHONE/DATA FLOOR OUTLET
DOUBLE TELEPHONE WALL OUTLET
DATA WALL OUTLET
DOUBLE COMBO PHONE/DATA OUTLET
PUBLIC PAYPHONE OUTLET
PP
ELEVATOR PHONE OUTLET
E
WIRELESS LAN (WI-FI) ACCESS POINT OUTLET
FAX/COPIER OUTLET
EMERGENCY SERVICES PHONE OUTLET
EM
F
C
√
ROOM 6103 ELECTRICAL DEMO PLAN
E-104
√
ROOM 6103 ELECTRICAL PLAN
E-105
√
ROOM 6103 LIGHTING DEMO PLAN
EL-104
√
ROOM 6103 LIGHTING PLAN
EL-105
√
ELECTRICAL DIAGRAMS
E-300
√
ELECTRICAL SCHEDULES
E-002
GENERAL NOTES:
1. DO NOT SCALE DRAWINGS. VERIFY DIMENSIONS ON ARCHITECTURAL DRAWINGS AND IN FIELD PRIOR TO COMMENCEMENT OF WORK.
2. VISIT SITE PRIOR TO BID AND VERIFY THAT CONDITIONS ARE AS INDICATED. CONTRACTOR SHALL INCLUDE IN HIS BID COSTS REQUIRED TO
MAKE HIS WORK MEET EXISTING CONDITIONS.
3. SYSTEM OUTAGES SHALL BE PERMITTED ONLY AT TIMES APPROVED BY OWNER - IN WRITING. WORK WHICH COULD RESULT IN AN ACCIDENTAL
OUTAGE (BEYOND BRANCH CIRCUITS) SHALL BE PERFORMED WITH THE OWNER'S MAINTENANCE PERSONNEL ADVISED OF SUCH WORK.
4. SERVICE SHALL BE MAINTAINED TO EXISTING AREAS DURING CONSTRUCTION. CONTRACTOR SHALL PROVIDE PORTABLE GENERATORS,
CABLES, OUTLETS, ETC. AS REQUIRED TO MAINTAIN CONTINUITY OF SERVICE. PLACEMENT OF SUCH PORTABLE EQUIPMENT SHALL BE SUBJECT
TO OWNER APPROVAL.
5. REVIEW ARCHITECTURAL, MECHANICAL AND OTHER DRAWINGS PRIOR TO BID.
6. WORK SHALL BE PERFORMED IN A WORKMANLIKE MANNER TO THE SATISFACTION OF THE ARCHITECT.
7. WORK, MATERIALS, AND EQUIPMENT SHALL CONFORM TO THE LATEST EDITIONS OF LOCAL, STATE, AND NATIONAL CODES AND ORDINANCES.
8. PROVIDE PERMITS AND INSPECTIONS REQUIRED.
9. CONTRACTOR'S FAILURE TO ORDER OR RELEASE ORDER FOR MATERIALS AND/OR EQUIPMENT WILL NOT BE ACCEPTED AS A REASON TO
SUBSTITUTE ALTERNATE MATERIALS, EQUIPMENT, OR INSTALLATION METHODS.
10. EXISTING SYSTEMS AND CONDITIONS SHOWN ON DRAWINGS FOR EXISTING BUILDINGS ARE TO BE NOTED “FOR GUIDANCE ONLY”. THE
ELECTRICAL CONTRACTOR TO FIELD CHECK ALL EXISTING CONDITIONS PRIOR TO BIDDING AND TO INCLUDE IN HIS BID AN ALLOWANCE FOR
REMOVAL AND/OR RELOCATION OF EXISTING CONDUITS, WIRES, DEVICES, FIXTURES, OR OTHER EQUIPMENT AS INDICATED ON THE PLANS OR
AS REQUIRED TO COORDINATE AND ADAPT NEW AND EXISTING ELECTRICAL SYSTEM TO ALL OTHER WORK AS REQUIRED
11. PROVIDE ELECTRICAL DEMOLITION REQUIRED. REFER TO ARCHITECTURAL AND ELECTRICAL DEMOLITION DRAWINGS FOR LOCATION AND
EXTENT OF DEMOLITION REQUIRED. CONTRACTOR SHALL VISIT SITE PRIOR TO BID TO DETERMINE EXTENT OF WORK INVOLVED.
12. PROVIDE ALL NECESSARY DEMOLITION TO REMOVE EXISTING UNUSED CONDUIT, WIRE, CABLE, J-BOXES, RECEPTACLES, SWITCHES, LIGHTS,
FIRE ALARMS DEVICES, ETC. COMPLETE WITH ASSOCIATED CIRCUITING TO SOURCE. WHERE IT IS NOT FEASIBLE TO REMOVE THE ABOVE,
OUTLET SHALL BE ABANDONED, WIRE REMOVED, AND BLANK COVER PLATES PROVIDED.
13. ALL (E) EQUIPMENT, LAMPS, BALLASTS, ETC. BEING REMOVED SHALL BE DISCARDED IN ACCORDANCE WITH APPLICABLE EPA REQUIREMENTS.
14. EXISTING LIGHT FIXTURES, ELECTRICAL EQUIPMENT, ETC. BEING REMOVED SHALL BE RETURNED TO THE OWNER, EXCEPT FOR THOSE ITEMS
BEING RELOCATED.
15. VERIFY EXACT LOCATION OF EQUIPMENT TO BE FURNISHED BY OTHERS PRIOR TO ROUGH-IN.
16. INSTALL ALL MATERIALS IN ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. ANY DEVIATIONS SHALL BE BROUGHT TO THE
ARCHITECT/ENGINEER'S ATTENTION PRIOR TO INSTALLATION.
17. FINAL CONNECTIONS TO EQUIPMENT SHALL BE IN ACCORDANCE WITH MANUFACTURER'S APPROVED WIRING DIAGRAMS, DETAILS, AND
INSTRUCTIONS. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PROVIDE MATERIALS AND EQUIPMENT COMPATIBLE WITH EQUIPMENT
ACTUALLY SUPPLIED.
18. CONTRACTOR SHALL BE RESPONSIBLE FOR REPLACING EQUIPMENT WHICH IS DAMAGED DUE TO INCORRECT FIELD WIRING PROVIDED UNDER
THIS SECTION, OR FACTORY WIRING IN EQUIPMENT PROVIDED UNDER THIS SECTION.
19. ALL ELECTRICAL SYSTEMS COMPONENTS SHALL BE LISTED OR LABELED BY U.L. OR OTHER RECOGNIZED TESTING FACILITY.
20. WIRING DEVICES SHALL BE SPECIFICATION GRADE AND RATED AT 20 AMPERES FOR LIGHT SWITCHES, AND 20 AMPERES FOR DUPLEX
RECEPTACLES. THE COLOR OF THE DEVICES AND COVER PLATES SHALL BE AS DIRECTED BY ARCHITECT.
21. ALL WIRING SHALL BE INSTALLED IN LISTED METALLIC RACEWAYS, UNLESS NOTED OTHERWISE. CONNECTORS SHALL BE INSULATED THROAT
TYPE. MINIMUM RACEWAY SIZE IS 3/4”. ALL FEEDERS SHALL BE INSTALLED IN RACEWAY CONFIGURATIONS SHOWN ON ONE-LINE. BRANCH
CIRCUITS 25A AND LARGER SHALL BE INSTALLED IN INDIVIDUAL RACEWAYS. BRANCH CIRCUITS 20A AND SMALLER MAY BE GROUPED INTO
RACEWAYS AS TO NOT EXCEED 6 CURRENT-CARRYING 75-DEGREE CONDUCTORS, OR 9 CURRENT-CARRYING 90-DEGREE CONDUCTORS, IN A
SINGLE RACEWAY. METAL CLAD CABLE IS NOT PERMITTED.
22. ALL EMPTY RACEWAY SYSTEMS SHALL HAVE A 200LB NYLON PULL STRING OR EQUAL, AND SHALL BE IDENTIFIED AT ALL JUNCTION, PULL AND
TERMINATION POINTS, USING PERMANENT METALLIC TAGS. TAG SHALL INDICATE INTENDED USE OF CONDUIT, ORIGINATION, AND TERMINATION
POINTS OF EACH INDIVIDUAL CONDUIT.
23. WIRE SHALL BE COPPER, 75 DEGREE CELSIUS RATED FOR GENERAL USE. WIRING WITHIN 3 INCHES OF FLUORESCENT BALLASTS WIRE SHALL BE
COPPER, MINIMUM 90 DEGREE CELSIUS RATED. SIZES INDICATED ARE FOR INSTALLATION IN A MAXIMUM 30 DEGREE CELSIUS AMBIENT.
CONDUCTOR AMPACITY SHALL BE DERATED FOR HIGHER AMBIENT INSTALLATIONS.
24. PROVIDE NEW UPDATED PANELBOARD DIRECTORIES FOR EXISTING AND NEW CIRCUITS BEING UTILIZED FOR COMPLETION OF PROJECT.
25. PANEL DIRECTORIES SHALL BE REMOVABLE. ROOM NAMES AND NUMBERS SHALL BE AS DIRECTED BY OWNER. DIRECTORIES SHALL BE TYPED
AND INSTALLED UNDER CLEAR PLASTIC COVERS.
26. FINAL CONNECTIONS TO MOTORS, TRANSFORMERS, AND OTHER VIBRATING EQUIPMENT SHALL BE SEAL TITE FLEX AND APPROVED FITTINGS.
DO NOT SECURE CONDUITS, DISCONNECTS, OR DEVICES TO DUCTWORK OR MECHANICAL EQUIPMENT.
27. FIRE ALARM, SOUND, TELEPHONE, COMPUTER AND SIMILAR SYSTEMS CONDUITS LARGER THAN 1” SHALL HAVE LONG RADIUS SWEEPS (12 TIMES
THE DIAMETER).
28. SYSTEMS SHALL BE TESTED FOR PROPER OPERATION. IF TESTS SHOW THAT WORK IS DEFECTIVE, CONTRACTOR SHALL MAKE CORRECTIONS
NECESSARY AT NO COST TO OWNER.
29. GUARANTEE THE INSTALLATION AGAINST DEFECTS IN MATERIALS AND WORKMANSHIP WHICH MAY OCCUR UNDER NORMAL USAGE FOR A
PERIOD OF ONE YEAR AFTER OWNER'S ACCEPTANCE. DEFECTS SHALL BE PROMPTLY REMEDIED WITHOUT COST TO THE OWNER.
30. SYSTEMS SHALL BE COMPLETE, OPERABLE, AND READY FOR CONTINUOUS OPERATION. LIGHTS, SWITCHES, RECEPTACLES, MOTORS, ETC.
SHALL BE CONNECTED AND OPERABLE.
REVI SION 1
09.05.2017
√
√
√
√
√
√
√
√
PROJ. NO.
DRAWN:
CHECKED:
DATE:
SCALE:
SHEET NUMBER
SHEET TITLE:
ISSUED FOR:
APPROVED:
As indicated
FOUR
SEASONS
RESORT AT VAIL
ONE
VAIL
ROAD
VAIL, CO 81657
8203.11
2017/09/05
ISSUE FOR BUILDING
PERMIT
FOUR SEASONS RESORT
AT VAIL
S:\BGPROJECTS\8203.11
VAIL
FOUR
SEASONS
MODEL
ROOM\DRAWINGS\ROOM
6103\8203.11E000.DWG
09.19.17
9:40:40 AM ALBUQUERQUE | AVON | DENVER | FORT COLLINS
303.278.3820 www˛bgbuildingworks˛com
Project No. 8203.11 Copyright 2017
1
REVISION 1
ELECTRICAL COVER
SHEET
E-000
BAS
MAS
MAS
3003 Larimer Street
Denver, Colorado 80205
phone 303.861.5704
www.ozarch.com
ARCHITECTURE
®
10/04/17